LOW VOLTAGE DISTRIBUTION

LOW VOLTAGEDISTRIBUTION POWER & CONTROL - General Features 42 - Applications 53 - Product Portfolio 64 - Main DISTRIBUTION Board (EletraGear) 8 Technical Data 9 Appearance 10 Product Breakdown 11 Admissible Current in Copper Bars 12 Main Busbar Supports 12 Dimensions and Possible Layouts 13 Possible Layouts 14 - Air Circuit Breaker 14 - Molded Case Circuit Breaker 155 - Sub DISTRIBUTION Board (EletraSub) 16 Technical Data 17 Standard Dimensions, Number of Ways and Ampere Ratinge 186 - Final DISTRIBUTION Board (Eletra-LD) 20 Technical Data 21 Standard Dimensions, Number of Ways and Ampere Ratinge 227 - Synchronizing Panel Board 248 - Automatic Transfer Switches (ATS Panels) 26 ATS Types 279 - Power Factor Correction Capacitors (PFC) 28 Technical Data 2910 - Motor Control Centers (EletraGear Plus) 30 Types of Starters 30 Technical Data 31

EletraGear is designed and tested as per the new IEC standard 61439-1,2. This panel is available up to 6300A, 100kA/ 1 sec, Form 4b. Low Voltage Switchboards are mainly used for electrical power distribution and control.

Tags:

  Distribution, 61439, New iec

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of LOW VOLTAGE DISTRIBUTION

1 LOW VOLTAGEDISTRIBUTION POWER & CONTROL - General Features 42 - Applications 53 - Product Portfolio 64 - Main DISTRIBUTION Board (EletraGear) 8 Technical Data 9 Appearance 10 Product Breakdown 11 Admissible Current in Copper Bars 12 Main Busbar Supports 12 Dimensions and Possible Layouts 13 Possible Layouts 14 - Air Circuit Breaker 14 - Molded Case Circuit Breaker 155 - Sub DISTRIBUTION Board (EletraSub) 16 Technical Data 17 Standard Dimensions, Number of Ways and Ampere Ratinge 186 - Final DISTRIBUTION Board (Eletra-LD) 20 Technical Data 21 Standard Dimensions, Number of Ways and Ampere Ratinge 227 - Synchronizing Panel Board 248 - Automatic Transfer Switches (ATS Panels) 26 ATS Types 279 - Power Factor Correction Capacitors (PFC) 28 Technical Data 2910 - Motor Control Centers (EletraGear Plus)

2 30 Types of Starters 30 Technical Data 31 IDS Technology 32 IDS System Features 33 Arc Safe Vertical Bus Section 34 Pressure Contact 34 Arc Fault Free Contacting Device 3411 - Switch-Rack 3512 - Customer Reference 36 new iec Std 61439 36 Separation Forms 37 Ingress Protection (IP) 38 IK Code Mechanical Impact Test 39 Arc Flash Protection 40 Anti-seismic Switchboards and Withstand for Vibration 41 Definitions 4241 - General FeaturesReliability and Service Continuityalfanar products are designed to withstand the toughest environmental conditions and offer an extremely high level of reliability even under the toughest temperature performance up to 50 C without derating with alfanar ACBs and framework to guarantee increased resistance to earthquakes as per (IEC 60068-3-3:2013).

3 Our products offer a variety of protection levels (IP40, IP42 up to IP66) for use in a variety of applications and harsh environments such as cement works, wet areas, iron and steel industry, and User Friendly alfanar products provide years of safe, reliable mechanical structure (frame) and the main busbar systems are designed to be maintenance-free and accessible from the eliminating the need to access the equipment from the rear, our equipment can be installed virtually anywhere in a modular design allows for easy installation, operation and maintenance and will accommodate most project specifications and quality systems and solutions are developed according to relevant international standards, offering a high degree of personal and operating - Applicationsalfanar Low VOLTAGE products are used for electrical power DISTRIBUTION and control and are generally installed downstream of transformers or generators that contain the main and DISTRIBUTION circuit breakers.

