KL700A Series Analogue Addressable Point Detectors Installation Manual X. Y Z. [ \. ] ^. 2007 Version / January 2007. 55370077. Installation and Maintenance Testing Check that all detectors are properly assembled in their Guide mounting bases. DESCRIPTION Activate the control panel and check for correct operation. For general guidelines on system planning, design, Check that all of the installed detectors are recognised by the installation, commissioning, use and maintenance, control panel. If any detector is not recognised, check that no refer to the EN54:14 (2001) standard and local duplicate addresses have been assigned, check the correct regulations. assembly of the detector and its connection. To test smoke detectors, apply smoke or approved aerosol KL700A Analogue Addressable Point ionisation smoke detector and verify alarm condition.

KL700A series installation manual (55370077) 3 Guía de Instalación y Mantenimiento DESCRIPCIÓN Insertando un destornillador pequeño en la ranura lateral de la

Tags:

  Addressable, Analogue, Analogue addressable

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of KL700A Series Analogue Addressable Point …

1 KL700A Series Analogue Addressable Point Detectors Installation Manual X. Y Z. [ \. ] ^. 2007 Version / January 2007. 55370077. Installation and Maintenance Testing Check that all detectors are properly assembled in their Guide mounting bases. DESCRIPTION Activate the control panel and check for correct operation. For general guidelines on system planning, design, Check that all of the installed detectors are recognised by the installation, commissioning, use and maintenance, control panel. If any detector is not recognised, check that no refer to the EN54:14 (2001) standard and local duplicate addresses have been assigned, check the correct regulations. assembly of the detector and its connection. To test smoke detectors, apply smoke or approved aerosol KL700A Analogue Addressable Point ionisation smoke detector and verify alarm condition.

2 KL710A Analogue Addressable Point rate of rise heat detector To test heat detectors apply temperature using for example a hair dryer and verify that the detector goes into alarm. KL731A Analogue Addressable Point optical smoke detector KL735A Analogue Addressable Point dual optical / heat detector Consult the fire panel manual for further test procedures. The KL700A Series detectors are designed specifically for use with MAINTENANCE. the Kilsen KSA700 Series of Analogue Addressable fire detection In normal environments cleaning should be done at least every control panels. On these systems the control panel communicates three or four years. It is recommended that random functional tests with the individual detectors using a unique data transmission be carried out every six months.

3 Protocol. The detectors continuously monitor the environment where they are installed and report any changes in smoke or heat KL700A , KL710A, KL735A. concentration to the control panel. In turn, the control panel generates the alarm condition if applicable. No special maintenance required. Only qualified personnel should carry out cleaning. Do not open the detector head. The detectors have indicators that flash in a pre-alarm condition and light continuously in a full alarm condition. The system is KL731A. reset at the control panel. To be carried out by qualified personnel. An optional remote indicator may be connected from the mounting base connections and will mimic the detector indicator. To clean the optical chamber 1.

4 Remove the detector from the mounting base. INSTALLATION. 2. Remove the detector cover by pressing the catch with a The detectors must not be exposed to dusty or dirty environments. screwdriver, turning and lifting (Figure [). During building works or repairs, the detectors must be removed. 3. Use a vacuum cleaner or compressed air to remove dust from Smoke detectors should not be installed in environments where the chamber. condensation may be present. 4. Replace detector cover and place detector into mounting base. The surface of the detector must not be painted. To replace the optical chamber Positioning Smoke and temperature detectors are designed to be positioned To avoid injury wear gloves when changing the on the ceiling and should be well away from ventilation inlets and optical chamber.]

