LIFEALARM PHOTOELECTRIC SMOKE DETECTOR FOR TWO …

FeaturesLIFE alarm PHOTOELECTRIC SMOKE DETECTOR with on-board sensitivity drift compensation* functional chamber enclosure: Louvered design enhances SMOKE capture by direct-ing flow to chamber Entrance areas are minimally visible when ceilingmountedMulti-function indicator LED indicates normal andalarm conditionsMagnetically operated functional test: Initiates alarm and verifies performance Identifies general sensitivity status using DETECTOR LEDM odels available in two sensitivity settings: Part No. 430559 (Part No. 430695 ULC), StandardSensitivity, nominal obscuration Part No. 430562, Special Application Sensitivity, nom-inal obscurationAvailable base options: Bases for 2-wire operation Auxiliary alarm relay outputOptional remote alarm indicating LEDD escriptionLIFE alarm PHOTOELECTRIC detectors provide many of theproven analog sensing features for applications wheredetectors are connected to conventional 2-wire initiatingdevice circuits (IDCs).

Features LIFEalarm® Photoelectric smoke detector with on- board sensitivity drift compensation* Functional chamber enclosure: • Louvered design enhances smoke capture by …

Tags:

  Functional, Smoke, Detectors, Photoelectric, Photoelectric smoke detectors

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of LIFEALARM PHOTOELECTRIC SMOKE DETECTOR FOR TWO …

1 FeaturesLIFE alarm PHOTOELECTRIC SMOKE DETECTOR with on-board sensitivity drift compensation* functional chamber enclosure: Louvered design enhances SMOKE capture by direct-ing flow to chamber Entrance areas are minimally visible when ceilingmountedMulti-function indicator LED indicates normal andalarm conditionsMagnetically operated functional test: Initiates alarm and verifies performance Identifies general sensitivity status using DETECTOR LEDM odels available in two sensitivity settings: Part No. 430559 (Part No. 430695 ULC), StandardSensitivity, nominal obscuration Part No. 430562, Special Application Sensitivity, nom-inal obscurationAvailable base options: Bases for 2-wire operation Auxiliary alarm relay outputOptional remote alarm indicating LEDD escriptionLIFE alarm PHOTOELECTRIC detectors provide many of theproven analog sensing features for applications wheredetectors are connected to conventional 2-wire initiatingdevice circuits (IDCs).

2 Each DETECTOR has an on-boardmicroprocessor that evaluates its PHOTOELECTRIC lightscattering chamber activity and makes an intelligentdecision based on light obscuration history as towhether an alarm condition is detectors are packaged in a patented hous-ing that minimizes the visibility of the air intake louversfrom the normal viewing locations while maintaining ahigh performance SMOKE capture ability. Bases areavailable for remote alarm LED indicator connectionsand auxiliary relay and Approvals ULListed ULC Listed FMApproved CSFM (Pending) MEA (NYC) (Pending)* LIFE alarm SMOKE DETECTOR operation is protected by one or more of the fol-lowing Patents: 5,515,468; 5,173,683; 5,543,777; 5,710,541;D383,407; D388,352.

3 D392, AND CONTROL EQUIPMENTDATA SHEETLIFEALARM PHOTOELECTRIC SMOKEDETECTOR FOR TWO-WIRE BASESPC2003002 One Stanton StreetMarinette, WI 54143006564 LIFE alarm PHOTOELECTRIC DETECTOR Mounted in BaseVoltage15 to 32 VDC, fromControl Panel IDC Standby Current100 A @ 24 VDCA larm Current,Up to 86 mA maximum,2-Wire Operationexact current is determinedby alarm current limiting ofconnectedIDCA uxiliary Relay RatingsRefer to page 2 underProduct SelectionAir Velocity Range0-2000 ft/min (0-610 m/min)UL Listed Temp. Range 32 to 100 F (0 to 38 C)Operating Temp. Range 15 to 122 F( 9 to + 50 C)Humidity Range10% to 95% RH from32 to 122 F(0 to 50 C) non-condensingColorFrost WhiteDimensions4 7/8 in. Dia. x 1 7/8 in. H,mounted in base(124 mm x 48 mm)SpecificationsSmoke DETECTOR FeaturesIntelligent Data Evaluation.

4 Conventional smokedetectors will typically drift toward being too sensitivedue to the accumulation of dust and dirt. With analogdetection, data from the PHOTOELECTRIC chamber is moni-tored and analyzed at the DETECTOR to provide a continu-ously shifting reference point. Drift Compensation. The data evaluation and its shift-ing reference point provide a software filtering processthat compensates for environmental factors (dust, dirt,etc.) and component aging, establishing an accuratereference for evaluating new activity. With this filtering,the resulting drift compensation provides a significantreduction in the probability of false or nuisance alarmscaused by shifts in sensitivity either up or Test Information.

