VPSMore Detailed Electrical Inspection ReportCover PageFlorida St., YourTown FL, 34292 Inspection prepared for: Electrical Inspection Actual Inspection Date: 3/3/2011 Time: 1 PM Age: 27 Years Size: 4,500 SF Weather: ClearWeather: 10-15 MPH Winds, 79 F, 80 RHInspector: A E HaasLic. # NACHI10120602, Florida Lic. HI1872836 Sunset Lake Blvd Ste 103, Venice, FL 34292 Phone: 941-492-4340 Fax: 941-492-4772 Email: VPSF lorida St., YourTown, FLPage 1 of 31 Report SummaryReport Summary The summary below consists of potentially significant findings. These findings can be a safety hazard, a deficiencyrequiring a major expenses to correct or items I would like to draw extra attention to. The summary is not a completelisting of all the findings in the Report , and reflects the opinion of the inspector. Please review all of the pages of the reportas the summary alone does not explain all the issues. All repairs must be done by a licensed and bonded trade orprofession.

VPS Florida St., YourTown, FL Page 2 of 31 Inspection Details Grounds We appreciate the opportunity to conduct this inspection for you! Please carefully read your entire Inspection Report.

Tags:

  More, Report, Electrical, Cover, Inspection, Detailed, Inspection report, More detailed electrical inspection report cover

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of More Detailed Electrical Inspection Report Cover Page

1 VPSMore Detailed Electrical Inspection ReportCover PageFlorida St., YourTown FL, 34292 Inspection prepared for: Electrical Inspection Actual Inspection Date: 3/3/2011 Time: 1 PM Age: 27 Years Size: 4,500 SF Weather: ClearWeather: 10-15 MPH Winds, 79 F, 80 RHInspector: A E HaasLic. # NACHI10120602, Florida Lic. HI1872836 Sunset Lake Blvd Ste 103, Venice, FL 34292 Phone: 941-492-4340 Fax: 941-492-4772 Email: VPSF lorida St., YourTown, FLPage 1 of 31 Report SummaryReport Summary The summary below consists of potentially significant findings. These findings can be a safety hazard, a deficiencyrequiring a major expenses to correct or items I would like to draw extra attention to. The summary is not a completelisting of all the findings in the Report , and reflects the opinion of the inspector. Please review all of the pages of the reportas the summary alone does not explain all the issues. All repairs must be done by a licensed and bonded trade orprofession.

2 I recommend obtaining a copy of all receipts, warranties and permits for the work 3 Item: 2 GFCI Some outside receptacles missing weatherproof 3 Item: 1 FoundationElectrical Multiple outside outlets on house foundation with missing /brokenweatherproof covers. Multiple outside outlets with open ground connections, get electrician toevaluate, 7 Item: 8 Need Repairs See diagram / Electrical plan. Consider that the Rodents in the attic space may have chewed on is a common problem. This could account for voltage drops. I did notsee and of this type of damage on Inspection but obviously only someparts of wires are pest control inspect regularly and treat for rodents and insects asneeded. (no insect damage seen in visible areas that were inspected).Plumbing/ElectricalPage 7 Item: 1 Plumbing Materials Drier ground connection irregular to pipe in Laundry room, loose. Havechecked by 7 Item: 3 AFCI GFCI Areas Note: kitchen does not have any GFCI AreasPage 12 Item: 4 Detectors andAlarm Missing detectors in areas - have electrician or detector contractor addas MasterPage 13 Item: 3 Electrical Den off of master bedroom has multiple open ground receptacles.

3 Havechecked ASAP by electrician. Computers not MasterPage 13 Item: 3 Exhaust Fan Terminated in the attic. This can cause a buildup of moisture andeventually mold in the attic. Recommend directing the vent towards theexterior to allow for proper #2 Page 15 Item: 4 Exhaust Fan Terminated in the attic. This can cause a buildup of moisture andeventually mold in the attic. Recommend directing the vent towards theexterior to allow for proper #3 Page 15 Item: 4 Exhaust Fan Terminated in 17 Item: 4 Garage Door'sReverse Status No eye beam system present. This appears to be an older unit whenthese safety features were not included with openers. We recommendupgrading to a newer model with all safety features included. VPSF lorida St., YourTown, FLPage 2 of 31 Inspection Details Grounds We appreciate the opportunity to conduct this Inspection for you! Please carefully read your entire Inspection Report . Call us after you have reviewed your Report , so we can go over any questions you may have.

4 Remember, when theinspection is completed and the Report is delivered, we are still available to you for any questions you may being inspected do not "Pass" or "Fail. - The following Report is based on an Inspection of the visible portionof the structure; Inspection may be limited by vegetation and possessions. Depending upon the age of the property,some items like GFI outlets may not be installed; this Report will focus on safety and function, not current code. Thisreport identifies specific non-code, non-cosmetic concerns that the inspector feels may need further investigation only thing that we guarantee is that we cannot find all the problems and defects. Some will be missed. An inspectionis not a perfect science. We do the best we can to find things that are an issue on the day we do the Inspection . Wemake no other claims and we make no real your safety and liability purposes, we recommend that licensed contractors evaluate and repair any critical concernsand defects.

