NEMA Contactor and Starter Specifications - Technical Data

Technical DataNEMA Contactor and Starter SpecificationsBulletins 500, 502, 503, 505, 506, 506X, 507, 507X, 509, 512, 513, 522E/F/G, 523E/F/GSummary of ChangesThis publication contains new and updated information as indicated in the following ResourcesThese documents contain additional information concerning related products from rockwell can view or download publications at To order paper copies of Technical documentation, contact your local Allen-Bradley distributor or rockwell automation sales Ratings2 Mechanical Ratings, Construction, Environmental3 Short Circuit Rating4AC Coil Data5 Auxiliary Contacts (NEMA A600 and P300) Bulletin 595, 5965 Load-life Curves6 Approximate Dimensions7 Type 1 General Purpose Lift-Off Enclosure7 Type 1 Hinged Enclosure with or without Control Transformer7 Type 1 General Purpose Painted Enclosure8 Type 3R/12 Rainproof, Dusttight, 4/4X Watertight, Non-metallic Enclosure with or without Control Transformer9 Type 3R/4/12 Rainproof, Dusttight Industrial Use Enclosures10 Unilock Enclosures Type 3R, 7 & 9, Class I Groups C & D, Class II, Groups E, F & G Divisions 1 & 211 Bolted Enclosures Type 3R, 7 & 9, Class I, Groups C & D, Class II, Groups E, F & G Divisions 1 & picPageRemoved NEMA Pump Panels and Open Type applicableResourceDescriptionPump Panel Specifications , public

2 Rockwell Automation Publication 500-TD014C-EN-P - March 2017 NEMA Contactor and Starter Specifications Specifications Electrical Ratings NEMA Size Load Voltage Continuous Current Rating Service Limit Current Rating (1) (1) Service-Limit Current Ratings — The service-limit current ratings that are shown represent the maximum rms current, in amperes, which the …

Tags:

  Specification, Automation, Starter, Rockwell automation, Rockwell, Starter specifications, Starter specifications specifications

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of NEMA Contactor and Starter Specifications - Technical Data

1 Technical DataNEMA Contactor and Starter SpecificationsBulletins 500, 502, 503, 505, 506, 506X, 507, 507X, 509, 512, 513, 522E/F/G, 523E/F/GSummary of ChangesThis publication contains new and updated information as indicated in the following ResourcesThese documents contain additional information concerning related products from rockwell can view or download publications at To order paper copies of Technical documentation, contact your local Allen-Bradley distributor or rockwell automation sales Ratings2 Mechanical Ratings, Construction, Environmental3 Short Circuit Rating4AC Coil Data5 Auxiliary Contacts (NEMA A600 and P300) Bulletin 595, 5965 Load-life Curves6 Approximate Dimensions7 Type 1 General Purpose Lift-Off Enclosure7 Type 1 Hinged Enclosure with or without Control Transformer7 Type 1 General Purpose Painted Enclosure8 Type 3R/12 Rainproof, Dusttight, 4/4X Watertight, Non-metallic Enclosure with or without Control Transformer9 Type 3R/4/12 Rainproof, Dusttight Industrial Use Enclosures10 Unilock Enclosures Type 3R, 7 & 9, Class I Groups C & D, Class II, Groups E, F & G Divisions 1 & 211 Bolted Enclosures Type 3R, 7 & 9, Class I, Groups C & D, Class II, Groups E, F & G Divisions 1 & picPageRemoved NEMA Pump Panels and Open Type applicableResourceDescriptionPump Panel Specifications , publication 1232-TD001 Provides Specifications for Bulletin 1232 and 1233 pump automation Wiring and Grounding Guidelines.

2 Publication general guidelines for installing a rockwell automation industrial Certifications website, declarations of conformity, certificates, and other certification automation Publication 500-TD014C-EN-P - March 2017 NEMA Contactor and Starter SpecificationsSpecificationsElectrical RatingsNEMASizeLoadVoltageContinuousCurr entRatingServiceLimitCurrentRating (1)(1)Service-Limit Current Ratings The service-limit current ratings that are shown represent the maximum rms current, in amperes, which the controller shall be permitted to carry for protracted periods in normal service. At service-limit current ratings, temperature rises shall be permitted to exceed those obtained by testing the controller at its continuous current rating. The current rating of overload relays or the trip current of other motor protective devices that are used shall not exceed the service-limit current rating of the Hp Rating(Non-plugging andnon-jogging duty)Maximum Hp Rating(Plugging andjogging duty) (2)(2)Plugging or Jogging Service The listed horsepower ratings are recommended for those applications requiring repeated interruption of stalled motor current that is encountered in rapid motor reversal in excess of five openings or closings per minute and shall not be more than ten in a ten minute PrimarySwitching kVa Rating(Inrush Current 20 timesContinuous Current)Transformer PrimarySwitching kVa Rating(Inrush Current = 20 to 40 timesContinuous Current)CapacitorSwitchingkVAR (3)(3)If maximum available current (at capacitor terminals)