5 Status information is avail-able by performing the magnetic test and observing thedetector LED pulses. The LED will normally go directlyinto alarm with the magnetic test. If there is an off-nor-mal condition, the LED pulses first to indicate the condi-tion and then goes into ReferenceDetector Locations. Locations should be determinedonly after careful consideration of the physical layoutand contents of the area to be protected. For further detailed installation information, refer toDetectors, Sensors, and Bases Application Manual,Part No. Selection. The standard sensitivity detec-tor, Part No. 430559, is recommended for most applica-tions. When a special application for a reduced sensitiv-ity DETECTOR is required, Part No.

6 430562 should be con-sidered. Consult Ansul for assistance in determining theproper SelectionSmoke DetectorsPart SensitivityCompatibility430559 LIFE alarm (standard)Compatible with DETECTOR bases:430695 (ULC)430562 PHOTOELECTRIC Nos. 430567 and 430569 Compatible BasesPart Basewith connections for IDC and LED connections are screw terminals430701 (ULC) Remote Alarm LED Indicatorfor in/out wiring, 18 to 14 AWG4305692-Wire Base with Auxiliary Alarm RelayRelay Ratings, Dual Form "C",For Suppressed Loads:& connections for Remote LED Indicator Power limited, 1 A @ 28 VDCNOTE:Must be connected as the only device Non-power limited, 1/2 A @ 120 VACon the IDC to ensure relay Connections (In/Out where required):4305702-Wire Base with Remote LED Indicator Relay contacts and IDC ( ), color coded430703 (ULC)18 AWG leads430572 Remote LED Alarm Indicator IDC (+) and LED wiring, screw terminals for430704 (ULC)18 to 14 AWGD etector AccessoriesPart Plate Required for mounting to 4 in.

7 Square box,fits 4 in. octagonal box May be used when retrofitting existing bases Compatible with Part No. 430567 and Part DETECTOR bases430572 Remote LED Indicator Mounted on single gang stainless steel plateLED IndicationStatusPulses approximately every 4 secondsNormalSteady OnAlarmLED Response to Magnetic Test *LED IndicationFollowed ByStatusActionLED turns ONAlarm is initiatedNormal,sensitivity is withinNonecompensation rangeLED pulses quickly,Alarm is initiatedMore sensitive,out of normalCleaning or othe6 times in 3 seconds,compensation rangeservice is requiredrthen turns ON LED pulses slowly,Alarm is initiatedLess sensitive, out of normal4 times in 8 seconds,compensation rangethen turns ONDoes not initiate AlarmDetector is malfunctioningService is requiredDetector Status LED IndicationsDimensions and Reference Information* Testing requires placing a magnet at the designated location on the DETECTOR cover for 4 seconds.

8 Refer to Application Manual, Part No. 431424, for fur-ther test and maintenance ADAPTER PLATE, PART NO. 430646(REQUIRED FOR 4 IN. SQUARE BOX)PARTNO. 430559 AND PART NO. 430562 DIMENSIONS MOUNTED ON BASEREMOTE RED LED INDICATOR, PART NO. 430572(NOT TO SCALE)6 3/8 IN.(162 mm)4 7/8 IN.(124 mm)LED STATUS INDICATOR(WITH CLEAR LENS)BASE HEIGHT11/16 IN. (17 mm)1/4 IN. ( mm)1 7/8 IN.(48 mm)006567006565 Mounting Information006566 ADAPTER PLATE, PART NO. 430646, REQUIREDFORMOUNTING TO SURFACE MOUNTEDBOXES AND TO 4 FLUSH MOUNT BOXESFLUSH MOUNT REFERENCE, MOUNT EVEN WITH FINALSURFACE, OR WITH UP TO 1/4 IN. ( mm) MAXIMUM RECESS4 IN. (102 mm)SQUARE BOX4 IN. (102 mm)OCTAGONAL BOX1 1/2 IN. (38 mm)MINIMUM BOX DEPTHPARTNO. 430569 INCLUDES ARELAY MODULE THATMOUNTS IN BASE ELECTRICALBOXSMOKE DETECTOR BASES,PARTNOS.

9 430567 AND 430569 SMOKE DETECTOR , PARTNOS. 430559 AND 430562 SURFACE MOUNT REFERENCEELECTRICAL BOX REQUIREMENTS:WITHOUT RELAY(BASE, PART NO. 430567):4 IN. OCTAGONAL OR 4 IN. SQUARE, 1 1/2 IN. DEEPSINGLE GANG, 2 IN. DEEPWITH RELAY(BASE, PART NO. 430569):4 IN. OCTAGONAL, 1 1/2 IN. DEEP, WITH 1 1/2 IN. EXTENSION RING4 IN. SQUARE, 1 1/2 IN. DEEP, WITH 1 1/2 IN. EXTENSION RINGPYRO-CHEM is a trademark of Tyco International Services AG or its affiliates.