Example: air traffic controller

Mechanical Release Fire Smoke Dampers - …

Model 2550 Mechanical ReleaseFire Smoke DampersAdvanced AirISSUE A, MAY 2008 Dampers for fire and Smoke ApplicationsMechanical Release fire Smoke Dampers - Type 25502 Advanced AirMechanical ReleaseFire Smoke DampersType 2550 The model 2550 is designed to close and stay closed ina fire situation creating a 4 hour fire rated barrier to stopthe spread of fire , Smoke and toxic fumes. The 2550incorporates the new unique interlocking opposed bladedesign that eliminates the need for blade seals whichburn out during fire conditions. The blade profile is ofaerodynamic double skin construction, and gives a metalto metal seal, which achieves low leakage performanceas stipulated in BS EN1366-2 ES classification for 240minutes in both horizontal and vertical 2550 includes a unique and versatile jackshaftarrangement with a Mechanical fusible link rated at 74 C.

Dampers for Fire and Smoke Applications Mechanical Release Fire Smoke Dampers - Type 2550 2 Advanced Air Mechanical Release Fire Smoke Dampers Type 2550 The model 2550 is designed to close and stay closed in

Tags:

  Mechanical, Release, Fire, Smoke, Dampers, Mechanical release fire smoke dampers

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Advertisement

Transcription of Mechanical Release Fire Smoke Dampers - …

1 Model 2550 Mechanical ReleaseFire Smoke DampersAdvanced AirISSUE A, MAY 2008 Dampers for fire and Smoke ApplicationsMechanical Release fire Smoke Dampers - Type 25502 Advanced AirMechanical ReleaseFire Smoke DampersType 2550 The model 2550 is designed to close and stay closed ina fire situation creating a 4 hour fire rated barrier to stopthe spread of fire , Smoke and toxic fumes. The 2550incorporates the new unique interlocking opposed bladedesign that eliminates the need for blade seals whichburn out during fire conditions. The blade profile is ofaerodynamic double skin construction, and gives a metalto metal seal, which achieves low leakage performanceas stipulated in BS EN1366-2 ES classification for 240minutes in both horizontal and vertical 2550 includes a unique and versatile jackshaftarrangement with a Mechanical fusible link rated at 74 C.

2 In alarm condition the power to the actuator is removedclosing the blades within 16 seconds. When the temperature is reached the fusible link breaks the connectionbetween the actuator and the blades. The blades are then held in the closed position by the knee-lock mechanismand can not be reopened until the fusible link has been replaced. The jackshaft arrangement allows multiple section units to be connected and driven by one actuator depending ontorque requirements. The 2550 damper is available with spigotted connections. Various installation option s areavailable, examples are detailed in our Methods of Installation Manual. This product is flexible and versatile and canbe modified to meet most special requirements on size and & Benefits Independently tested to the BS EN1366 -2 testfor integrity and leakage requirements achievingan ES240 classification.

3 Unique double skin blade design that achieveslow leakage tested to British and Americanstandards without the need for synthetic bladeseals. Closure maintained by the unique knee-lock mechanism which prevents blades from re-opening the damper. Wide range of actuators are available fromBelimo, Honeywell and Johnson's to meet mostrequirements. Junction box that allows easy site wiringconnection. All components fitted to the damper soinstallation simple and straight forward,therefore no additional modification to SpecificationBlades: Double skin galvanised mild steel asstandard. Double skin grade 430 stainless galvanised mild steel standard, 430 stainless steel optionalFrame Corners:Die formed corner channels, buttonlocked for strength and rigidityCasings: galvanised mild steel standard, grade 430 stainless steel optionalCasing Corners:Welded mitre corners finished withaluminium aerosol :External linkage.

4 Enclosed within the frameand out of air stream. Zinc electroplated mild : Oil filled sintered bronze up to 200 diameter zinc electroplated mild steelbolted directly through the :Zinc electroplated mild , Bottom & Side Jamb Seals:Cambered grade301 stainless AirDampers for fire and Smoke ApplicationsMechanical Release fire Smoke Dampers - Type 2550 Control OptionsStandard Control - Spring ClosedThe actuator without power the blades will be in the closed position and when power applied the blades will fullyopen. In alarm the power would be removed the damper blades fully close within 16 seconds. When the mechanicalfusible link reaches 74 C it breaks breaking the connection with the actuator. The blades would not reopen until thefusible link is Open - Fail Safe ClosedThe damper without power the blades will be in the open position and when power applied the blades will close fullyshut.

5 In alarm the power would be removed and the blades will fully open within 16 seconds until the mechanicalfusible link reaches 74 C the blades will instantly shut by breaking the connection to the - Volume ControlThe actuators without power the blades will be in the closed position and when power is applied the blades will fullyopen. From the open position through a signal 0-10 volts the damper blades can be adjusted between fully open andfully closed allowing volume control. In alarm the power is removed closing the blades within 16 seconds. When themechanical link reaches 74 C it breaks the connection to the actuator. Blade Indication - Micro switchesTo give indication of the blade position to BMS or similar micro switches that can be supplied integral to the actuatoror mounted within the DetailsNLComNCNOComNCNO12212223242526 BlueBrownBlk/RedBlk/BluBlk/GryWht/RedWht /BluWht/Gry12212223242526 BlackRedBlk/RedBlk/BluBlk/GryWht/RedWht/ BluWht/GryM9210-BDC-3 orM9220-BDC-3 (230V)M9210-BGC-3 orM9220-BGC-3 (24V)10 Switch80 Switch2550 type Dampers with electrical actuators are suppliedto site with the flying leads of the actuator coiled up for on-site wiring diagram (right) shows the standardconnections for all Johnson type actuators.

