Example: bankruptcy

Kidde Fire Systems ADS with 3M Novec 1230 Fire Protection ...

1 Effective: November 2018K-45-103 Rev ACKidde fire Systems ADS with 3M Novec 1230 fire Protection FluidCylinder component Datasheet600 lb. Cylinder and Valve AssembliesDESCRIPTIONK idde fire Systems Advanced Delivery fire suppression ( Kidde ADS) Systems are Listed by the UnderwritersLaboratory, Inc. (UL) and tested by Factory Mutual (FM).These Systems are designed for total flooding in accor-dance with NFPA 2001, Standard on Clean Agent Extin-guishing Systems . These Systems have been tested toUL 2166, Standard for Safety; Standard for HalocarbonClean Agent Extinguishing System Units, and otherparameters established jointly by UL and Kidde ADS system uses a unique method for propel-ling the 3M Novec 1230 fire Protection Fluid (Hereinreferred to as agent) from the storage cylinder, throughthe piping system and out of the dischar

Kidde Fire Systems ADS™ with 3M™ Novec™ 1230 Fire Protection Fluid Cylinder Component Datasheet 600 lb. Cylinder and Valve Assemblies DESCRIPTION Kidde Fire Systems Advanced Delivery Fire Suppression (Kidde® ADS) systems are Listed by the Underwriters Laboratory, Inc. (UL) and tested by Factory Mutual (FM).

Tags:

  Descriptions, Component, Fire, Suppression, Fire suppression

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of Kidde Fire Systems ADS with 3M Novec 1230 Fire Protection ...

1 1 Effective: November 2018K-45-103 Rev ACKidde fire Systems ADS with 3M Novec 1230 fire Protection FluidCylinder component Datasheet600 lb. Cylinder and Valve AssembliesDESCRIPTIONK idde fire Systems Advanced Delivery fire suppression ( Kidde ADS) Systems are Listed by the UnderwritersLaboratory, Inc. (UL) and tested by Factory Mutual (FM).These Systems are designed for total flooding in accor-dance with NFPA 2001, Standard on Clean Agent Extin-guishing Systems . These Systems have been tested toUL 2166, Standard for Safety; Standard for HalocarbonClean Agent Extinguishing System Units, and otherparameters established jointly by UL and Kidde ADS system uses a unique method for propel-ling the 3M Novec 1230 fire Protection Fluid (Hereinreferred to as agent) from the storage cylinder, throughthe piping system and out of the discharge nozzles.

2 Nitro-gen gas pressure from one or two separate storage cylin-ders is introduced into the vapor space of the agentcylinder at a controlled rate. This nitrogen pressure actsto propel the liquid agent through the pipe at a higher flowrate. It can also propel the agent farther through the pipenetwork allowing for the placement of storage cylindersremotely from the protected Kidde ADS system is extremely well-suited to appli-cations involving remote agent storage and situationswhich limit the maximum pipe size to be used. The KiddeADS system is capable of using smaller pipe sizes to dis-charge large quantities of a control head actuates the two nitrogen cylinderdischarge valves, the nitrogen pressure actuates theagent cylinder discharge valve and pressurizes the agent is then propelled by its own vapor pres-sure and the nitrogen pressure through the dischargevalve and into the system pipe network.

3 The liquid agenttravels through the system pipe network at a high RANGE LIMITATIONS: The operating temperature range for all componentsused in the Kidde ADS system is 32 F to 130 F (0 Cto 54 C) The agent cylinder operating temperature must bebetween 60 F to 80 F (16 C to 27 C) when protect-ing two or more separate Kidde ADS system installation is based on therequirements of NFPA 2001, Standard on Clean AgentExtinguishing Systems , Current :Both the nitrogen drivers and agent storage cylinders areto be installed in the vertical position only. The nitrogendriver is located to the immediate right apart from theagent cylinder.

4 The nitrogen driver cylinder is connectedto the agent cylinder by using the nitrogen transfer com-ponents. The nitrogen transfer components useddepends upon whether the system uses one or two nitro-gen Well Suited for Complicated Pipe Networks and Large Area Coverage with Minimal Roomfor Cylinder Storage 3-Inch Valve Outlet 300 lb. to 600 lb. Fill Capacity Agent Cylinder Liquid Level Indicator UL Listed, File Number 4674 FM Approved For RoHS Compliance, See the Individual component Datasheets Uses one or two Nitrogen DriversEffective: November 20182K-45-103 Figure 1. Single Cylinder Installation Dimensions, 600 lb.

