INTRODUCTION u CODES u EXAMPLES code 3 Check Commercial . First Edition By douglas hansen & Redwood Kardon Illustrations & layout by Paddy Morrissey 2010 by The Taunton Press, Inc. ISBN 10 1-60085-082-0 ISBN 13 978-1-60085-082-0. code Check is a trademark of The Taunton Press, Inc., registered in the Patent & Trademark Office. code Check Commercial is a field inspection guide to important code requirements and common code violations in the construction and remodeling of light commercial buildings. It applies to multi-family residential, offices, restaurants, tenant improvements, warehouses, small manufacturing facilities, stores, hotels, and other commercial buildings. This book does not apply to one- and two-family dwellings and townhouses, which are covered in other books in the code Check series, nor does it apply to clinics or high-hazard occupancies (Group H) for manufacturing, processing, or storing combustible or hazardous materials. The citations inside this book would need to be greatly expanded to include these occupancies; they require a licensed design professional.

BUILDING u BUILDING TYPES u SETBACKS 5 CONSTRUCTION TYPES, HEIGHT & AREA LIMITATIONS Chapter 5 of the IBC provides tables that limit the size and height of buildings based upon their

Tags:

  Introduction, Code, Example, 3check, Introduction codes examples code 3check

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of INTRODUCTION CODES EXAMPLES Code 3Check …

1 INTRODUCTION u CODES u EXAMPLES code 3 Check Commercial . First Edition By douglas hansen & Redwood Kardon Illustrations & layout by Paddy Morrissey 2010 by The Taunton Press, Inc. ISBN 10 1-60085-082-0 ISBN 13 978-1-60085-082-0. code Check is a trademark of The Taunton Press, Inc., registered in the Patent & Trademark Office. code Check Commercial is a field inspection guide to important code requirements and common code violations in the construction and remodeling of light commercial buildings. It applies to multi-family residential, offices, restaurants, tenant improvements, warehouses, small manufacturing facilities, stores, hotels, and other commercial buildings. This book does not apply to one- and two-family dwellings and townhouses, which are covered in other books in the code Check series, nor does it apply to clinics or high-hazard occupancies (Group H) for manufacturing, processing, or storing combustible or hazardous materials. The citations inside this book would need to be greatly expanded to include these occupancies; they require a licensed design professional.

2 This book helps streamline access to relevant information in the CODES that apply to commercial construction. It is not intended to replace those CODES ; its purpose is to help you quickly find the information you need from them. The CODES listed in Table 1 (T1) contain thousands of pages of information that cannot be condensed into something as small as this book. We have excluded items such as water & gas supply tables that are covered in other books in the code Check series so that we might include items for which code digests are not so readily available, such as suspended ceilings, commercial kitchen hoods, and commercial wiring. Table 1 (T1) lists the primary CODES used in this book. To determine the CODES applicable in your area, contact the local building department. In most cases, CODES do not go into effect until one or more years after the publication date and then stay in effect for approximately three years. In other words, most jurisdictions would begin enforcing a 2009 code in 2010 or 2011 and continue using that code through 2012 or 2013 or even past that date.

3 This book does not include energy CODES , which vary greatly from state to state, or CODES for green building, which have been adopted in some areas. Contact the local building department in the planning stages to determine how these CODES might affect your project. Special thanks to Thomas Trainor, General Contractor, and Jeff Hutcher, City of Oakland, for their assistance. For more information, any updates, and why Benjamin Franklin is featured in the code Check series, visit: KEY & EXAMPLES . Each item with a checkbox refers to a code rule and is followed by a code citation in brackets TABLE 1 MODEL CODES REFERENCED IN THIS BOOK [ ]. The subheading in bold print above the list of citations indicates which code from T1 is used for that group of references. Subject Model code Abbreviation Organization example , from page 7: Building 2009 International Building code 09 IBC ICC Fire Doors 09 IBC. Fire 2009 International Fire code 09 IFC ICC n Door req's permanent labeling including manu & ratings_____ [ ].

4 The 2009 International Building code section requires fire doors to have permanent labels that include the manufacturer and the fire ratings. 2009 International Plumbing code 09 IPC ICC. Plumbing In the plumbing and mechanical sections, there are often two citations. The first one, in 2009 Uniform Plumbing code 09 UPC IAPMO brackets, is the citation from one of the International CODES , and the second citation is from the Uniform CODES (see table at left). 2009 International Mechanical code 09 IMC ICC. Mechanical &. example , from page 27: 2009 International Fuel Gas code 09 IFGC ICC Temperature & Pressure Relief Valves (TPRV) 09 IPC 09 UPC. Fuel Gas 2009 Uniform Mechanical code 09 UMC IAPMO n TPRV req'd all storage type water heaters_____ [ ] { }. 2009 International Plumbing code section and 2009 Uniform Plumbing code section 2008 National Electrical code 11 NEC NFPA require all storage tank water heaters to have a temperature & pressure relief valve.

5 Electrical Lines that end with an EXC mean that code exceptions follow in the next lines. The lines 2009 Standard for Electrical Safety containing the exceptions start with a bullet rather than a checkbox. NFPA 70E NFPA. in the Workplace example , from page 11: 2008 Building code Requirements Concrete ACI 318 ACI Stairways 09 IBC. for Structural Concrete n Min width 44in EXC_____[ ]. 2008 Building code Requirements 36in OK if occupant load <50_____ [ ]. Masonry ACI 530 ACI. for Masonry Construction 2009 International Building code Section requires stairways to be 44 inches wide, and exception 1 in section allows 36 inch wide stairways when the occupant load is less than 50. TABLE 2 ORGANIZATIONS & ACRONYMS. Lines that are part of lists also begin with bullets rather than checkboxes. AAMA American Architectural Manufacturers Association example , from page 11: ACCA Air Conditioning Contractors of America n In SDC D-F, geotechnical investigation to also include:_____ [ ].