5 Note that this Report is a snapshot in time. If purchasing, we recommend that you or yourrepresentative carry out a final walk-through Inspection immediately before closing to check the condition of theproperty, using this Report as a guide..1. AttendanceIn Attendance: Client was Home TypeHome Type: Single Family OccupancyOccupancy: Moderate to heavy personal and household items was observed. Occupied - Furnished: Heavy volume ofpersonal and household items Grounds ElectricalObservations: Accent lighting needs review, multiple issues. Badly rusted Electrical boxes. Check all. Some light fixtures broken. Check all bulbs and fixtures after transformer boxes boxes lights free of debris. VPSF lorida St., YourTown, FLPage 3 of 31 Foundation Roof Fixtures in need of weather proof Cover , others GFCIO bservations: GFCI at end of Bar-BQ grill counter slugish to respond. Check or replace. Some outside receptacles missing weatherproof Foundation ElectricalObservations: Some GFCI did not respond correctly to test, suggest replacing for safety.

6 See Electrical fault map. GFCI reset in main breaker panel in foyer area, right side panel box. Multiple outside outlets on house foundation with missing /broken weatherproof covers. Multiple outside outlets with open ground connections, get electrician to evaluate, door lights need securing, lights on walls. VPSF lorida St., YourTown, FLPage 4 of 31 Attic 1. CheckObservations: Visible lightening protection cables / devices appeared intact. Cannot see actual grounding below grade. Some soffit lights seem as they are combined with motion sensors but these are probably broken. Lights not seen inOn grounding lines for lightening rods motion sensor broken outside kitchen ElectricalObservations: Exposed wires seen. Most not accessible due to insulation coverage. A lot of loose old wires and cables lying around, recommend removal of unused and securing active , needs clean up and is a hazard, consider adding a walkway path.

7 VPSF lorida St., YourTown, FLPage 5 of 31 Electrical Needs to be grouped, bathroom vent fans duct into attic space - bathroom vent fans duct into attic space - are not electricians. Feel free to hire an electrician prior to closing. If we feel that it is safe enough to open the Electrical panel, we will check theinterior components of service panels and sub panels, the conductors, and the over-current protection devices. Inside the house, we will check arepresentative number of installed lighting fixtures, switches, and receptacles. This is not an exhaustive Inspection of every component and installationdetail. There will be receptacles and switches and lights that we will not have time to inspect. Ask property owner about all of the wall , it is essential that any recommendations that we may make for correction should be completed before the close of escrow, because anelectrician could reveal other problems or recommend that only actual GFCI outlets are tested and tripped.

8 Some baths may have non-GFCI outlets which are protected by a GFCI outlet in a remotearea (garage, another bath, etc.). Confirm with owner that apparent non-GFCI outlets within 6 of wet areas are thus protected. Also, note that mostelectricians agree that smoke detectors are good for about 5 years, and the breakers in your panel box have an expected life of about 20 years. Therefore, if this home was built before 1990, consider having the panel box and breakers evaluated by a licensed electrician, as an overheatedbreaker can result in a structural fire. If your home does not have a carbon monoxide detector (few do!), we recommend making that investment. Anyhome that has a Bulldog Pushmatic, Zinsco, Sylvania Zinsco or Federal Pacific Electric panel should have it evaluated by a licensed electrician, asthese older types of panels and breakers have been known to overheat and cause house Electrical PanelLocation: Main disconnect location: West side of the house.

9 Exterior of structureLocation: Sub Panel Location: In Entry area of house. VPSF lorida St., YourTown, FLPage 6 of 312. Main Amp BreakerObservations: 400 amp (200 x 2).Main incoming disconnects seen here on outside on west outside garden Breakers in off positionObservations: 04. Cable FeedsObservations: The service entrance is a lateral, underground BreakersMaterials: Copper non-metallic sheathed cable : All of the circuit breakers appeared serviceable. GFCI breakers noted to only bathroom areas and to exterior of house. Several loose wires noted in right Electrical panel box, a loose ground and a loose neutral wire. Have electricianreview and major system safety or function concerns noted at time of second Inspection date of 3/10 defects on right side panel Neutral wire. Disconnected ground wire. VPSF lorida St., YourTown, FLPage 7 of 31 Plumbing/ Electrical 6. FusesMaterials: 15 amp. 20 : The sub panel normal outlet breakers were a mixture of 15 and 20 amp units.

10 This this Needs AttentionObservations: Most receptacles accessed tested Need RepairsObservations: Some receptacles tested a voltage drop a little too high under load conditions. In my experience many houses thatare relatively new ones have an average of 3 - 8 or 9 percent voltage drop. I generally Report only those that are greater than 10% voltage drop, but recommend you get an electrician to testfurther. See diagram / Electrical plan. Consider that the Rodents in the attic space may have chewed on wires. This is a common problem. This couldaccount for voltage drops. I did not see and of this type of damage on Inspection but obviously only some parts of wiresare pest control inspect regularly and treat for rodents and insects as needed. (no insect damage seen in visibleareas that were inspected).1. Plumbing MaterialsObservations: Copper pipes noted - used as a ground in laundry room. Have electrician verify this is correct.