INTRODUCTION TO PROFIBUS DP - Unict

BusWorksTM 900PB SeriesProfiBus/RS485 Network I/O ModulesTechnical ReferenceINTRODUCTION TO PROFIBUS DPACROMAG INCORPORATED Tel: (248) 624-154130765 South Wixom Road Fax: (248) BOX 437 Wixom, MI 48393-7037 2002, Acromag, Inc., Printed in the and specifications are subject to change without notice. 8500-698-A02M000 INTRODUCTION To PROFIBUS DP_____Acromag, Inc. Tel:248-624-1541 Fax:248-624-9234 TO PROFIBUS DPABOUT DP SLAVE STATE ON/Reset Configuration Exchange Safe OF Send and Request Data Send Data w/No DP DATA CHARACTER Data Error TELEGRAM Of Address & Source Code Or Frame Access Check COMMAND STATES AND APPLICABLE Power Exchange Of Of information is provided as a service to our customers and to othersinterested in learning more about PROFIBUS .

the OSI (Open System Interconnection) reference model per international standard ISO 7498. In this model, every layer handles precisely defined tasks. Layer 1 of this model is the physical layer and defines the physical transmission characteristics. Layer 2 is the data link layer and defines the bus access protocol.

Tags:

  Model, Reference, Reference model, The iso

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Advertisement

Transcription of INTRODUCTION TO PROFIBUS DP - Unict

1 BusWorksTM 900PB SeriesProfiBus/RS485 Network I/O ModulesTechnical ReferenceINTRODUCTION TO PROFIBUS DPACROMAG INCORPORATED Tel: (248) 624-154130765 South Wixom Road Fax: (248) BOX 437 Wixom, MI 48393-7037 2002, Acromag, Inc., Printed in the and specifications are subject to change without notice. 8500-698-A02M000 INTRODUCTION To PROFIBUS DP_____Acromag, Inc. Tel:248-624-1541 Fax:248-624-9234 TO PROFIBUS DPABOUT DP SLAVE STATE ON/Reset Configuration Exchange Safe OF Send and Request Data Send Data w/No DP DATA CHARACTER Data Error TELEGRAM Of Address & Source Code Or Frame Access Check COMMAND STATES AND APPLICABLE Power Exchange Of Of information is provided as a service to our customers and to othersinterested in learning more about PROFIBUS .

2 Acromag assumes noresponsibility for any errors that may occur in this document, and makes nocommitment to update or keep this information sure to visit Acromag on the web at is a registered trademark of Microsoft is a registered trademark of Modicon, OFCONTENTSI ntroduction To PROFIBUS DP_____Acromag, Inc. Tel:248-624-1541 Fax:248-624-9234 following information describes the operation of PROFIBUS DP as itrelates to Acromag Series 900PB DP slave I/O modules. For more detailedinformation on PROFIBUS , you may refer to the PROFIBUS Trade Organization atthe PTO website manufactures a line of I/O modules that support PROFIBUS DPover RS485.

3 Feel free to visit our website at to obtainthe latest information about these and other Acromag Series 900PB modules utilize the popular PROFIBUS DPFieldBus communication format. PROFIBUS was created in 1989 by theGerman government in cooperation with several manufacturers ofautomation equipment. It is a messaging format specifically designed forhigh-speed serial I/O in factory and building automation applications. It is anopen standard and is recognized as the fastest FieldBus in operation is based on RS485 and the European EN50170 Electrical DP suffix refers to Decentralized Periphery , which is used to describedistributed I/O devices connected via a fast serial data link with a centralcontroller.

4 To contrast, a programmable logic controller (PLC) normally hasits input/output channels arranged centrally. By introducing a network busbetween the main controller (master) and its I/O channels (slaves), we havedecentralized the is based on universal international standards and oriented tothe OSI (Open System Interconnection) reference model per internationalstandard ISO 7498. In this model , every layer handles precisely definedtasks. Layer 1 of this model is the physical layer and defines the physicaltransmission characteristics. Layer 2 is the data link layer and defines thebus access protocol. Layer 7 is the application layer and defines theapplication functions.