6 For furtherdetails, or full wiring details for other actuator types,please contact Advanced Air Sales. Dampers for fire and Smoke ApplicationsMechanical Release fire Smoke Dampers - Type 25504 Advanced AirDimensional DetailMultiple Section UnitsFor requirements over the maximum allowable single section size, Advanced Air Dampers can be provided in multiplesection arrangements. Please contact Advanced Air Sales for further multiple arrangements of Dampers are required to be fitted, the installer should submit their proposedarrangement to the relevant local authority of fire officer responsible for installation,For all other spigot and frame types, contact Advanced Air - 4mmNDH - 4mmRectangular Spigotted ModelsNDW - Nominal Duct WidthNDH- Nominal Duct HeightOverall Casing Width/Height = Duct Width/Height + 50mmMinimum Single Section Duct Size: 100mm x 100mmMaximum Single Section Duct Size: 750mm x 1000mmFor damper sizes below 200mm width or height, the casinglength increases.

7 Please contact our Advanced Air sales forfull dimensional Handed Unit - 4mmCircular Spigotted ModelsNDD- Nominal Duct DiameterOverall Casing Width/Height = Duct Diameter + 75mmMinimum Single Section Duct Size: 100mmMaximum Single Section Duct Size: 750mmFor damper sizes below 200mm the casing lengthincreases. Please contact our Advanced Air sales for fulldimensional Handed Unit Shown5 Advanced AirDampers for fire and Smoke ApplicationsMechanical Release fire Smoke Dampers - Type 2550 How to Order or To SpecifySuggested Specification - Mechanical Release fire Smoke DampersFire Smoke Dampers shall be provided in the positions as indicated on the drawings and shall be suitable formounting in the horizontal or vertical plane. They shall be certified by the manufacturer to have been tested to thetemperature time curve of BS ISO 10294 for a period of 4 Hours with a classification of ES 240 as stated in BS fire Smoke Dampers shall have factory fitted installation frames to HVCA specification and the MechanicalContractor shall allow for all additional framing, supports and bracing to secure the damper to the structure to thesatisfaction of the Building Control fire Smoke Dampers to be manufactured with galvanised blades of double skin construction.

8 The blades shall behoused within a galvanised mild steel casing with stainless steel side jambs and spigot connections. The fire smokedamper shall have a Mechanical fail safe fusible link in the air stream set at 74 C which breaks the connection withthe actuator causing the blades to slam shut. (The actuator shall be factory fitted.)The fire Smoke Dampers shall operate up to 1500 Pa positive or negative pressure at a maximum velocity of 20 fire Smoke Dampers shall be independently supported of the ductwork on each side of the blades and mountingframes, supports and sleeves are to be approved by the requisite fire Authorities and Building Control fire Smoke Dampers to be Model 2550 as manufactured by Advanced Air (UK) Ltd or equal and Release fire Smoke Dampers - Type 25502 5 5 0 - 1 1 (0 0 1)ModelMechanical ReleaseFire Smoke Damper255 OperationRight Hand Drive0 Left Hand Drive2 Drive Both Sides (Multiple Sections)5 Duct ConnectionFlanged Frame0 Rectangular Spigot1 Circular Spigot2 Flat-Oval Spigot3 Rectangular Sleeve4 Mounting TypeNone (default)0 HEVAC/HVCA Frame1 Dry Wall/HEVACC ombination Frame6 Dry Wall Flange7 Notes: - Cleats are available as an additional accessory.

9 For further details of installation accessories, please refer to page 32 BearingsOilite (Up To 200 C)3 Construction74 C Fusible Link0 MaterialGalvanised Mild Steel0430 Grade Stainless Steel Blades,Galvanised Mild Steel Casing1430 Grade Stainless Steel Blades and Casing2 Dampers for fire and Smoke ApplicationsInstallation Accessories6 Advanced AirAdvanced Air fire Smoke Dampers can be installed in a variety of walls and floors and to assist with installationdampers can be supplied with accessories to suit. All accessories are factory fitted with following available HEVAC Installation frame allows the damper to be built directlyinto masonry walls and concrete floors. It allows the damper toexpand in fire conditions, thus maintaining the integrity of the wall AccessoriesHEVAC Installation FrameThe Sleeve and Angle frame installation can be used as analternative to the HEVAC frame.

10 A sleeve can be factory fitted to thedamper and additional angles are fixed to the flange whichsandwiches the wall at the same and Angle FrameDry wall frames are can be used in all installations where the damperis being installed into dry wall partitions or together with fibrouscurtains. The frame offers a means of connecting the damperassembly with the Wall Frame 7 Advanced AirDampers for fire and Smoke ApplicationsInstallation AccessoriesAdvanced Air Dampers have been tested when installed in both thevertical (wall) and horizontal (floor) OrientationNote:It is important that the appropriate installation accessory is used to suit on site requirements. For a fire barrierto maintain its integrity in a fire situation the damper must be securely installed and the damper should beindependently supported. Advanced Air are able to discuss your requirements and help with selections.


Related search queries