Multi-Position, Variable-Speed, ECM-Based Air ... - …

5/16* Complete warranty details available from your local dealer or at To receive the 10-Year Parts Limited Warranty, online registration must be completed within 60 days of installation. Online registration is not required in California or Features Internal factory-installed thermal expansion valves for cooling and heat pump applications Variable-speed ECM blower motor ComfortNet Communicating System compatible Auto configuration of the airflow and tonnage in communicating mode Provides constant CFM over a wide range of static pressure conditions independent of duct system CFM indicator Fault recall of six most recent faults Provides adjustable low CFM for efficient fan-only operation Improved humidity and comfort control Built-in compatibility with multi-stage heat pump and cooling applications

2 www.goodmanmfg.com SS-GAVPTC SS-GAVPTC www.goodmanmfg.com 3 Product Specifications AVPTC 24B14A* AVPTC 25B14A* …

Tags:

  Specification

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Advertisement

Transcription of Multi-Position, Variable-Speed, ECM-Based Air ... - …

1 5/16* Complete warranty details available from your local dealer or at To receive the 10-Year Parts Limited Warranty, online registration must be completed within 60 days of installation. Online registration is not required in California or Features Internal factory-installed thermal expansion valves for cooling and heat pump applications Variable-speed ECM blower motor ComfortNet Communicating System compatible Auto configuration of the airflow and tonnage in communicating mode Provides constant CFM over a wide range of static pressure conditions independent of duct system CFM indicator Fault recall of six most recent faults Provides adjustable low CFM for efficient fan-only operation Improved humidity and comfort control Built-in compatibility with multi-stage heat pump and cooling applications

2 All-aluminum evaporator coil 3 kW 25 kW electric heater kits AHRI certified; ETL listed Rigid SmartFrame cabinet Cabinet air leakage less than at inch H O when tested in accordance with ASHRAE standard 193 Cabinet air leakage less than at inch H O when tested in accordance with ASHRAE standard 193 Horizontal or vertical configuration capabilities 21" depth for easier attic access DecaBDE-free thermoplastic drain pan with secondary drain connections Screw-less sides and back helps to reduce condensation when installed in humid locations Foil-faced insulation covers the internal casing to reduce cabinet condensation Galvanized.

3 Leather grain-embossed finish Glue-less cabinet insulation retention Tool-less filter accessMulti-Position, Variable-Speed, ECM-Based Air Handler with Internal TXVC omfortNet Compatible 1 to 5 TonsAVPTCC ontentsAir Handler Nomenclature ..2 Heater Kit Nomenclature ..2 Product Specifications ..3 Dimensions ..4 Airflow Data ..5 Heat Kit Data ..10 Wiring Diagram ..13 Accessories ..15 ,7891011,12 BrandEngineering*ASingle- PieceMajor/Minor RevisionsAirhandler*Not used for inventory managementUnit ApplicationRefrigerant ChargeR Multi Position PSC Motor4 = R- 410AS Multi Position EEM MotorV Multi Position Variable- Speed ElectricalMotor- Commuminacating1 208/230V, 1 Phase.

4 60 HzCabinet FinishCabinet WidthU UnpaintedB = 17 "P PaintedC = 21" D = 24 "Expansion DeviceT Expansion DeviceNominal Capacity @ 13 SEERV Inverter Tuned Expansion Valve24 = 2 Tons31 = 2 Tons48 = 4 Tons25 = 2 Tons36 = 3 Tons49 =4 Tons29 = 2 Tons37 = 2 - 3 Tons59 = 4- 5 TonsCommunications30 = 2 Tons42 = 3 Tons60 = 5 TonsC = ComfortNetTM Compatible61 = 5 Tons33 = 2 Tons39 = 3 TonsHKSX03XA AA123456,7 Unit TypeRevisionsHKS Heat Kit for Engineering RevisionsAir HandlersPhaseCircuit BreakerE Three Phase 240 VX No circuit breakerF Three Phase 208/240 VC Circuit BreakerG Three Phase 460 VA Single Phase 208 VB Single Phase 240 VC Single Phase 208/240 V D Three Phase 208 VHeating Capacity @ 240 Volts03 kW15 kWCabinet Size (MAX)

5 05 kW wth 150F limitC C Cabinet06 kW with 170F limitD D Cabinet08 kW25 kWX All Cabinet Sizes10 SpecificationsAVPTC24B14A*AVPTC25B14A*AV PTC29B14A*AVPTC30C14A*AVPTC31C14A*AVPTC3 3C14*AVPTC36C14A*AVPTC37B14A*AVPTC37C14A *AVPTC37D14A*AVPTC39C14*Nominal RatingsCooling (BTU/h)24,00024,00030,00030,00030,00024, 00036,00036,00036,00036,00036,000 CFM (High range)1100/6001085/6501085/6101200/60013 15/8701090/6851600/7001085/6101315/87013 75/8651315/965 BlowerDiameter9 "9 "9 "10 "10 "10 "10 "9 "10 "10 "10 "Width6"6"6"8"8"8"10 "6"8"10 "8"Coil Drain Connection FPT " " " " " " " " " " "Service ValveLiquid " " " " " " " " " " "Suction " " " " " " " " " " "Electrical DataVoltage208/240208/240208/240208/2402 08/240208/240208/240208/240208/240208/24 0208/240 Min Circuit Overcurrent Device (amps)15/1515/1515/1515/1515/1515/1515/1 515/1515/1515/1515/15 Minimum VAC197197197197197197197197197197197 Maximum VAC253253253253253253253253253253253 Blower Ship Weight (lbs)

