Transcription of Liebert HPW - Dataromskjøling
1 Liebert HPW -- PD -- 273136 -- HPWO utdoor Package Cooling System for Mobile Network Access NodesPrecision Cooling forBusiness--Critical ContinuityPRODUCT DOCUMENTATIONL iebert HPW 05--15 Liebert HPW 05--- 15 Reliability, Flexibility and TCOL iebert HPWis the newest high performance wall---mount outdoor package cooling system, de-signed to assure proper environmental conditions inside technological environments, especiallyBTS or Node B for mobile telecom s reliable:mechanical design ideal for managing high sensible heat load in harsh s flexible:available in upflow or downflow air delivery versions with the same compact cabinetdimension, Liebert HPWcan configured with different main options as free cooling, emergencycooling 48 Vdc and s designed tominimise the Total Cost of Ownership(TCO) thanks to high efficiency (EER),high effectiveness (displacement like, cooling process), low installation and maintainance HPWcooling unit can handle up to 15 kW sensible heat load site, with efficiency(EER) higher than 3, in environments temperature range from ---30_Cuptomorethan50_C, sav-ing in 10yearslifetime 50%of Totalcost of Ownership if compared with traditional airconditioningsystem!
2 Front viewRear viewIndex of ContentsLiebert of ContentsContents1 Features and Benefits2 Model Description andSelection3 Mechanical Specifications4 Control5 Options6 Accessories7 Test and Reference Norms8 Technical Data9 Overall Dimensions10 InstallationThe product conforms to European Uniondirectives 2006/42/EC; 2004/108/EC;2006/95/EC and 97/23 are supplied complete with a testcertificate and conformity declaration andcontrol component HPWunits are CE marked as theycomply with the European directivesconcerning mechanical, electrical andelectromagnetic Quality ManagementSystem of Emerson NetworkPower High PerformanceAir Conditioning has beenapproved by Lloyd's RegisterQuality Assurance to thequality management systemstandard ISO 9001 and Benefits1 Liebert and BenefitsUse the most adaptive and suitable wall mount solution!
3 Liebert HPWcanbeconfiguredinoverflow( Liebert HPW---O) or down flow ( Liebert HPW--- D)version, resulting as extremely adaptive to different site layout; whatever is the chosen deliveryair version wall cuts are the same, the condenser section is always positioned on the top part ofthe unit reducing critical environment impact on condenser efficiency and permitting easier andmore effective maintenance the air in the best way!UsetheLiebert HPW---Dversion togetefficiency and effectivenessatsametime: Liebert HPW---D delivers the cold air straight down, close to the racks suction area and intakes the hot air out-coming from the heat sources in the top part of the room. In this way the mixing effect betweencooling unit cold air and the electronic equipment hot airis denied resulting in a doublebeneficialeffect: the racks are fed by cold air where it is needed and the air conditioner treats only the hotair maximising its temperature inside the racks, high efficiency of the cooling equipment, hot spot absencein the site: distributing the air in a smart way is very energy!
4 The use of the freecooling gives the possibility to stop the compressor and condenser fan, usingthe external fresh air to cool the site: the annual energy absorption, requested to cool the site,goessensibly down. The0---100% finemodulation allowsto keep constantly thedesired itsown airdistribution (only hot airis exhausted), Liebert HPWdownflowversion, extends the yearly freecooling use, increasing the energy site reliability! Liebert HPW, equipped withe the Emergency Cooling feature, does not stop the operation evenin case of mains failure: fed by 48 V DC emergency supply from back up systems, Liebert HPWautosets its parameters to ventilate and maximise the freecooling to keep the indoor temperaturebelow the shut down limit, reliablity of the site means also reliability of the unit.
5 Downflow modelallowstostarttheEmergengy Freecoolingatahigherexternaltemperature, reducing thesiteshutdown installation and start---up!No piping or refrigeration work is requested on site: just prepare cut---outs in the wall, accordingto the template, and make power available. As soon the unit is fixed and sealed on the wall, placethe remote display in a suitable position and feed the up usingthefastplugconnectoroption(availabl eonrequest):no wiring is requested on site and the connection can be performed even by non skilled person-nel. In case of unit replacement, the fast plugs allow replacement ina few versions:DownfloworOverSOnesitepreparati on:samewallcutsSCoolingeffectivenessSCoo lingEfficiencySEnhancedFreecoolingSConti nuerevenuefromsiteSNopiping,fastelectric alconnections2 Model Description and SelectionsLiebert Description and Selections35410987 Cooling Capacity kW (Nominal cooling capacity)12 Model Nomenclature / Digit Numbers_____Wall Mounted Unit606 MWCabinet Size(Small,Medium)ML i e b e r t H P W W M 0 5 --- 0 6 S O / S D --- H P W W M 0 6 --- 1 5 M O / M DBASEUNIT.
