Example: stock market

Merlin GerinMulti 9 System Protection Miniature Circuit ...

Merlin GerinMulti 9 SystemProtectionMiniature Circuit BreakersGet more with the world s Power & Control specialistProtectionCircuit Breaker Limitation CapabilityThe limitation capability of a Circuit breaker is that characteristic wherebyonly a current less than the prospective fault current is allowed to flow undershort- Circuit is illustrated by limitation curves which give:"The limited peak current in relation to theRMS value of the prospective short-circuitcurrent (the short- Circuit current being thatcurrent which would flow continuously in theabsence of Protection equipment)."The limited current stress in relation to theRMS value of the prospective short-circuitcurrent."Current limiting capability. The advanceddesign of the Multi-9 range provides currentlimitation with far better Protection than con-ventional Circuit breakers. For example, on a6A rating with a prospective short Circuit of5000A, the current will be limited at 350A or7%.

C60N circuit-breakers 6kA, C curve AS/NZS 4898 Approval No: N13634 functions description technical data common to C60N circuit breakers cpower circuit vvoltage rating: 240/415 V AC - for 2P single phase 240/480V v I2t classification: 3 vnumber of cycles (O-C): 20 000 vfoolproof terminal design - moving barrier prevents incorrect cable insertion

Tags:

  C60n

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of Merlin GerinMulti 9 System Protection Miniature Circuit ...

1 Merlin GerinMulti 9 SystemProtectionMiniature Circuit BreakersGet more with the world s Power & Control specialistProtectionCircuit Breaker Limitation CapabilityThe limitation capability of a Circuit breaker is that characteristic wherebyonly a current less than the prospective fault current is allowed to flow undershort- Circuit is illustrated by limitation curves which give:"The limited peak current in relation to theRMS value of the prospective short-circuitcurrent (the short- Circuit current being thatcurrent which would flow continuously in theabsence of Protection equipment)."The limited current stress in relation to theRMS value of the prospective short-circuitcurrent."Current limiting capability. The advanceddesign of the Multi-9 range provides currentlimitation with far better Protection than con-ventional Circuit breakers. For example, on a6A rating with a prospective short Circuit of5000A, the current will be limited at 350A or7%.

2 Installation of current limiting Circuit breakersoffers several advantages:#Better network protectionCurrent limiting Circuit breakers considerablyreduce the undesirable effects of short-circuitcurrents in an installation.#Reduced thermal effectsCable heating is reduced, hence longer cablelife.#Reduced mechanical effectsElectrodynamic forces reduced, thus electri-cal contacts are less likely to be deformed orbroken.#Reduced electromagnetic effectsMeasuring equipment situated near an elec-trical Circuit less Unit VariationsCircuit Breaker MarkingCurve B tripping:3 to 5 times the ratedcurrent (In); Protection of generators,persons, very Ctripping:5 to 10 In; Protection of circuits,general Dtripping:10 to 14 In; Protection of high surgecircuits, welders, trans-formers, MA(magnetic only)tripping: 12 In; Protection of motorstarters (+ thermal pro-tection when combinedwith contactor).

3 Circuit ProtectionA choice of several curvesWhatever Circuit has to be pro-tected, a C60 or C120 circuitbreaker provides the perfectsolution with a suitable Circuit Breaker Model Number2. Tripping Curve3. Circuit Breaker Current Rating4. Operating Voltage5. Rated Breaking Capacity6. Circuit Breaker Part Number7. Electrical Diagram - No. of Poles8. I2t classificationMerlin Gerin Multi 9 SystemMiniature Circuit breakersTripping curvesMarkings & limitation capability123458C60HC63415V~1000032 .. 12345667multi 9 Page 1 Miniature Circuit Breakers up to 63AC60a 6kA3C60H 10kA4C32H-DC 10kA18( Circuit breakers for DC applications)electrical auxiliaires C6010accessories C6016 Miniature Circuit Breakers up to 125AC120N 10kA6C120H 15kA8electrical auxiliaries C12010accessories C12016Tm Motor MechanismTM C60/C12021 Page18mm pole width27mm pole widthFor supplementary technical information, consult AUS010306 Dimensions23 Page 2 Schneider Electric Help Centre: 1300 369 233protectioncircuit-breakers up to 63 AC60a kA, C curveAS/NZS 4898 Approval No: N13634functionsdescriptiontechnical dataC60a Circuit -breakerscpower circuitvvoltage rating: 240 V ACvnumber of cycles (O-C).

