Micropilot FMR62 Technical Information

Level measurement in liquidsApplication Continuous, non-contact level measurement of liquids,pastes and sludges Integrated PEEK antenna or PTFE-plated, flush-mounted antenna Maximum measuring range: 80 m (262 ft) Temperature: 40 to +200 C ( 40 to +392 F) Pressure: 1 to +25 bar ( to + psi) Accuracy: 1 mm ( in) International explosion protection certificates; WHG Linearity protocol (3-point, 5-point)Your benefits Reliable measurement thanks to improved focusing and small beam angle,particularly in vessels with many internal fittings Compact design enables installation in the case of small vessels and small processconnections Safety by design - ensures highest safety Easy, guided commissioning with intuitive user interface inlocal language Reliable measurement even in variable product and process conditions Maximum reliability thanks to multi-echo tracking HistoROM configuration memory makes for easier commissioning,maintenance and diagnostics SIL2 as per IEC 61508, SIL3 for homogeneous or diverse redundancy.

Micropilot FMR62 4 Endress+Hauser Important document information Safety symbols Symbol Meaning DANGER DANGER! This symbol alerts you to a dangerous situation.

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of Micropilot FMR62 Technical Information

1 Level measurement in liquidsApplication Continuous, non-contact level measurement of liquids,pastes and sludges Integrated PEEK antenna or PTFE-plated, flush-mounted antenna Maximum measuring range: 80 m (262 ft) Temperature: 40 to +200 C ( 40 to +392 F) Pressure: 1 to +25 bar ( to + psi) Accuracy: 1 mm ( in) International explosion protection certificates; WHG Linearity protocol (3-point, 5-point)Your benefits Reliable measurement thanks to improved focusing and small beam angle,particularly in vessels with many internal fittings Compact design enables installation in the case of small vessels and small processconnections Safety by design - ensures highest safety Easy, guided commissioning with intuitive user interface inlocal language Reliable measurement even in variable product and process conditions Maximum reliability thanks to multi-echo tracking HistoROM configuration memory makes for easier commissioning,maintenance and diagnostics SIL2 as per IEC 61508, SIL3 for homogeneous or diverse redundancy.

2 3rd partyapproved Easy proof testing for SIL and WHG Seamless integration in process control and asset management systems RFID TAG - easy identification of measuring points for improved data access Heartbeat TechnologyProductsSolutionsServicesTechn ical InformationMicropilot FMR62 Free space radarTI01303F/00/ FMR622 Endress+HauserTable of contentsImportant document for certain types of in at the and and system ..9 Measured on plug supply entries ..21 Cable operating value of ambient of gas : integrated : flush mount with heat temperature temperature according to IEC61010-1 of compatibility (EMC).. temperature, process : GT18 housing (stainless steel, corrosion-resistant)..45 Materials: GT19 housing (plastic)..46 Materials: GT20 housing (die-cast aluminum, powder-coated, seawater-resistant)..47 Materials: antenna and process : Weather protection with remote display and operating integration via and seal according to ANSI/ISA MR 0175 / ISO MR equipment with allowable pressure 200 bar (2 900 psi).

3 56 Marine standard EN 302729-1 standard EN 302372-1 / Industry radio , product standards and linearity linearity FMR62 Endress+ Instructions (XA)..73 Micropilot FMR624 Endress+HauserImportant document informationSafety symbolsSymbolMeaningDANGERDANGER!This symbol alerts you to a dangerous situation. Failure to avoid this situation will result inserious or fatal !This symbol alerts you to a dangerous situation. Failure to avoid this situation can result inserious or fatal !This symbol alerts you to a dangerous situation. Failure to avoid this situation can result inminor or medium !This symbol contains Information on procedures and other facts which do not result inpersonal symbolsSymbolMeaningSymbolMeaningDirect currentAlternating currentDirect current and alternating currentGround connectionA grounded terminal which, as far asthe operator is concerned, isgrounded via a grounding ground connectionA terminal which must be connectedto ground prior to establishing anyother connectionA connection that has to be connectedto the plant grounding system: Thismay be a potential equalization lineor a star grounding system dependingon national or company codes for certain types ofinformationSymbolMeaningPermittedProce dures, processes or actions that are , processes or actions that are , processes or actions that are additional to documentationAReference to pageReference to graphicVisual inspectionSymbols in graphicsSymbolMeaning1, 2, 3.

