Example: quiz answers

Listed and Certified Gas Detection for Sewage …

Detection at every and Certified Gas Detection for Sewage collection treatment FacilitiesIn Compliance with NFPA 820 Pumping Stations Wet Wells Primary Sedimentation Flow Equalization Tanks Headworks Oxygen Aeration Tanks Grit Removal Screening Disinfection Clarifiers Denitrification De-chlorination Bar Screen Area Sludge Storage Pre-aeration Tanks Scum Handling Areas Odor Control Areas Methane Recovery Ammonia Stripping Sludge treatment Digesters In Buildings Digester Gas Storage / Processing Underground Tunnels Co-generation SystemsUniversal Point Gas Monitor Accepting Combustible (Infrared or Catalytic), Toxic, and Oxygen Gas SensorsDetection at every 2 or 3-Wire Transmitter Models Accepts All SensAlert Plus Sensors for Toxic or Combustible Gases and Oxygen Deficiency Optional HART and Modbus Communication ProtocolsNon-Intrusive User Interface Fully Configurable, Assignable Relays with Time Stamped Calibration-Event Data, Sensor End of Life Data and Warning Test-on-Demand Function for Automated Bump TestsFM Certified for Hazardous Classified Areas Class I, II and III, Div.

Detection at every point. Listed and Certified Gas Detection for Sewage Collection Treatment Facilities In Compliance with NFPA 820 ^ t t W ] u ^ ] u v & o }

Tags:

  Treatment, Collection, Facilities, Detection, Sewage, Gas detection, Gas detection for sewage collection treatment facilities

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of Listed and Certified Gas Detection for Sewage …

1 Detection at every and Certified Gas Detection for Sewage collection treatment FacilitiesIn Compliance with NFPA 820 Pumping Stations Wet Wells Primary Sedimentation Flow Equalization Tanks Headworks Oxygen Aeration Tanks Grit Removal Screening Disinfection Clarifiers Denitrification De-chlorination Bar Screen Area Sludge Storage Pre-aeration Tanks Scum Handling Areas Odor Control Areas Methane Recovery Ammonia Stripping Sludge treatment Digesters In Buildings Digester Gas Storage / Processing Underground Tunnels Co-generation SystemsUniversal Point Gas Monitor Accepting Combustible (Infrared or Catalytic), Toxic, and Oxygen Gas SensorsDetection at every 2 or 3-Wire Transmitter Models Accepts All SensAlert Plus Sensors for Toxic or Combustible Gases and Oxygen Deficiency Optional HART and Modbus Communication ProtocolsNon-Intrusive User Interface Fully Configurable, Assignable Relays with Time Stamped Calibration-Event Data, Sensor End of Life Data and Warning Test-on-Demand Function for Automated Bump TestsFM Certified for Hazardous Classified Areas Class I, II and III, Div.

2 1 or 2 Groups A, B, C, D, E, F and G Performance Tested and Certified SensorsIntrinsically Safe Sensor Head Simple Remote Sensor or Duct Mount Permits Hot-swap of Sensor for Shop or Field Calibration Hot Work Permit is Not RequiredFM Certified Intelligent Sensors Calibration and Application Parameters Stored in Onboard Non-volatile Memory for Auto-recognition and Setup upon Sensor InstallFlexible Installation or Retrofit 2-Wire or 3-Wire Transmitters Remote Sensor / Gassing Configurable Alarms and Fault Currents Conditions PRODUCT SPECIFICATIONSE nclosure Material ..NEMA 3R Fiberglass wall mount with two 3/4 conduit entries Dimensions: ..11 (H) X 10 (W) X (D) ( X X ) Weight:.. lbs ( kg) Temperature: ..-4 to 104 F (-20 to 40 C) Humidity: ..5-95% RH, non-condensing for indoor or outdoor locations. Indicators and Controls External: ..Flowmeter, green power LED and red fault/low flow LED Internal.

3 On-Off switch, voltage out adjust and flow rate adjust Outputs: ..Two 24 VDC power terminals, SPDT fault/low flow relay contact Power In/Out: 85 264 VAC, 47-63 Hz, Amps; 24 VDC, Amp Hazloc ..FM approved* for Class I, Division 2, Groups C & D location to sample from Class I, Division 2,Groups C DC Supply: ..UL60950-1, UL508, UL1310(3), EN60950-1, CE Mark Pump: ..Diaphragm type rated at lpm @ 40 H2O at pressurized leak rate of < inch wc drop in 5 seconds at 25 inches wc Wetted parts: ..Polycarbonate, Neoprene, Tygon 2075, Silicone Silastic, 304/316ss, Buna-N, Brass, PVC, Glass, Acrylic and User TubingCautionsDo not use for Acid gases such as Cl2, ClO2, HCl, HF, HCN, NH3, NO2, SO2 and others since the PPM gases are absorbed by the tubing, moisture and various wetted parts slowing or completely eliminating response to the target gas. Do not attempt to use below freezing without heat tracing and a means to keep the system above 32 F (0 C).