4 10 000vfoolproof terminal design- moving barrier prevents incorrect cableinsertion- cable strand centering guides ensurecorrect cable positions and strand groupingvisolation with positive contact indicationvbistable din clip, simplifies disassemblycenvironmentvtropicalisation: treatment 2(relative humidity: 95 % at 55 C)vconnection: tunnel terminals for thefollowing cables:- up to 25A : 25mm2 stranded- 32 to 63A : 35mm2 strandedThe Circuit -breakers combine the followingfunctions:- Protection of circuits against short-circuitcurrents,- Protection of circuits against overloadcurrents,- control,- Protection of persons against C60a Circuit -breakers are used in thedomestic sectors where single phase faultlevels are less than or equal to curveutilisationcables feeding conventional datac power circuitvtripping curves: the magnetic trip unitoperates between 5 and 10 Invbreaking capacity- according to AS/NZS 4898 Icu ultimatebreaking capacity (0-C0 cycle):type rating cataloguewidthquantity (A) numberin boxof 9 mmC curve C60a1P6113542121011355212161135621220113 5721225113392123211358212401135921250113 60212631136121212catalogue numbers11357- isolation,rating voltagebreaking (A) (V)capacityIcu (A) 240 4500 Page 3protectioncircuit-breakers up to 63 AC60N Circuit -breakers6kA, C curveAS/NZS 4898 Approval No: N13634functionsdescriptiontechnical data common toC60N Circuit breakerscpower circuitvvoltage rating: 240/415 V AC- for 2P single phase 240/480Vv I2t classification: 3vnumber of cycles (O-C).

5 20 000vfoolproof terminal design- moving barrier prevents incorrect cableinsertion- cable strand centering guides ensurecorrect cable positions and strand groupingvisolation with positive contact indicationvbistable din clip, simplifies disassemblycenvironmentvtropicalisation: treatment 2(relative humidity: 95 % at 55 C)vconnection: tunnel terminals for thefollowing cables:- up to 25A : 16mm2 flexible with cable end: 25mm2 stranded- 32 to 63A : 25mm2 flexible with cable end: 35mm2 strandedC curveutilisationcables feeding conventional datac power circuitvtripping curves: the magnetic trip unitsoperate between 5 and 10 Invbreaking capacity according toAS/NZS 4898, Icu ultimate breaking capacity(O-CO cycle):ratingtypevoltagebreakingcapacity (A)(V)Icu (A) 0003P4156 000 The Circuit -breakers combine the followingfunctions:- Protection of circuits against short-circuitcurrents,- Protection of circuits against overloadcurrents,- control,- isolation,- Protection of persons against numberstyperatingcatalogue(A)numberC curve C60N1P1257972257984258006258011025802162 5803202580425258053225806402580750258086 3258092P12581122581242581462581510258161 6258172025818252581932258204025821502582 263258233P125825225826425828625829102583 0162583120258322525833322583440258355025 8366325837123456258041212342581825832 Width in modof 9mm - 2 Width in modof 9mm - 4 Width in modof 9mm - 6 Page 4 Schneider Electric Help Centre: 1300 369 233protectioncircuit-breakers up to 63 AC60H Circuit -breakers10kA, B, C and D curvesAS/NZS 4898 Approval No: N13634functionsdescriptiontechnical data common toC60H Circuit -breakerscpower circuitvvoltage rating.

6 240/415 V ACvbreaking capacity- according to AS/NZS 4898,Icv ultimate breaking capacity (O-CO cycle):ratingtypevoltagebreak. cap.(A)(V)Icu (A) , 2P240/41510 0003P, 000vI2t classification: 3vfoolproof terminal design- moving barrier prevents incorrect cableinsertion- cable strand centering guides ensurecorrect cable positions and strand groupingvisolation with positive contact indicationvbistable din clip, simplifies disassemblyvisolation with positive contact indication:opening is indicated by a green strip on thedevice operating handle. This indicatorshows opening of all the polesvnumber of cycles (O-C): 20 000cenvironmentvtropicalisation: treatment 2(relative humidity: 95 % at 55 C)vconnection: tunnel terminals for thefollowing cables:- up to 25A :16mm2 flexible with cable end;25mm2 stranded- 32 to 63A :25mm2 flexible with cable end;35mm2 strandedThe Circuit -breakers combine the followingfunctions:- Protection of circuits against short-circuitcurrents,- Protection of circuits against overloadcurrents,- control,B curveutilisationwhen there are small inrush currents(generators, long cables).