5 CylinderFigure 2. Dual Driver Installation, Vertical Mounting for 600 lb. Systems413689524070cu. in .600 lb . in.(1524 mm) in.(867 mm) in.(1283 mm) in.(940 mm) in.(457 mm) in.(559 mm) in.(267 mm) in.(545-622 mm)58 in.(1473 mm) in.(1613 mm) in.(1810 mm)1. ASSY - CYL. AND VALVE, AGENT2. ASSY - CYL. AND VALVE NITROGEN DRIVER3. HOSE - FLEXIBLE DISCHARGE4. STRAP - AGENT CYLINDER5. ASSY - DISCHARGE HEAD6. ASSY - ACTUATION7. FITTING - ORIFICE8. HOSE - HIGH PRESSURE9. STRAP - NITROGEN DRIVER CYLINDERS4136895274070cu. in .600 lb .SIDE VIEWFRONT VIEW1. ASSY - CYL. AND VALVE, AGENT2. ASSY - CYL.

6 AND VA L VE NITROGEN DRIVER3. HOSE - FLEXIBLE DISCHARGE4. STRAP- HFC-227 EACYLINDER5. ASSY - DISCHARGE HEAD6. ASSY - ACTUA TION7. FITTING - ORIFICE8. HOSE - HIGH PRESSURE9. STRAPNITROGEN DRIVER in.(268 mm) in.(914 mm) in.(1524 mm) in.(867 mm) in.(1283 mm) in.(940 mm) in.(457 mm) in.(559 mm) in.(268 mm) in.(545-622 mm)58 in.(1473 mm) in.(1613 mm) in.(1810 mm)Effective: November 2018K-45-1033 Single Driver SystemsThe control head is attached to the nitrogen driver bymeans of electric, cable, lever, or pneumatic actuating of the agent cylinder is done upon transferof nitrogen from the driver cylinder using the actuationassembly kit (P/N 06-129882-001).

7 Assembly includes: Nitrogen transfer fitting 1/8-in. flex loop 1/8-in. flare fitting 1/8-in. branch tee 1/8-in. Schrader fitting and cap Pressure operated control headSingle Driver Actuation Assembly Ordering InformationDual Driver SystemsThe control head is attached to the master nitrogen driverby means of electric, cable, lever or pneumatic actuating of the second nitrogen driver and agent cylinder is done upon transfer of nitrogen from the masterdriver cylinder using the actuation assembly kit (P/N 06-129985-001). Assembly includes: Nitrogen Y Transfer Fitting 1/8-in. Flex Loop 1/8-in.

8 Flare Fitting 1/8-in. Branch Tee 1/8-in. Schrader Fitting and Cap Pressure Operated Control Head 3/4-in. Nipple (Hex)Dual Driver Actuation Assembly Ordering Information06-129882-001 Contains:Item Transfer Fitting2182-878737-000 Pressure Operated Control Head(Pneumatic Actuator)3106-118191-001 Fitting Flared 1/8-in. x 1 Flexible Actuation Hose5106-118192-0011/8-in. Branch Tee61WK-263303-0001/8-in. Schrader Valve71WK-263304-0001/8-in. Schrader Valve CapFor more information, refer to datasheet K-85-1032435671306-129985-001 Contains:Item NumberDescription1106-236260-001 Nitrogen Transfer "Y" Fitting2182-878737-000 Pressure Operated Control Head(Pneumatic Actuator)3206-118191-001 Fitting Flared 1/8" x 1/4"4106-118193-0013/16" Flexible Actuation Hose5106-118192-0011/8" Branch Tee61WK-263303-0001/8" Schrader Valve71WK-263304-0001/8" Schrader Valve Cap8106-118330-0013/4" NippleFor more information, refer to datasheet K-85-110243567138 ACTUATION.

9 When using 3M Novec 1230 fire Protection fluid, the Kidde ADS system can use one or two drivers with the 600 cylinder. Use the flow calculation software to determine which setup is applicable for the fire Systems400 Main StreetAshland, MA 01721Ph: : is a registered trademark of Kidde -Fenwal, Inc., or its parents, subsidiaries or literature is provided for informational purposes only. Kidde -FENWAL, INC. believes this data to be accurate, but it is published and presented without any guarantee or warranty whatsoever. Kidde -FENWAL, INC. assumes no responsibility for the product's suitability for a particular application.

10 Product features specified are only applicable when the fire suppression system is correctly designed, installed, maintained and serviced by trained, authorized Kidde fire Systems distributors as per the applicable design, installation, operation, and maintenance manuals. If you need more information on this product, or if you have a particular problem or question, contact: Kidde -FENWAL, INC., Ashland, MA 01721 USA, Telephone: (508) Rev AC 2018 Kidde -Fenwal, INFORMATION (USA)Jurisdiction: EARC lassification: EAR99 This document contains technical data subject to the to NFPA standards, the following inspection and/or maintenance procedure must be scheduled as listedbelow and performed upon the occurrence of any event, which might affect the reliability of the system.


Related search queries