4 Item numbers1., 2., of stepsA, B, C, ..ViewsA-A, B-B, C-C, ..SectionsMicropilot FMR62 Endress+Hauser5 SymbolMeaning-Hazardous areaIndicates a hazardous area (non-hazardous area)Indicates the non-hazardous at the deviceSymbolMeaningSafety instructionsObserve the safety instructions contained in the associated Operating resistance of the connection cablesSpecifies the minimum value of the temperature resistance of the connection FMR626 Endress+HauserTerms and abbreviationsTerm/abbreviationExplanatio nBADocument type "Operating Instructions"KADocument type "Brief Operating Instructions"TIDocument type " Technical Information "SDDocument type "Special Documentation"XADocument type "Safety Instructions"PNNominal pressureMWPM aximum Working PressureThe MWP can also be found on the of FlightFieldCareScalable software tool for device configuration and integrated plant asset managementsolutionsDeviceCareUniversal configuration software for Endress+Hauser HART, PROFIBUS.

5 FOUNDATION Fieldbus and Ethernet field devicesDTMD evice Type ManagerDDDevice Description for HART communication protocolDCRelative dielectric constant rOperating toolThe term "operating tool" is used in place of the following operating software:FieldCare / DeviceCare, for operation via HART communication and PCBDB locking Distance; no signals are analyzed within the FMR62 Endress+Hauser7 Registered trademarksHART Registered trademark of the HART Communication Foundation, Austin, USAKALREZ , VITON Registered trademark of DuPont Performance Elastomers , Wilmington, USATEFLON Registered trademark of DuPont de Nemours & Co., Wilmington, USATRI CLAMP Registered trademark of Ladish Co. Inc., Kenosha, USAM icropilot FMR628 Endress+HauserFunction and system designMeasuring principleThe Micropilot is a "downward-looking" measuring system, operating based on the frequencymodulated continuous wave method (FMCW). The antenna emits an electromagnetic wave at acontinuously varying frequency.

6 This wave is reflected by the product and received again by A0032017 1 FMCW principle: transmission and reflection of the continuous waveRReference point of measurementDDistance between reference point and product surfaceThe frequency of this wave is modulated in the form of a sawtooth signal between two limitfrequencies f1 and f2:ft12f2f1!t!f A0023771 2 FMCW principle: result of frequency modulation1 Transmitted signal2 Received signalThis results in the following difference frequency at any time between the transmitted signal and thereceived signal: f = k twhere t is the run time and k is the specified increase in frequency modulation. t is given by the distance D between the reference point R and the product surface:D = (c t) / 2where c is the speed of propagation of the summary, D can be calculated from the measured difference frequency f. D is then used todetermine the content of the tank or FMR62 Endress+Hauser9 InputMeasured variableThe measured variable is the distance between the reference point and the product surface.

7 The levelis calculated based on "E", the empty distance entered. Optionally, the level can be converted to othervariables (volume, mass) by linearization (32 value pairs).Measuring rangeMaximum measuring rangeDeviceAntenna 1)Maximum measuring rangeFMR62GE:integrated, PEEK, 20 mm / 3/4"10 m ( ft)GF:integrated PEEK, 40 mm / 1-1/2"22 m (72 ft)GM:PTFE cladded flush mount 50 mm / 2"50 m (164 ft)GN:PTFE cladded flush mount 80 mm / 3"80 m (262 ft)1) Feature 070 in the product structureUsable measuring rangeThe usable measuring range depends on the antenna size, the medium's reflective properties, theinstallation position and any possible interference in preparationFor dielectric constants (DC values) of many media commonly used in various industries referto: the Endress+Hauser DC manual (CP01076F) the Endress+Hauser "DC Values App" (available for Android and iOS)Operating frequencyApprox. 80 GHzSeveral FMR6x devices can be installed in one tank thanks to the short measuring duration and thehigh beam power Peak power: mW Average output power: 63 WMicropilot FMR6210 Endress+HauserOutputOutput signalHARTS ignal codingFSK mA over current signalData transmission rate1 200 Bit/sGalvanic isolationYesSwitch outputFor HART devices, the switch output is available as an option.

