METROLL CYCLONIC DESIGN FOR ROOFING & WALLINGA Met-TECH GUIDECORODEK , TRIMCLAD & METROSPAN PROFILESOCTOBER 20192 What is Met-TECH ? Met-TECH is METROLL s Technical Resource Centre. It is the one stop shop for all of METROLL s product and technical information. Perfect for builders, contractors and specifiers to source all the information they may require. You can find other Met-TECH items on our website DESIGN FOR ROOFING & WALLINGThe METROLL CYCLONIC DESIGN Manual for ROOFING and WALLING provides all relevant information for builders, contractors and specifiers who wish to specify or use METROLL Corodek , Trimclad and Metrospan in CYCLONIC Products & Profiles CYCLONIC Testing

James Cook University. 1. The table values are only valid for use when the supporting steel members are high enough tensile strength, G450 with a thickness greater than 0.75mm or F17 Hardwood. 2. Roof sheeting shall be crest fixed to supports with Class 4 self drilling screws (refer fixing table), in accordance with manufacturers recommendations.

Tags:

  Design, James, Fixings, Roofing, Walling, Cyclonic, Metroll, Metroll cyclonic design for roofing amp walling

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of METROLL CYCLONIC DESIGN FOR ROOFING & WALLING

1 METROLL CYCLONIC DESIGN FOR ROOFING & WALLINGA Met-TECH GUIDECORODEK , TRIMCLAD & METROSPAN PROFILESOCTOBER 20192 What is Met-TECH ? Met-TECH is METROLL s Technical Resource Centre. It is the one stop shop for all of METROLL s product and technical information. Perfect for builders, contractors and specifiers to source all the information they may require. You can find other Met-TECH items on our website DESIGN FOR ROOFING & WALLINGThe METROLL CYCLONIC DESIGN Manual for ROOFING and WALLING provides all relevant information for builders, contractors and specifiers who wish to specify or use METROLL Corodek.

2 Trimclad and Metrospan in CYCLONIC Products & Profiles CYCLONIC Testing Northern Territory - Deemed to Comply Referenced Australian Standards Technical Notes to Limit State Capacity Tables Limit State Capacity Tables Fastener Selection & Information CYCLONIC Span Tables - ROOFING CYCLONIC Span Tables - WALLING CYCLONIC Span Tables - Residential ROOFING DESIGN Notes to Limit State Capacity Tables for D Class Wind Regions Region D ROOFING & WALLING Installation & General Information Disclaimer Information 3 3 3 3 3 4 5 910 1112131417 Back Cover3 MATERIALS METROLL ROOFING and wall cladding products are manufactured from high tensile G550 or G300 zinc-aluminium coated or colour coated steel conforming to AS 1397.

3 METROLL offers a wide range of colours and finishes including galvanised, the full range of COLORBOND and ZINCALUME steel & PROFILES The following products are covered in this manual: METROLL CORODEK METROLL TRIMCLAD METROLL METROSPAN These products are suitable for use in residential, commercial and industrial TESTING The Building Code of Australia requires all roof cladding used in CYCLONIC areas to withstand a Low High Low (LHL) CYCLONIC testing has undergone extensive testing to confirm it meets or exceeds all relevant requirements of the BCA and associated Australian Standards.

4 METROLL s products were tested at the Cyclone Testing Station - james Cook University. wind pressures and capacities stated in this manual are based on the testing completed and comply with Simplified DESIGN tables provided comply with AS4055. Ultimate limit state capacity tables comply with TERRITORY - Deemed to Comply The data tables in this brochure may be used for designers, builders and contractors operating in the Northern Territory. METROLL products have been approved under the deemed to Comply regime. More information can be accessed on the NT BAC AUSTRALIAN STANDARDSAS/NZS :2011AS/NZS :2011AS/NZS 1397:2013AS/NZS :1992AS/NZS :1994AS :1986AS/NZS 2334:1980AS/NZS 2728:2007AS :2003AS :2002AS :1992AS :1992AS 4055:2012 HB 39.