5 PROFIBUS DP uses only layers 1 & 2 of this model , plusthe user interface. Layers 3 to 7 are not PROFIBUS system uses a bus master to poll slave devices distributed inmulti-drop fashion on an RS485 serial bus. A PROFIBUS slave is anyperipheral device (I/O transducer, valve, network drive, or other measuringdevice) which processes information and sends its output to the slave forms a passive station on the network since it does not havebus access rights, and can only acknowledge received messages, or sendresponse messages to the master upon request. It is important to note thatall PROFIBUS slaves have the same priority, and all network communicationoriginates from the master.

6 Acromag I/O modules form intelligent modules implement the PROFIBUS protocol via an industry-standard SPC3 ASIC from Siemens. This ASIC acts like a RAM or UART chip to the internal microcontroller and completely handles the requirementsof the protocol standard. The ASIC will transfer network data to and fromthe microcontroller and automatically provide the response to the busaccording to the PROFIBUS PROFIBUSI ntroduction To PROFIBUS DP_____Acromag, Inc. Tel:248-624-1541 Fax:248-624-9234 PROFIBUS master forms an active station on the network. ProfiBusDP defines two classes of masters. A class 1 master handles the normalcommunication or exchange of data with the slaves assigned to it.

7 A class 2master is a special device primarily used for commissioning slaves and fordiagnostic purposes. Some masters may support both class 1 and class 2functionality. Master-to-master communication is normally not permitted inProfibus, except in order to grant bus access rights to another master via theexchange of a token. However, master-to-master communication betweentwo mono-master systems can be facilitated using a DP-DP gateway. Notethat the exchange of bus access rights via this token ring only appliesbetween masters on the class 1 master device is normally a central programmable controller(PLC), or a PC running special software.

8 The class 1 master sets the baudrate and the slave s auto-detect this rate. The class 1 master handles thedata exchange with the slaves assigned to it, and acts as the main controllerfor the exchange of I/O information with its distributed slaves, cyclicallyretrieving user I/O data according to a defined message cycle. A master cancommunicate actively with its assigned slaves, but only passively (uponrequest) with another class 2 master class 2 master is usually a configuration device, perhaps a laptopor programming console, and is provided for commissioning, maintenance,or diagnostic purposes. It acts like a supervisory master in that it canactively communicate with class 1 masters and their slaves, in addition to itsown slaves, but usually only for the purpose of configuration, problemdiagnosis, and data/parameter exchange.

9 That is, class 2 masters may onlybriefly take over control of a slave. All exchanges between a class 2 masterand class 1 master originate with the class 2 DP normally operates using a cyclic transfer of data betweenmaster(s) and slave(s) on an RS485 network. That is, an assigned masterperiodically requests (polls) each node (slave) on the network. All datacommunication exchanges between a master and slave originate from themaster device. Each slave device is assigned to one master and only thatmaster may write output data to that slave. Other masters may readinformation from any slave, but can only write output data to their ownassigned can address individual slaves, a defined group of slaves (multi-cast), or can broadcast a telegram to all connected slaves.

10 Slaves will returna response to all telegrams addressed to them individually, but do notrespond to broadcast or multi-cast telegrams from a master sends Broadcast and Multi-Cast messages as global controltelegrams using address 127 and an optional group number for a targetedgroup of PROFIBUS uses a cyclic (periodic) polling mechanism betweenmasters and slaves, it is also deterministic. That is, the behavior of aProfiBus system can be reliably predicted over time. In fact, PROFIBUS wasdesigned to guarantee a deterministic response. To contrast, CAN andEthernet are event-driven bus systems and consequently form non-deterministic To PROFIBUS DP_____Acromag, Inc.