NLAB Panelboards - Filnor

The NLAB panel providesprotection for lightning andappliance circuits in commercialand industrial :AC Systems - 240 volt maximum 3 Phase 4 Wire with Neutral 1 Phase 3 Wire with Neutral 1 Phase 2 Wire with Neutral 3 Phase 3 WireInterior: Branch circuit breakers to bebolted to bus All bus bar to be copper rated1000 ampere per square inch Standard short circuit bracingfor 10,000 AIC Underwriters Laboratories : Door and trim are flat gaugesteel per code Flush catch and lock Continuous piano hinge Fronts bolted to box Standard painted finish ANSI61 gray Directory card with plasticcover on back of doorBoxes: Galvanized sheet steel per codegauge 3/4 inch flange for rigidity andfastening trim Blank ends Wire gutters meet or exceedUL/NEC requirementsApplications: Filnor , Inc.

Furnish factoryassembled NLAB panelboards complete with enclosing cabinets as manufactured by Filnor, Inc. where indicated on the drawings. Provide

Tags:

  Panelboard, Nabl, Nlab panelboards

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Advertisement

Transcription of NLAB Panelboards - Filnor

1 The NLAB panel providesprotection for lightning andappliance circuits in commercialand industrial :AC Systems - 240 volt maximum 3 Phase 4 Wire with Neutral 1 Phase 3 Wire with Neutral 1 Phase 2 Wire with Neutral 3 Phase 3 WireInterior: Branch circuit breakers to bebolted to bus All bus bar to be copper rated1000 ampere per square inch Standard short circuit bracingfor 10,000 AIC Underwriters Laboratories : Door and trim are flat gaugesteel per code Flush catch and lock Continuous piano hinge Fronts bolted to box Standard painted finish ANSI61 gray Directory card with plasticcover on back of doorBoxes: Galvanized sheet steel per codegauge 3/4 inch flange for rigidity andfastening trim Blank ends Wire gutters meet or exceedUL/NEC requirementsApplications: Filnor , Inc.

2 Is a leader in customand commercial lightning anddistribution panels for: Aerospace Banking Communications Data Processing Electronics Government Medical Military Petrochemical UPS Power/Distribution Utilities Waste Water/SanitationPage 1 of 5 NLAB PanelboardsApplicationsNLAB Box 2328 227 N. Freedom Ave. Alliance, OH 44601 Phone: (330) 821-7667 Fax: (330) 829-3175 Website: Email: c o mNLAB Panelboards 5/25/04 5:54 PM Page 1 Furnish factoryassembled NLAB Panelboards complete withenclosing cabinets asmanufactured by Filnor , indicated on thedrawings. Providepanelboards of dead front,circuit breaker type, 120/240volt 1 phase 3 wire , 208Y/120volt 3 phase 4 wire solidneutral, with main lugs ormain switch/breaker asi n d i c a t e d.

3 Circuit breakers shall be bolt-on-type, quick-make quick-break, trip-free, thermalmagnetic with a minimuminterrupting capacity of10,000 amperes symmetricalat rated voltage. Trippedindication shall be clearlyshown on the breaker handletaking a position between ON and OFF. Circuitbreakers shall be equippedwith individually insulated,braced and protectedconnectors. Branch breakersto be connected for sequencephasing, breakers 1 and 2connected to phase a ,breakers 3 and 4 to phase b ,etc, to conform to branchcircuit numbering systemshown on drawing. Polarity orblock phasing will not beacceptable.

4 The front faces ofall circuit breakers shall beflush with each other. Largepermanent individualnumbers shall be affixed inauniform position. Provisionsfor additional breakers shallbe such that field addition ofconnectors or mountinghardware will not be requiredto add breakers to thepanelboard. Where spaces arecalled for, panel bus shall beextended behind the bus structure andmain lugs, main breaker ormain switch shall havecurrent ratings as shown onthe panelboard schedule. Suchratings shall be established byheat rise tests with maximumhot spot temperature on anyconnector or bus bar.

5 Heatrise test shall be conducted inaccordance with UL 67. Allbus bar shall be copper. Busbar shall be rated for 1000amperes per square inchm i n i m u m .The panelboard assemblyshall be enclosed in a steelcabinet. The size of the wiringgutters and gauge of steelshall be in accordance withNEMA Standards PublicationNo. PB1 and UL StandardsNo. 67 for Panelboards . Thebox shall be fabricated fromgalvanized steel or equivalentrust resistant steel. Enclosureto be for indoor or outdooruse as indicated. A ground baris to be furnished in the shall include a doorover the breaker handles witha tumbler-type lock withcatch.