4 Excessive condensation will occur when sampling from a higher to a lower temperature.* FM approval SENSIDyNE ADvANTAgEThe Sensidyne SensAlert Plus is FM and CSA approved for unrestricted Hazardous (Classified) Area installation and operation. Plus Series Combustible, Toxic, and Oxygen gas sensors are performance tested and Certified to FM and ATEX standards for assured reliability. The sensor head is Certified Intrinsically Safe enabling shop calibration and hot-swap without declassifying the area. System components, such as Sample Draw, are also FM approved and Listed as required by NFPA understands wastewater applications and works directly with customers to deliver effective and reliable solutions to their gas Detection requirements. Sales and on-site service personnel are knowledgeable and experienced to help resolve application issues and provide local training and ongoing support. Class 1 Division 2 or Non-hazardous AreaOutdoor ventAlarm Contacts4-20 mA RS-48524 vDCCalibration gas InletCoalescing Filter + DrainAC or DC Power InAC Annunciation3-Way valveAir Sample From Class I, Division 1, group C or D Area GasFormulaDensityTLV/LELSpanTypePart Number Ammonia* ppm/15%100 ppmLI, EC, D823-0201-21 Ammonia* 25 ppm/15%300 ppm LI, EC, D823-0201-41 Carbon , 3% IDLH5% volInfrared823-0205-52 Carbon Monoxide* ppm100 ppmEC, ND823-0219-23 Bleach (Use Cl2)

5 Ppm5 ppmLI, EC823-0202-22 Chlorine* ppm5 ppm LI, EC823-0202-22 Chlorine* ppm10 ppm LI, EC823-0202-21 GasolineHC Mixture2 to 4 vol100% LELI nfrared823-0211-51 Hydrogen Chloride* ppm20 ppmEC, ND823-0208-22 Hydrogen Sulfide* ppm10 ppmEC, ND823-0206-23 Hydrogen Sulfide* ppm50 ppmEC, ND823-0206-22 Hydrogen Sulfide* ppm100 ppmEC, ppm/250 ppm STEL500 ppmEC, vol100% LELI nfrared823-0211-51 Natural vol100% LELI nfrared823-0211-51 NitrogenN2 Monitor O2 Deficiency- -- -- -OxygenO2~ , IDLH25% volEC, D823-0240-22 Sewer GasCO2, CH4~ vol100% LELI nfrared823-0211-51 Sludge GasCH4, CO2~ vol100% LFLI nfrared823-0211-51 Sulfur Dioxide* ppm10 ppmEC, ND823-0218-22* Additional Ranges Available LI: Low Interference; EC: Electrochemical; D: Depleting with Gas Exposure; ND: Non-depleting with ExposureTLVs from ACGIH or OSHA, IDLH from NIOSH, STEL from ACGIH, LELs from NFPA 325 and NFPA 820 Listed Gas Detection Sample Draw SystemTyPICAl WET WEll gAS Detection SySTEm WITh SAmPlE DRAWREmOTE SENSOR KITSR emote Calibration Fixture821-0218-01 Run rigid condulet to mounted gas sensors with remote gassing simplify monitoring difficult access areas for Methane or other hazards.

6 Sensors may also be duct mounted in the same manner. The Transmitter is at face level for ease of routine Numbers821-0207-02 Division 1823-0207-01 Division 2100 Feet Maximum Belden 27326 ASCable by , Condulet, Seal, and Cable Glands 112th Circle North, Suite 100 St. Petersburg, Florida 33716 : 800-451-9444 / +1 727-530-3602 Fax: +1 2013 Sensidyne, LP WWTP-Brochure-Rev. B Seal Required in Division 1 Detection at every and References1 US EPA, 832-R-04-001, September 2004, Office of Wastewater Management, Washington DC 204602 The Federal Water Pollution Control Act of 1948, 1972 Amendments to Clean Water Act, and continuing Amendments to 20113 NFPA 820, Standard for Fire Protection in Wastewater treatment and collection facilities , 10 States Recommended Standards for Wastewater facilities , Great Lakes - Upper Mississippi River Board of State and Provincial Public Health4 NFPA 70, National Electrical Code, Article 500, Hazardous (Classified) Intrinsically safe equipment and wiring shall not be capable of releasing sufficient electrical or thermal energy under normal or abnormal conditions to cause ignition of a flammable or combustible atmospheric mixture in its most easily ignitable state.

7 Nearly 16,000 municipal Sewage collection and treatment systems in the US, serve over 75 percent of the population 1. The facilities have exceptional regulatory 2, environmental and safety requirements 3 with quality of life consequences for everyone. Sewage collection systems operate on gravity flow to central lift or pumping stations which deliver the raw Sewage to a treatment plant. Sewage decomposition produces Sewer Gas (Carbon Dioxide, Methane, Hydrogen Sulfide, et al) which presents Oxygen deficiency, toxic gas and the risk of fire or explosion hazards. Fuels and industrial solvents might also be in the collection system. All of these gases and vapors require monitoring to provide early warning of life threatening Station Wet Wells and screening exposes workers to sewer gas or floating flammables and these areas are Hazardous 4, Class I, Division 1, Group D. Placing electronic equipment in wet corrosive environments subject to flooding is not practical and seldom done anymore.

8 Listed Sample Draw or remote mounted Intrinsically Safe 5 sensors from Sensidyne are a lower-cost and minimal maintenance solution for all plant applications vary widely but have similar conditions to pumping stations. Sensidyne has proven solutions and support for all water and waste water treatment gas Detection treatment IS BIg BUSINESS 12345678910111214131. Enclosure Certified for Hazardous (Classified) Environments2. Large Backlit Alphanumeric Display (Backlit on 3-Wire only)3. HART or Modbus RS-485 Communication (Optional)4. Alarm Relay Card (Optional)5. Intrinsically Safe Sensor Head6. Test-on-Demand Gas Generator7. Plus Series Intelligent Sensor8. O-ring Seal9. Sensor Retainer10. Moisture Barrier (Optional)11. Remote Gassing Fixture (Optional)12. Sensor Shield13. Flow Block for Remote Sampling and Cal Plug (Optional)14. Baffled Rainshield (Optional)SENSAlERT PlUS ExPlODED vIEW


Related search queries