6 100116129118144118118129144155118 Note: Minimum Circuit Ampacity (MCA) and Maximum Overcurrent Protection (MOP) for blower without supplemental heat installed. Refer to unit nameplate and/or Heat Kit Data for specification with approved accessory heaters installedAVPTC42D14A*AVPTC48C14A*AVPTC48 D14A*AVPTC49C14*AVPTC49D14A*AVPTC59C14A* AVPTC59D14A*AVPTC60D14A*AVPTC61D14A*Nomi nal RatingsCooling (BTU/h)42,00042,00048,00048,00042,00048, 00048,00060,00060,000 CFM (High range)1700/8001660/7001800/13501420/1040 1530/11951595/8751990/14452000/16002025/ 1630 BlowerDiameter10 "10 "10 "10 "10 "10 "11 "11 "11 "Width10 "10 "10 "8"10 "8"10 "10 "10 "Coil Drain Connection FPT " " " " " " " " "Service ValveLiquid " " " " " " " " "Suction " " " " " " " " "Electrical DataVoltage208/240208/240208/240208/2402 08/240208/240208/240208/240208/240 Min Circuit Overcurrent Device (amps)15/1515/1515/1515/1515/1515/1515/1 515/1515/15 Minimum VAC197197197197197197197197197 Maximum VAC253253253253253253253253253 Blower 1111 Ship Weight (lbs)155125167125167144155167167 Note.

7 Minimum Circuit Ampacity (MCA) and Maximum Overcurrent Protection (MOP) for blower without supplemental heat installed. Refer to unit nameplate and/or Heat Kit Data for specification with approved accessory heaters AVPTC24/ 30/ 36/ 42/ 48/ "( cm).55"( cm) "( )DE21" " "( cm).55"( cm)AFINLET(FRONT VIEW)1"( cm).55"( cm) " ( cm)INLET(RIGHT SIDE VIEW) "( cm) "( cm) "( cm) "( cm) "( cm) "( cm) "( cm) "( cm) "( cm) "( cm) "( cm) "( cm) "( cm)PLASTICBREAKERCOVERLOGO LOCATIONSEE DRAIN PORT DETAILLIQUID LINESUCTION TUBEINLETTUBEDRAIN PORT DETAILM odel ABCDEFGHAVPTC24B144516 17 1815 14 8 11 AVPTC30C144919 21 2017 17 10 12 AVPTC36C144919 21 2017 17 10 12 AVPTC42D145823 24 28 25 21 12 12 AVPTC48C144919 21 2017 17 10 12 AVPTC48D145823 24 28 25 21 12 12 AVPTC60D145823 24 28 25 21 12 12 AVPTC25 / 29/ 31 /37/ 49/ 59 " ( cm) " ( cm)

8 " ( cm) " ( cm) " ( cm) " ( cm) ".52" ( cm) "( cm)21"A1" ( cm).54" ( cm) " ( cm)INLET(RIGHT SIDE VIEW).62" ( cm) " ( cm) " ( cm) " ( cm) " ( cm) " ( cm) " ( cm)FINLET(FRONT VIEW) " ( cm) " ( cm) " ( cm)SEE HORIZONTALDRAIN PORT DETAILSEE VERTICALDRAIN PORT DETAILSUCTION TUBELIQUID LINEINLETTUBEM odel ABCDEFGHAVPTC25B14*4516 17 15 1214 9 12 AVPTC29B14*53 16 17 23 20 14 9 7 AVPTC31C14*53 19 2121 18 17 10 6 AVPTC33C14*49 19 21 179 14 17 109 12 AVPTC37B14*53 16 17 23 20 14 9 7 AVPTC37C14*53 19 2121 18 17 10 6 AVPTC37D14*53 23 24 21 18 21 12 6 AVPTC39C14*49 19 21 179 14 17 109 12 AVPTC49C14*49 19 21 179 14 17 109 12 AVPTC49D14*5823 24 26 22 21 12 25 AVPTC59C14*53 19 2121 18 17 10 6 AVPTC59D14*53 23

9 24 21 18 21 12 6 AVPTC61D14*58 23 24 26 22 21 12 25 DataModelSpeed : When applying a humidistat (normally closed), refer to the installation and operating instructions. The humidistat can adjust the cooling airflow to 85%. Data (cont.)ModelSpeed Data (cont.)Note: When applying a humidistat (normally closed), refer to the installation and operating instructions. The humidistat can adjust the cooling airflow to 85%.ModelSpeed Heat Airflow & Dipswitch SettingsHTR kW91011 AVPTC24B14 AVPTC25B14 AVPTC29B14 AVPTC30C14 AVPTC31C14 AVPTC33C14 AVPTC36C14 AVPTC37B14 AVPTC37C14 AVPTC37D14 AVPTC39C143 ONONON730550550730---600NR550---------5 ONONOFF780650650780850700850650850124085 06 ONOFFON850700700850900750900700900124090 08 ONOFFOFF95080080095010008751000800100012 40100010 OFFONON102585087510251170950120087511701 240117015 OFFONOFFNR875875NR1345950144010501345152 0134519*OFFOFFONNR------NR1345---1500--- 1345---134520NR------NR------1500------1 520---21 or 25*OFFOFFOFFNR------NR------NR---------- --Note.

10 Airflow data shown applies to the electric heat only in either legacy mode or communicating mode operation--- indicates Not Rated* Within thermostat user menu, CTK0* communicating thermostat will display 20kW for OFF- OFF- ON dipswitch selection, 21kW for OFF-OFF-OFF dipswitch selection. For match up with a 2 ton outdoor unit: Heater kit application shall not exceed 10 kW. Airflow for 5 kW up to 10 kW heater kits shall be set to 850 cfm speed tap of ON-ON-ON. For match up with a 3 ton outdoor unit: Heater kit application shall not exceed 15 kW. Airflow for 5 kW up to 15 kW heater kits shall be set to 1300 cfm speed tap of ON-OFF-ON.