4 Loads are motors, heating equipment, lighting and air-conditioning , Infrastructure and Industrial:Airports, hospitals, factories, shopping malls, hotels, commercial and residential : Power generation, transmission, DISTRIBUTION substations, water and waste water treatment and Gas: Oil and gas plants, petrochemical plants and DISTRIBUTION BoardSwitch-Rack 3 - Product PortfolioEletraGear Main DISTRIBUTION BoardATS, Synch, 2 out of 3,.. PFC Power Factor CorrectionEetraSubSub DISTRIBUTION BoardEletraGear PlusMotor Control Center8 EletraGear Overview Tested for Internal Arc Fault as per (IEC-61641:2014) for 100KA, 300 m sec (Classified as PSC ). Tested to withstand vibration caused by an earthquake of Richter magnitude 8 (Zone - 4), in accordance with (IEC 60068-3-3:2013). The design makes it suitable for seismic risk sites such as the western region of KSA. RAL7035 color is standard, other colors can be provided upon request. Neutral and earth busbars can be rated up to 100% of the main busbar.

5 Optimized solution with compact design provides 6300A in 800mm depth IEC 61439 -1 & 2 IEC 60529 IEC62262 IEC 61641 IEC60068-3-3 IEC60068-2-57 IBC2006/SBC301 SBC401 SASOTest Certificate (ASTA / KEMA)4 - Main DISTRIBUTION Board (EletraGear)A switchboard is a large single panel, frame, or assembly of panels on which are accessed from front, rear or both sides. They are generally installed immediately after the power source (transformers or generators).EletraGear is designed and tested as per the new iec standard 61439 -1,2. This panelis available up to 6300A, 100kA/ 1 sec, Form VOLTAGE Switchboards are mainly used for electrical power DISTRIBUTION and DataEnclosure NameEletraGearElectrical DataRated voltageRated operating VOLTAGE UeUp to 690 VRated insulation VOLTAGE UiUp to 1000 VRated impulse withstand VOLTAGE UimpUp to 12 kVOvervoltage categoryUp to IV Material groupIIIaDegree of pollution3 Rated frequency50/60 HzRated currentBusbar typePure copper bars.

6 With Rated current for main DISTRIBUTION busbar InUp to 6100 AConditional short circuit current IccUp to 100 kA @ short-time withstand current Icw Up to 100 kA @ 1 SecRated short-time withstand current Icw Up to 65 kA @ 3 SecRated peak withstand current IpkUp to 220 kAIncoming and outgoingIncoming feedersUp to 6300 ADistribution feedersUp to 6300 AArc fault Prospective short-circuit currentUp to 100 kA @ 300 ms Direct contact protectionForm of separationUp to 4bProtection against electric shock YesSeismic withstand capability test and induced vibrationsYesVentilationForced / NormalMechanicalCharacteristicsSkid base heightUp to 300 mmNumber of useful modules (1 module = 50mm)43 MDegree of protectionExternal mechanical impacts strength IKUp to IK10 External degree of protection IPUp to IP55 Steel componentsFrame thicknessUp to 3 mmSheet metal materialAluZinc steelElectrogalvanized /Stainless SteelSurface protectionElectrostatic powder coating/ EpoxyStandard colorsRAL7035*Panel mountingFree standing onlyGeneralInstallation environmentAmbient temperature ( C)

7 40*Relative humiditymax 50% at 40 CMaximum altitudeUp to 2000m*BusbarBusbar system3 PH, Neutral and PEBusbar insulating materialPVC sleevingBusbar plating materialBare / tin / silver*For higher altitude ,ambient temperature and special colors please contact its new design, alfanar EletraGear has changed the concept of the bulky LV main DISTRIBUTION board and moved the competition to the next level, it is manufactured and tested to fulfil the ultimate needs in all s ability to change the color of the switchgear according to customer requirments and applicable standards( RAL and ANSI series ) fortifies the unique appearance and Breakdownalfanar switchgear is precisely sized to meet your requirements and budget. Each main DISTRIBUTION board provides a ready to use optimized solution, designed to the exact size and requirements for your specified functional busbar6 Roof2 Busbar connection to main horizontal busbar 7 Cable compartment3 Incomer ACB breaker 6300 Amp8 Outgoing ACB breaker 4000 Amp4 Cable connection9 Horizontal MCCB solution5 Frame member10 Skid base1679108543212 Admissible Current in Copper BarsMain Busbar SupportsFor increased safety and to guarantee a higher level of short circuit without any side effects, EletraGear provides its design features and possible short circuit.