7 Technical datacpower circuitv tripping curve:the magnetic trip units operate between3 and 5 curveutilisationcables feeding conventional datacpower circuitv tripping curve:the magnetic trip units operate between 5and 10 curveutilisationloads with a high inrush current(motors, transformers).technical datacpower circuitvtripping curve:the magnetic trip units operate between10 and 14 isolation,- Protection of persons against 5catalogue numberstype rating BCD (A) CurveCurveCurveC60H1P1258392563925695225 8402564025696425841256422569862584225643 2569910258432564425700162584425645257012 0258452564625702252584625647257033225847 2564825704402584825649257055025849256512 5707632585025652257082P12585225653257092 2585325654257104258542565625712625855256 5625713102585625658257141625857256592571 5202585825660257162525859256612571732258 6025662257184025861256632571950258622566 525721632586325666257223P125865256672572 3225866256682572442586725670257266258682 5671257271025869256722572816258702567325 7292025871256742573025258722567525731322 5873256762573240258742567725733502587525 67925735632587625680257364P1258782500725 2112258792500825212425880250102521462588 1250112521510258822501225216162588325013 2521720258842501425218252588525015252193 2258862501625220402588725017252215025888 250182522263258892501925223121234protect ioncircuit-breakers up to 63 AC60H

8 Circuit -breakers10kA, B, C and D curveAS/NZS 4898 Approval No: N136341234567812345625845258712585725883 Width in modof 9mm - 2 Width in modof 9mm - 4 Width in modof 9mm - 6 Width in modof 9mm - 8 Page 6 Schneider Electric Help Centre: 1300 369 233protectioncircuit breakers up to 125AC120N Circuit -breakers10kA, B, C curves - AS/NZS 489810kA, D curve AS 3947-2functionThe Circuit -breakers combine the followingfunctions:- Protection of circuits against short circuitcurrents,- Protection of circuits against overloadcurrents,- control,Technical data common to C120N circuitbreakerscpower circuitvcurrent rating: 63 to 125 Avvoltage rating 415 V ACv insulation voltage Ui: 500 Vv impulse withstand voltage Uimp: 6 kVvbreaking capacity:- according to AS/NZS 4898 Icv ultimatebreaking capacity (O-CO cycle) typevoltagebreaking cap.(V)Icu (A)1, 2, 3, 4P240/41510000v according to AS3947-2 Icu ultimatebreaking capacity (O-CO cycle) typevoltagebreaking cap.

9 (V)Icu (kA)1P2401041532, 3, durability:- 20000 cycles (O-C)velectrical durability:- 63 A: 10000 cycles (O-C)- A: 5000 cycles (O-C)vI2t classification: 3visolation with positive contact indication:opening is indicated by a green strip on thedevice operating handle. This indicatorshows opening of all the polesvfoolproof terminal design- moving barrier prevents incorrect cableinsertion- cable strand centering guides ensurecorrect cable positions and strand groupingvbistable din clip: simplifies disassemblyv63 to 125A:- up to 35mm2 flexible withcable end- up to 50mm2 strandeddescription- isolation,- Protection of persons against curveutilisationwhen there are small inrush currents(generators, long cables).technical datacpower circuitv tripping curve:the magnetic trip units operate between3 and 5 curveutilisationcables feeding conventional datacpower circuitv tripping curve:the magnetic trip units operate between 5and 10 curve - For industrial use onlyutilisationloads with a high inrush current(motors, transformers).

10 Technical datacpower circuitvtripping curve:the magnetic trip units operate between10 and 14 No:Q00542 Approval No:Q00542 Page 7protectioncircuit-breakers up to 125 AC120N Circuit -breakers10kA, B, C curves - AS/NZS 489810kA, D curve AS 3947-21834018344123142catalogue numbers183491835553164275318642typeratin gBCD(A)CurveCurveCurveB curve C120N1P631834018356183788018341183571837 91001834218358183801251834318359183812P6 3183441836018382801834518361183831001834 618362183841251834718363183853P631834818 3641838680183491836518387100183501836718 3881251835118369183894P63183521837118390 8018353183721839110018354183741839212518 3551837718393 Width in modof 9mm - 3 Width in modof 9mm - 6 Width in modof 9mm - 9 Width in modof 9mm - 12 Page 8 Schneider Electric Help Centre: 1300 369 233protectioncircuit breakers up to 125AC120H Circuit -breakers15kA, B, C curves - AS/NZS 489815kA, D curve AS 3947-2functionThe Circuit -breakers combine the followingfunctions:- Protection of circuits against short circuitcurrents,- Protection of circuits against overloadcurrents,- control,Technical data common to C120N circuitbreakerscpower circuitvcurrent rating: 10 to 125 Avvoltage rating 415 V ACv insulation voltage Ui: 500 Vv impulse withstand voltage Uimp: 6 kVvbreaking capacity:- according to AS/NZS 4898 Icu ultimatebreaking capacity (O-CO cycle) typevoltagebreaking cap.