6 ACI American Concrete Institute Determination of lateral pressure on foundation walls AF&PA American Forest & Paper Association Site-specific liquefaction study per ASCE-7 chapter 21. Lateral pressure on foundation walls and a site-specific liquefaction study are included in AISI American Iron & Steel Institute geotechnical investigations in SDC D F. ASCE American Society of Civil Engineers Figure and table references are highlighted by bold print and color. ASHRAE American Society of Heating, Refrigerating & Air-Conditioning Engineers EXAMPLES , from page 36: ASTM American Society for Testing & Materials n Use all electrodes in F44 when present on premises_____[ ]. CISCA Ceilings & Interior Systems Construction Association n Size based upon service conductor size T34_____[ ]. The line that all electrodes present be used is illustrated in figure 44. The table that gives the IAPMO International Association of Plumbing & Mechanical Officials size for grounding electrode conductors is table 34.

7 code citations that are changes from the previous code are highlighted in a different color, ICC International code Council and followed by an endnote. NFPA National Fire Protection Association example , from page 4. NRCA National Roofing Contractors Association n Min 33in high vehicle barrier req'd @ end of drive lane or if distance OSHA Occupational Safety & Health Administration to surface below 1ft _____ [ ]4. The color and endnote indicate that this item is code change #4 on page 45. The table on UL Underwriters Laboratories page 45 summarizes the change as Height of vehicle barrier raised.. CONSTRUCTION TYPES, HEIGHT & AREA LIMITATIONS BUILDING SETBACK AND OPENINGS. Chapter 5 of the IBC provides tables that limit the size and height of buildings based upon their occupancy and construction type. Chapter 6 provides more detail on characteristics of differ- Building Setbacks & Fire-Resistance 09 IBC. ent construction types. The larger and taller a building is, the greater the need for fire resistance n Min fire-resistance rating of exterior walls per T7_____ [ ].

8 And limitations on the fire load. When planning a project, check IBC table 503 to determine if n Rating only from interior if FSD >10ft, from both sides if 10ft_____ [ ]6. the occupancy and construction type are within the limits allowed by that table. n FSD measured perpendicular to wall_____ [ ]. Types of Construction 09 IBC n FSD measured to closest interior lot line, centerline of street, or n All buildings classified by type and in accordance w/ T6_____ [ ] imaginary line between 2 buildings on same lot_____ [ ]. n Height & area of building limited by occupancy & construction type____ [ ] n For buildings on same lot, assume imaginary line between buildings___ [ ]. n For existing building & new building on same lot, imaginary line to BUILDING TYPES & FIRE-RESISTANCE (IN HOURS) comply w/ T7 & T8 for the existing building, EXC_____ [ ]. TABLE 6. [T601] 2 buildings on 1 lot can be considered single building if complying Type I Type II Type III Type IV Type V w/ height & area limitations of for the more restrictive occupancy_[ ].

9 Element A B A A. B A A. B HT A A. B Allowable Openings 09 IBC. Primary structural frame 3 B. 2 B. 1 0 1 0 HT 1 0 n Max allowable area of openings per T8 EXC_____ [ ]. Exterior bearing walls 3 2 1 0 2 2 2 1 0 Unlimited openings in wall facing street w/ 15ft FSD_____ [ ]. Interior bearing walls 3B 2B 1 0 1 0 1/HT 1 0 Unlimited openings where exterior not req'd to be fire-resistive__ [ ]. Exterior nonbearing walls n Protected openings (fire-rated glass) req'd to comply as fire doors, fire See T7. & partitions shutters, or fire window assemblies per & EXC_____ [ ]. Interior nonbearing walls Protection not req'd if building fully sprinklered & exterior openings 0 0 0 0 0 0 HTC 0 0. & partitions protected by water curtain w/ automatic sprinklers_____ [ ]. Floor construction &. 2 2 1 0 1 0 HT 1 0. secondary members TABLE 8 ALLOWABLE OPENINGS IN EXTERIOR WALLS [ ]. Roof construction & Fire Separation Distance Degree of Protection Allowable Area 1 1 D.

10 1 D. 0 D. 1 D. 0 HT 1. D. 0. secondary members <3 ft. not permitted A. An automatic fire sprinkler system is allowed to substitute for 1-hour construction provided no height or UP-NS not permitted area increases & no substitution for rating of exterior walls. 3 ft. to <5 ft. S or P 15%. B. Reduction of 1 hour OK for elements supporting roof only. UP-NS 10%. C. 2 layers solid 1 in. wood, or 4 in. laminated, or 1-hour construction. 5 ft. to <10 ft. D. Heavy timber is allowed to substitute for a 1-hour rating. S or P 25%. UP-NS 15%. 10 ft. to <15 ft. S or P 45%. TABLE 7 FIRE RESISTANCE OF EXTERIOR WALLS [T602] UP-NS 25%. 15 ft. to <20 ft. S or P 75%. Fire Separation Type of Occupancy Groups Occupancy Groups Distance Construction F-1, M, S-1 A, B, E, F-2, I, R, S-2, U UP-NS 45%. 20 ft. to < 25 ft. S or P no limit <5 ft. All 2 1 UP-NS 70%. 25 ft. to <30 ft. IA 2 1 S or P no limit 5 ft. & <10 ft. 30 ft. not required Others 1 1. UP-NS = Unprotected & Nonsprinklered, S or P = Sprinklered or Protected IA & IB 1 1A.