5 Air extractors. Once the location is decided, the detector base should be fitted first either to the pre-wired mounting box or direct Follow steps 1 and 2 above. to the ceiling through the S700 mounting supplement. To remove optical chamber place thumb on the OUT mark of the Connections steel mesh area, hold the detector and pull firmly (Figure \). The detectors must be connected as shown in figure X. The cable To insert the new optical chamber align the hanging mesh (Figure from the last detector on the loop should return to the control panel ]) with its entry area and press down firmly to ensure chamber to close the loop. clips into place (Figure ^). The positive line cable (+) must be connected to terminal 1, and Once the optical chamber has been replaced the detector must be the negative line (-) to terminal 3.

6 If a remote indicator is used, its calibrated with PG700 Analogue programmer and calibration unit positive line cable (+) must be connected to terminal 2 in the before it can be used. See PG700 instruction label for more mounting base and the negative to terminal 3. details. To connect the cables in the mounting base, remove a piece of insulation (about 1 cm in length), pass the cables through the hole SECURITY CERTIFICATE ( KL700A ). and connect each cable in its proper location. To lock each cable, unscrew each mounting base connection. Slide the un-insulated tip KILSEN radioactive IR-B/197/97. of the cable under the metal piece and screw down. The KL700A has been approved by Spanish Industry and Energy Check cable continuity before connecting.

7 Ministry, as EXEMPT from authorisation as radioactive installation. Approval code .. NHM-D161. Addressing The detector corresponds exactly with approved sample. Each detector requires a numeric address between 1 and 125 for identification purposes. The address may be set using the PG700 Quality ISO9001 certified portable address programmer or the fire system control panel. Source Amersham International plc. Consult the handset or fire panel manual for more full instructions. NRPB and CIEMAT laboratories measures done, (following Connecting the detector to the mounting base European Nuclear Energy Agency): Once the mounting base is in position, the detector is connected Radioactive Americium 241. by inserting it and turning (figure Y).

8 To remove the detector, turn Average activity .. Ci ( kBq). it in the opposite direction. Radiation level at Sv/h 2. Locking catch Contamination ..< Bq/cm All of the detector heads have a locking catch to prevent Valid use period is for 10 years. It is forbidden to tamper with the unauthorised removal. workings of the unit or to remove any labels or signs. If radioactive To enable locking, the locking catch must be broken (figure Z). source is suspected of being faulty, please contact KILSEN After connecting the detector, it will be locked in place. This certificate covers all devices with referred approval code. To remove a locked detector, press through the hole (figure \). using a screwdriver or similar, and turn. 2 KL700A Series installation manual (55370077).

9 Mecanismo de bloqueo Gu a de Instalaci n y Todos los detectores de la serie KL700A disponen de un Mantenimiento mecanismo de bloqueo que evita substracciones indeseadas DESCRIPCI N (figura ). Si se desea, los detectores pueden ser bloqueados eliminando la Ver la norma EN54:14 (2001) y disposiciones pesta a indicada en la figura antes de montarlos en el z calo. locales sobre protecci n contra incendios para Insertando un destornillador peque o en la ranura lateral de la obtener directrices generales respecto al dise o, base y haciendo presi n a la vez que girando el detector en instalaci n, puesta en marcha, uso y mantenimiento sentido contrario a las agujas del reloj, se puede volver a separar de estos sistemas . la cabeza del z calo (figura ).

10 KL700A Detector anal gico puntual de humos - i nico Comprobaci n KL710A Detector anal gico puntual t rmico est tico y Comprobar que todos los detectors han sido insertados termovelocim trico adecuadamente en sus respectivos z calos. KL731A Detector anal gico puntual de humos - ptico Activar la central de incendios y verificar su correcto KL735A Detector anal gico puntual ptico-t rmico funcionamiento. La serie de detectores KL700A ha sido dise ada espec ficamente Comprobar que la central de incendios reconoce todos y cada para su uso con centrales de control anal gicas Kilsen serie uno de los detectors y que no hay ninguna direcci n KSA700. En estos sistemas la central de incendios comunica con duplicada. cada uno de los detectores a trav s de un protocolo de Para comprobar los detectors de humo, aplicar humo o transmisi n nico y propietario.