6 DIGITS1,2,3,4,5 Packaged outdoor wall mounted air conditioner, direct expansion(R407C) with built---in air cooled condenserD i g i t 6 --- Ai rf low p a t hD=DownflowO=OverDigit 7 --- Emergency cooling (EFC)0= No emergency cooling1= Emergency cooling through 48 Vdc fan(*)2= Emergency cooling through 230 Vac(*)A= No emergency cooling + Alarm boardB= Emergency cooling through 48 Vdc fan + Alarm board(*)C= Emergency cooling through 230 Vac + Alarm board(*)(*) Option possible only if digit 9 = 1, 2, A, or BDigit 8 --- Main power supply and electric heating0= 230V / 1Ph / 50Hz, no electric heating, for 4 --- 6kW400V / 3Ph / 50Hz, no electric heating, for 8 --- 16kW1= 230V / 1Ph / 50Hz, with electric heating, for 4 --- 6kW400V / 3Ph / 50Hz, with electric heating, for 8 --- 16kWDigit 9 --- Fresh air freecooling (FC)0= No freecooling1= Freecooling with modulating damper2= Freecooling with fast return damperA= Freecooling with modulating damper and HumitempB= Freecooling with fast return damper and HumitempDigit 10 ---Microprocessor control1= Control without display2= Control with remote display (cable included)
7 With Hiromatic Evolution (Graphic display)(inclusive of RS422 with RJ connectors)5= Languages Set 1, temperature control(GB, F, I, D, E, P, NL, S)6= Languages Set 2, temperature control(GB, PL, CZ, H, RUS, TK)D i g i t 1 1 --- Ai r f i lt ers0=G31=G42= G3 + clogged filter pressure switch on internal air3= G4 + clogged filter pressure switch on internal airD i g i t 1 2 --- Pa cki ngP= PLP and palletC= Cardboard and wooden crateS=SeaworthyDigit 13 ---Condensing control0= Condensing control ON---OFF1= Modulating condenser fan speed control (Variex)D i g i t 1 4 --- C oi ls0= Standard aluminium fins1= Standard evaporator fins and epoxy coated condenser fins2= Epoxy evaporator fins and standard coated condenser fins3= Epoxy coated evaporator and condenser finsD i g i t 1 5 --- G ri lls0= N o g rill (on ly HP W --- O version )1= Simple (not adjustable) intake and delivery (only HPW---Dversion)2= Simple (not adjustable) intake and double adjustable ond elivery (on ly HP W --- D version )Finned (not adjustable) intake and double adjustable ond elivery (on ly HP W --- O version )
8 D i g i t 1 6 --- Free0=FreeoptionalwaysDigit 17 ---Special requirements0=NoneX=Special3 Mechanical SpecificationsLiebert SpecificationsCabinetThe unit is designed to be installed outdoor, coping with the worst weather self---supporting cabinet is made of heavy gauge galvanised steel panels, painted on bothsides with RAL7035 polyester powder, insulated with polyurethane foam, fire---proof class 1. Thebackpanel(wallside)includesintegralsp igots,50mm , aluminum external screws are anti---vandalism type, to be opened with a special tool supplied with theunit. Metal safety grids rated IP20 --- protect the machine and prevent contact with sensitive/dan-gerous circuitThe refrigeration compressor is a hermetic, scroll type, complete with internal protection againstover heating.
9 A crankcase heater maintains a minimum refrigerant temperature to allow reliablestart---up and operation even in very cold circuit is pre---charged with refrigerant and includes a thermostatic expansion valve, filterdryer and sight glass, low pressure and high pressure switches and two access compressor is housed in a compartment separated from the air flow and protected by aninsulated panel closed with anti---vandalism screws, accessible from the front side for sectionA single coil with copper tubes and aluminum fins, having a large heat exchange surface to re-duce humidity removal and increase galvanized steel condensate drain tray (10/10 mm thick) is fanEvaporator fans are centrifugal type, with backward curved blades (plug---type), direct driven byintegral electric are statically and dynamically balanced with self---lubricated bearings, equipped with an airflow sensor as standard to provide an alarm in case of low air sectionA wide surface condensing coil (L or U shape) is provided.
10 It is designed in copper tubes withaluminium fins and sized to allow operations at least up to up to 50_C outdoor air fanThe condenser fan is of the axial type, with integral IP54 motor and internal thermal protection,statically and dynamically balanced, including sealed---for---life bearings. Blades, impeller andcasing are made from corrosion---proof is protected by metal safety grids, rated filterThe filtering system iscomposed by twofilters, one for the indoor air and one for the fresh air (eas-ily removable from the front outdoor side of the unit). Filters are pleated type (except indoor airfilter on over version) with a synthetic fiber surface and metal frame, giving G3 class efficiency(CEN---EN) as panelThe electrical board is housed in a compartment isolated from the air stream and closed by ascrewed on panel.