3 Is greater than 3000 A, contact your local rockwell automation sales office, Allen-Bradley distributor, or NEMA ICS-2 InrushCurrent [A] PeakIncluding Offset[V][A][A]1 3 1 3 1 3 1 3 3 3 001152002303804605759111/3 1 1-1/21-1/21-1/2221/4 1/2 1111-1/21-1/2 87011520023038046057518211 2 335551/2 1 1-1/21-1/21-1 140111520023038046057527322 3 7-1/27-1/21010101 2 6 1-1/23 211520023038046057545523 7-1/2 10152525252 5 7-1 14181 12 25314833115200230380460575901047-1/2 15 25305050507-1/2 15 1620 1214 28352 1418 27 53679474115200230380460575135156 405075100100 14 2734 2023 1417 1012 2329 40 8010015815115200230380460575270311 75100150200200 607512515015014 27 5468 4147 14 2734 2024 4759 80 16020031636115200230380460575540621 150200300400400 12515025030030027 54 108135 8194 18823414 27 5468 4147 94117 160 32040063267230460575810932 300600600

4 2404806009470823046057512151400 450900900 36072090014205923046057522502590 80016001600 6651325167025380 rockwell automation Publication 500-TD014C-EN-P - March 20173 NEMA Contactor and Starter SpecificationsMechanical Ratings Construction Environmental NEMASizeMechanical Life(Millions of Operations)Maximum Number ofAuxiliary ContactsOperating Time [ms]Pick-up (Average)Drop-out (Average) 888408 888459 811884 NEMASizeWire Size forPower TerminalsRequired Torque onPower Terminal WireClamps and PressureConnectors or LugsTy p e o f PowerTerminalContact MaterialRequirements for Sizing of WirePower ContactsAuxiliary Contacts00# AWG9 lb inPressure terminalsSilver alloySilverAll wire rated 167 F (75 C) or higher must be sized per the local Electrical Code for167 F (75 C) # AWG20 lb inSaddle or wire clamps1# AWG20 lb in2# AWG45 lb inPressure terminals3# AWG150 lb in4# AWG275 lb in5#4 MCM375 lb in6 Lugs sold separately(1)(1)Contact your local Allen-Bradley distributor or rockwell automation sales bus connections onlyNEMASizeOperatingPositionOperatingTe mperature RangeAltitudeCorrosion-Resistance00 HorizontalStarters with eutectic alloyOverload relay +149 F ( +65 C)Starters with SMP Overload relay +131 F ( +55 C)(provided condensation is prevented)10 000 feet before deratingAll metal parts are treated forcorrosion-resistance0 Vertical123456 Horizontal7 Vertical894 rockwell automation Publication 500-TD014C-EN-P - March 2017 NEMA Contactor and Starter SpecificationsShort Circuit RatingCombination contactors and starters with disconnect switch.

5 Bulletin 502, 506, 512, 522E, 522F, and 522 GCombination Contactors and Starters with Disconnect Switch: Bulletin 502, 506, 512, 522E, 522F, and 522 GNEMASizeFuseTypeAvailable Short Circuit Amperes RMS Symmetrical [A]Maximum Voltage[V] , , K10 , R100 0006L18 0007L18 000 Combination Lighting Contactors with Disconnect Switch: Bulletin 502 LLighting Contactor Rating[A]FuseTypeAvailable Short Circuit Amperes RMS Symmetrical [A]Maximum Voltage[V] , , K10 , R100 000 Combination Contactors and Starters with Circuit Breaker: Bulletin 503, 507, 513, 523E, 523F, and 523 GEnclosureTypeNEMASizeAvailable Short Circuit Amperes RMS Symmetrical [A]Maximum Voltage[V]1, 3R, 3R/4/12, 4/4X (stainless) 000480 Unilock 3R, 7, & 9 Bolted 3R, 7, & 93R, 3R/4/12, 4/4X (stainless)1, 3R, 3R/4/12, 4/4X (stainless) 000600 Unilock 3R, 7, & 000 Bolted 3R, 7, & 93R, 3R/4/12, 4/4X (stainless)618 000725 000 Combination Lighting Contactors with Circuit Breaker.

6 Bulletin 503L EnclosureTypeLighting Contactor Rating[A]Available Short Circuit Amperes RMS Symmetrical [A]Maximum Voltage[V]1, 3R, 3R/4/12, 4/4X (stainless) 000480 Unilock 3R, 7, & 000 Bolted 3R, 7, & 0001, 3R, 3R/4/12, 4/4X (stainless) 000600 Unilock 3R, 7, & 000 Unilock 3R, 7, & 3R, 7, & automation Publication 500-TD014C-EN-P - March 20175 NEMA Contactor and Starter SpecificationsAC Coil DataAuxiliary Contacts (NEMA A600 and P300) Bulletin 595, 596 NEMA SizeOperating Volt Amperes Burden [VA]Heat Dissipation [W]Coil Operating Limits60 Hz & ( poles) ( poles) ( poles)66045103 ( poles)84058104 ( poles) ( poles) (Series L) (1)(1)This rating is for the size 6 Contactor coil only. All starters are shipped with an interposing relay as (Interposing relay) 7 (2)(2)Size 7 starters are shipped with a 250 VA control circuit transformer and an interposing relay with a 120V coil.