8 Short circuit level30 kA50 kA 65 kA 85 kA 100 kABusbar typeMax. distance between supportsVBB600 mm400 mm300 mm250 mm250 mm*HBB700 mm650 mm550 mm380 mm400 mm*Please contact alfanarThe current available inside the horizontal copper bars, based on the number, cross-section and the outside ambient temperature is shown in the following current in plated copper for 40 C without ventilation and 50 C with forced cooling: Busbar Size (mm)AmpQuantity WidthThickness1b20102501b30104001b301060 01b50106301b55108001b60101000*1b70101000 1b851012502b551016002b701020002b85102500 3b851030003b1001032004b1001040004b150105 0005b150106300*for MCC only All sizes mentioned in the above table are subject to manufacturer s technical recommendation changes In case of higher ingress protection over IP 43, forced ventilation is recommended In case of ratings of 4000A and higher, forced ventilation is recommended Maximum allowed size for the VBB feeding multi branch breakers = 3 x 85 x 10 Dimensions and Possible LayoutsFor special dimensions upon requestHeight (mm)160018002300 Width (mm)40060080010001200 Depth (mm)60080010001200 For more information please contact alfanarEletraGear cubicles have the following representative dimensions, constructed to provide the best solution using minimum space without affecting power efficiency.

9 Height (mm)2150 Width (mm)40060080010001200 Depth (mm)800 For more information please contact alfanarWDH14 Possible Layouts Air Circuit BreakerWidth 600 mm800 to 2000 AmpDepth 800 mmWidth800 mm2500 to 4000 AmpDepth 800 mmWidth1200 mm5000 to 6300 AmpDepth 800 mm Molded Case Circuit BreakerEletraGear type tested MCCB panel boards are designed for easy handling and quick, simple compact MCCB design provides a maximum cabling area within the enclosure with removable top and bottom gland plates for easier installation and cable 3 / 4 Form 1 / 2 Width1000 mm800 mmDepth 800 mm800 mmBased on the modular configuration of each solution, various arrangements are available according to the size and polarity: Up to form 4b in width 1000 Up to 11 125 or 250 AF alfanar MCCBs 3P can be placed in one cubical for form 3 / 4 Up to 24 125 or 250 AF alfanar MCCBs 3P can be placed in one cubical for form 1 / 216 The EletraSub DISTRIBUTION Board is is a component of an electricity supply system which divides an electrical power feed into subsidiary circuits while providing a protective fuse or CB for each Sub Main DISTRIBUTION Board (EletraSub) serves as a complete solution for the DISTRIBUTION of power and is available up to 630A.

10 The design provides complete flexibility at the time of installation, complying with IEC 61439 -1, Overview EletraSub is used in a variety of sectors such as utilities and co-generation, pharmaceutical factories, generator manufacturers, critical power plants, data centers and in the oil and gas industry. Easy interchangeability of components Wall mounted and free standing designs Available in 2/14 way (3 Pole) to 6/42 way (1 Pole) outgoing MCCB s Enclosure Protection Class up to IP66 Bare Copper / tin plated / silver plated / PVC sleeved copper busbars Available in stainless steel enclosures for outdoor applications Neutral and earth busbars can be rated up to 100% of the main busbar Internal separation up to Form-3a5 - Sub DISTRIBUTION Board (EletraSub)Standards IEC 61439 -1 & 2 IEC 60529 IEC62262 IEC 61641 IEC60068-3-3 IEC60068-2-57 IBC2006/SBC301 SBC401 SASOTest Certificate (ASTA /UL)