8 See product structure, feature 20:"Power Supply, Output", option B: "2-wire; 4-20mA HART, switch output"Devices with PROFIBUS PA and FOUNDATION Fieldbus always have a switch outputFunctionOpen collector switching outputSwitching behaviorBinary (conductive or non-conductive), switches when the programmable switchpoint is reachedFailure modenon-conductiveElectrical connectionvaluesU = 16 to 35 VDC, I = 0 to 40 mAInternal resistanceRI < 880 The voltage drop at this internal resistance has to be taken into account onplanning the configuration. For example, the resulting voltage at a connectedrelay must be sufficient to switch the voltagefloating, Insulation voltage 1 350 VDC to power supply aund 500 VAC to groundSwitch pointfreely programmable, separately for switch-on and switch-off pointSwitching delayfreely programmable from 0 to 100 s, separately for switch-on and switch-offpointNumber of switching cyclescorresponds to the measuring cycleSignal sourcedevice variables Level linearized Distance Terminal voltage Electronic temperature Relative echo amplitude Diagnostic values, Advanced diagnosticsNumber of switching cyclesunlimitedSignal on alarmDepending on the interface, failure Information is displayed as follows: Current output (for HART devices) Failsafe mode selectable (in accordance with NAMUR Recommendation NE 43):Minimum alarm: mAMaximum alarm (= factory setting): 22 mA Failsafe mode with user-selectable value.

9 To mA Local display Status signal (in accordance with NAMUR Recommendation NE 107) Plain text display Operating tool via digital communication (HART, PROFIBUS PA, FOUNDATION Fieldbus) orservice interface (CDI) Status signal (in accordance with NAMUR Recommendation NE 107) Plain text displayLinearizationThe linearization function of the device allows the conversion of the measured value into any unit oflength or volume. Linearization tables for calculating the volume in cylindrical tanks are pre-programmed. Other linearization tables of up to 32 value pairs can be entered manually or FMR62 Endress+Hauser11 Galvanic isolationAll circuits for the outputs are galvanically isolated from each dataHARTM anufacturer ID17 (0x11)Device type ID0x112 BHART description files (DTM, DD) Information and files under: loadmin. 250 HART device variablesThe measured values can be freely assigned to the device values for PV (primary variable) Level linearized Distance Electronic temperature Relative echo amplitude Area of incoupling Analog output adv.

10 Diagnostics 1 Analog output adv. diagnostics 2 Measured values for SV, TV, FV (second, third and fourth variable) Level linearized Distance Electronic temperature Terminal voltage Relative echo amplitude Absolute echo amplitude Area of incoupling Analog output adv. diagnostics 1 Analog output adv. diagnostics 2 Supported functions Burst mode Additional transmitter statusWireless HART dataMinimum start-up voltage16 VStart-up mAStart-up time40 sMinimum operating VMultidrop mASet-up time1 sMicropilot FMR6212 Endress+HauserPower supplyTerminal assignment2-wire: 4-20mA HART891+ mmSpare part71108xxx2- wire level4-20 mA4-20 mAHART[21]open-1+24-20mA1-channel overvoltage protection-[16]A7B! mA54123+ + #+ mA54123+ 6# A0011294 3 Terminal assignment 2-wire; 4-20mA HARTAW ithout integrated overvoltage protectionBWith integrated overvoltage protection1 Active barrier with power supply ( RN221N): Observe terminal voltage2 HART communication resistor ( 250 ): Observe maximum load3 Connection for Commubox FXA195 or FieldXpert SFX350/SFX370 (via VIATOR Bluetooth modem)4 Analog display device: Observe maximum load5 Cable screen; observe cable specification64-20mA HART (passive): Terminals 1 and 27 Overvoltage protection module8 Terminal for potential equalization line9 Cable entryMicropilot FMR62 Endress+Hauser132-wire: 4-20mA HART, switch output1+ mAHART10 mmSpare part71108xxx2- wire4-20 mAPFSHART[02/03]open-A1+2-3+4-13++244-20 mA/FIELDBUS4-20mA/2-channel overvoltage protection--[17]B1098711++ mA 250 "3+3+4-4-++ $$% mA 250 " A0013759 4 Terminal assignment 2-wire.