7 Voltage is then rectified to DC for the Contactor DC Coil 7 (Interposing relay) 8 (3)(3)Size 8 starters are shipped with a 350 VA control circuit transformer and an interposing relay with a 120V coil. Voltage is then rectified to DC for the Contactor DC Coil 8 (Interposing relay) 9 (4)(4)Size 9 starters are shipped with a 750 VA control circuit transformer and an interposing relay with a 120V coil. Voltage is then rectified to DC for the Contactor DC Coil 9 (Interposing relay) Maximum AC Contact Rating Per PoleAC RatingDesignationMaximum Voltage60 Hz or 50 Hz[A]Continuous CarryingCurrent [A][VA] DC Contact Rating Per Pole (Maximum Continuous Carrying Current is 5 A)DC Rating Designation125V DC250V DC600V A(Requires 2 Contacts in Series) A(Requires 2 Contacts in Series)6 rockwell automation Publication 500-TD014C-EN-P - March 2017 NEMA Contactor and Starter SpecificationsLoad-life CurvesBulletin 500 Line contactors and starters are designed to provide high performance in various applications.

8 These load-life curves are based on rockwell automation tests according to the requirements defined in IEC 947-4. Actual contact life may vary based on the application, duty cycle, and environmental conditions from that indicated by the find the Contactor s estimated electrical life, follow these guidelines: Choose the appropriate graph that most closely approximates the utilization category of the application. Locate the intersection of the life-load curve of the appropriate Contactor with the application s operational current (Ie) found on the horizontal axis. Read the estimated contact life in millions of operations along the vertical Life for Mixed Utilization Categories AC3 and AC4In many applications, the utilization category cannot be defined as either purely AC3 or AC4. In those applications, the electrical life of the Contactor can be estimated from the following equation:Where:L mixed= Approximate contact life for a mixed AC3/AC4 utilization category applicationL AC3= Approximate contact life in operations for AC3 utilization category (from AC3 life-load curves below)L AC4= Approximate contact life in operations for AC4 utilization category (from AC4 life-load curves below)P AC4= Percentage of AC4 operationsUtilization CategoriesCategory Typical Duty.

9 AC3 Starting of squirrel cage motors and switching off only after the motor is up to of squirrel cage motors with inching and plugging 500 Load / Life Curves AC3 and AC4 ( )L mixed =L AC31 + PAC4 1L AC3L AC4 NEMA SIZEOPERATING CYCLES10M8M6M4M2M1M800K600K400K200K100K8 0K60K40K20K10 KOPERATIONAL CURRENT Ie (APMERES)AC3 NEMA SIZEOPERATING CYCLES10M8M6M4M2M1M800K600K400K200K100K8 0K60K40K20K10 KAC4 OPERATIONAL CURRENT Ie (APMERES) rockwell automation Publication 500-TD014C-EN-P - March 20177 NEMA Contactor and Starter SpecificationsApproximate DimensionsApproximate dimensions are shown in inches (millimeters). Dimensions are not intended for manufacturing 500 and 509 Contactors and Starters, 3-Pole Type 1 General Purpose Lift-Off EnclosureBulletins 500, 505, 509, 520E, 520F, and 520G Contactors / Starters, Type 1 Hinged Enclosure with or without Control TransformerNote.

10 For Types 3R/12, 4/4X, 4X, and Bolted Type 7 & 9 and 3R, 7 & 9 dimensions, contact your local rockwell automation sales office or Allen-Bradley Size/ Current RatingDimensions in Inches (Millimeters)AWidthB HeightC DepthDEFGHJ (171) (246) (71) (104) (25) (48) (163) (41) (25) (37) (86) (184) (325) (71) (104) (31) (60) (226) (49) (31) (37) (92)NEMA Size/ Current RatingBulletin in Inches (Millimeters)AWidthBHeightCDepthDEMounti ngFMountingGMountingHJ(Mounting) & (254) (381) (162) (148) (127) (95) (191) (27) (324)2500 & 509without transformer2500 & 509with (356) (457) (162) (148) (178) (146) (292) (25) (400) & 5203500 & (330) (559) (216) (201) (165) (133) (267) (27) (502)2505 & MTG & 1-1/8 DOUBLE PLACESONE ADDITIONAL KNOCKOUT ONRIGHT SIDE(LEFT VIEW)(FRONT VIEW)(BASE VIEW)SIZE 0-1 ONLY(BOTTOM VIEW)(3 ADDITIONAL KNOCKOUTS AT TOP) 2 MTG (BASE VIEW)SIZE 2 3 MTG ,1[]JHBGFCDKNOCKOUTS FOR(4) PILOT DEVICESDOOR PADLOCKFEATURE15" X 10" X 6(5) PILOT DEVICES18" X 14" X 622" X 13" X 9"8 rockwell automation Publication 500-TD014C-EN-P - March 2017 NEMA Contactor and Starter SpecificationsApproximate dimensions are shown in inches (millimeters).