5 1997 Structural DESIGN Actions - Permanent, imposed & other DESIGN Actions - Wind Sheet & Strip - Hot dipped zinc-coated or aluminium/zinc & Installation of Sheet Roof & Wall Cladding - MetalSpecification for Rainwater Goods, Accessories & Fasteners - Metal shape or sheet rainwater goods & metal accessories & Rainwater Goods Selection & Nails - Metric Sheet Metal Products for Interior/Exterior Building Applications - Performance & Drainage - Stormwater Screws for the Building & Construction Industries - General requirements and mechanical of Testing Sheet Roof & Wall Cladding - Resistance to concentrated to Wind Pressures for Non- CYCLONIC Loads for Code for Metal Roof & Wall CRITERIAThe following criteria from AS/NZS 1170 have been used to generate the tables in

6 This brochure:1. Importance Level 2. Annual probability of exceedance 1 V500 = 66m/s, Fc + , VR = 69 Ms = Mt = Md = Cpe = as per AS/NZS Height multiplier as determined by Structural For local pressure factors and building aspect ratios refer to AS 1170, Table NOTES TO LIMIT STATE CAPACITY TABLESLIMITATIONS Information provided is for roof application only. Values in shaded cells denotes spans that exceed foot traffic limitations. Internal spans should have both end spans 20% shorter than tabulated values. The maximum permissible free edge overhang is 150mm from the screw line.

7 The maximum permissible stiffened edge overhang is 300mm from the screw line. Sheeting span can be limited by maximum batten spacing when using CYCLONIC steel battens. It is essential that the relevant deemed to comply information (for NT) for the batten product is used in conjunction with these TO TABLEST hese tables have been prepared by LCJ Engineers Pty Ltd. Information is based on Low High Low testing completed by the Cyclone Testing Station - School of Engineering, james Cook The table values are only valid for use when the supporting steel members are high enough tensile strength, G450 with a thickness greater than or F17 Roof sheeting shall be crest fixed to supports with Class 4 self drilling screws (refer fixing table), in accordance with manufacturers recommendations.

8 Length to suit insulation, sarking and 30mm embedment into Description of span types in the tables refer to the support configurations below:LLLLDOUBLE BMTC orodek 900mm1300mm1600mmTrimclad 1350mm1850mm-Metrospan 1800mm2250mm-FOOT TRAFFICR ecommended maximum spans for foot traffic on roofs are:C Class Wind RegionsEQUAL SPANINTERNAL SPAN5 Support StructureBMT mmCyclone Washers Fitted?Span TypeMAX. DESIGN PRESSURE (kPa) FOR SPAN (mm)450600750900120015001800 Metal , or Timber F17 sInternal sInternal sInternal sInternal value denotes spans outside of recommended foot trafficCORODEK CYCLONIC LIMIT STATE CAPACITY TABLEULTIMATE LIMIT STATE DESIGN PRESSURE (kPa) Table and values must be used in conjunction with the DESIGN Notes to Limit State Capacity Tables6 Support StructureBMT mmCyclone Washers Fitted?

9 Span TypeMAX. DESIGN PRESSURE (kPa) FOR SPAN (mm)4506009001200150018002100 Metal or Timber F17 sInternal sInternal sInternal value denotes spans outside of recommended foot trafficTRIMCLAD CYCLONIC LIMIT STATE CAPACITY TABLEULTIMATE LIMIT STATE DESIGN PRESSURE (kPa) Table and values must be used in conjunction with the DESIGN Notes to Limit State Capacity Tables7 Support StructureBMT mmCyclone Washers Fitted?Span TypeMAX. DESIGN PRESSURE (kPa) FOR SPAN (mm)450600750900120015001800 Metal or Timber F17 sInternal sInternal sInternal LIMIT STATE DESIGN PRESSURE (kPa) METROSPAN CYCLONIC LIMIT STATE CAPACITY TABLET able and values must be used in conjunction with the DESIGN Notes to Limit State Capacity Tables8 CORODEK BMT mmCyclone Washers Fitted?

10 Span TypeMAX. DESIGN PRESSURE (kPa) FOR SPAN (mm) sInternal sInternal value denotes spans outside of recommended foot trafficSERVICEABILITY LIMIT STATE DESIGN PRESSURE (kPa) TABLES TRIMCLAD BMT mmCyclone Washers Fitted?Span TypeMAX. DESIGN PRESSURE (kPa) FOR SPAN (mm) sInternal value denotes spans outside of recommended foot trafficMETROSPAN BMT mmCyclone Washers Fitted?Span TypeMAX. DESIGN PRESSURE (kPa) FOR SPAN (mm) sInternal and values must be used in conjunction with the DESIGN Notes to Limit State Capacity Tables9 FASTENER SELECTION & INFORMATION SUPPORTING MEMBERCORODEK TRIMCLAD METROSPAN Timber F17 Hardwood Supports14-10 x 50mm Type 17 14-10 x 65mm Type 17 14-10 x 65mm Type 17 Steel Supports - BMTM6-11 x 50mm Roof Zips or equivalentM6-11 x 50mm Roof Zips or equivalentM6-11 x 50mm Roof Zips or equivalentSteel Supports - BMT14-10 x 53mm Hex Head14-10 x 53mm Hex Head14-10 x 53mm Hex HeadSide Lap (where required)