6 The inner door shall beover the switch handles over 48 inches inheight shall be equipped withthree-point catch and lockwith vault handle. Allpanelboard locks to be keyedalike. A circuit directory cardwith clear plastic coveringshall be provided on theinside of the inner AssuranceReference Latest Standards:Underwriters Laboratories Inc.(UL) - UL and boxes - UL 50 National Electrical Manufacturers Association (NEMA) -PB1 (latest revision)Federal Case Circuit BreakersWP-375bNational Fire Protection Association (NFPA) 70, National ElectricalCode (NEC)Requirements of Regulatory Codes and OrdinancesPage 2 of 5 NLAB PanelboardsSpecificationsNLAB Box 2328 227 N.

7 Freedom Ave. Alliance, OH 44601 Phone: (330) 821-7667 Fax: (330) 829-3175 Website: Email: c o mNLAB Panelboards 5/25/04 5:54 PM Page 21 Phase 3 Wire SN1 20/240 Volts AC or DC# of Mains AmpereCabinetApprox. ShippingPolesCatalog #RatingHeightWeight12 NLAB12-3L100A236514 NLAB14-3L100A307816 NLAB16-3L100A307818 NLAB18-3L100A307820 NLAB20-3L225A339522 NLAB22-3L225A339524 NLAB24-3L225A339526 NLAB26-3L225A3610728 NLAB28-3L225A3610730 NLAB30-3L225A3610732 NLAB32-3L225A3911934 NLAB34-3L225A3911936 NLAB36-3L225A3911938 NLAB38-3L225A4213040 NLAB40-3L225A4213042 NLAB42-3L225A42130 Main Switch/Main Circuit Breakers: Mounted Circuit Breakers: 20 amp.

8 Single pole, 120 volt, AC. 15 thru 60 amp. ratings for single pole breakers canbe furnished at the same price when Only or Provisions for Future Breakers: Figure panel for total number of poles, including Pole Main BreakerBoxes 20 Wide# of Mains AmpereCabinetApprox. ShippingPolesCatalog #RatingHeightWeight12 NLAB12-3AB100A308514 NLAB14-3AB100A3310516 NLAB16-3AB100A3310518 NLAB18-3AB100A3310520 NLAB20-3AB225A3916022 NLAB22-3AB225A3916024 NLAB24-3AB225A3916026 NLAB26-3AB225A4217528 NLAB28-3AB225A4217530 NLAB30-3AB225A4217532 NLAB32-3AB225A4519234 NLAB34-3AB225A4519236 NLAB36-3AB225A4519238 NLAB38-3AB225A4820540 NLAB40-3AB225A4820542 NLAB42-3AB225A48205 Page 3 of 5 NLAB-33 Phase 4 Wire SN120/208 Volts# of Mains AmpereCabinetApprox.

9 ShippingPolesCatalog #RatingHeightWeight12 NLAB12-4L100A236514 NLAB14-4L100A307816 NLAB16-4L100A307818 NLAB18-4L100A307820 NLAB20-4L100A339522 NLAB22-4L100A339524 NLAB24-4L100A339526 NLAB26-4L100A3610728 NLAB28-4L100A3610730 NLAB30-4L100A3610732 NLAB32-4L225A3912234 NLAB34-4L225A3912236 NLAB36-4L225A3912238 NLAB38-4L225A4213340 NLAB40-4L225A4213342 NLAB42-4L225A421333 Pole Main BreakerBoxes 20 Wide# of Mains AmpereCabinetApprox. ShippingPolesCatalog #RatingHeightWeight12 NLAB12-3AB100A308514 NLAB14-3AB100A3310516 NLAB16-3AB100A3310518 NLAB18-3AB100A3310520 NLAB20-3AB225A3916022 NLAB22-3AB225A3916024 NLAB24-3AB225A3916026 NLAB26-3AB225A4217528 NLAB28-3AB225A4217530 NLAB30-3AB225A4217532 NLAB32-3AB225A4519234 NLAB34-3AB225A4519236 NLAB36-3AB225A4519238 NLAB38-3AB225A4820540 NLAB40-3AB225A4820542 NLAB42-3AB225A48205 NLAB-4 NLAB PanelboardsCatalogue No.

10 & OptionNLAB PanelboardsCatalogue No. & Box 2328 227 N. Freedom Ave. Alliance, OH 44601 Phone: (330) 821-7667 Fax: (330) 829-3175 Website: Email: c o mNLAB Panelboards 5/25/04 5:54 PM Page 3 Mains: Increase bus capacity to 400ampere Main breaker to 400 ampere Main fused disconnect switch Compression lugs Sub-feed lugs Asco remote control as mainInteriors: To fit existing boxes Split bus or meter loop Remote control switches 200% rated neutral Time clock Sub-feed breakersBoxes: Aluminum Stainless steel Nema 3R Nema 4X Nema 12 Special drilling Special knockouts Increase gauge Increase gutters PaintedFronts.