Transcription of NO HYDRANT–NO PROBLEM - TurboDraft™
1 Lightweight design sets up in minuteswith minimal personnel using 5-inchlarge diameter hose (LDH) No need for cumbersome hard suctionhose Gain access to static water sourcespreviously unreachable usingtraditional drafting techniques Usable in lakes, ponds, streams, rivers,canals, swimming pools, etc. Generate usable fire flow rates of 670gpm or more Recognized by insurance agencies asan alternate water supply source Eliminate need for multiple dryhydrant installations No permits, engineering ormaintenance Suitable for emergency dewateringand flood mitigationN O H Y D R A N T N O P R O B L E MF I R E E D U C T O RTurboDraft WATER EDUCTOR FOR fire FIGHTINGD istant Water Source Situation1,2,3for 5 UnitPumpLength ofLift Discharge Available 5 HosePressureFire Flow1.
2 250 10 165 psig670 GPM20 165 psig470 GPM100 10 170 psig570 GPM20 170 psig400 GPM150 10 175 psig480 GPM20 175 psig325 GPM200 10 180 psig440 GPM20 180 psig280 GPM2 1/2 NSTCONNECTIONSUCTION FLOWDISCHARGE 5 STORZMOTIVEWATER SUPPLYF igure 15 SUPPLY LINE2 1/2 DISCHARGELINEV alues listed reflect the minimum available flow rate in gallons per : Using 6 large diameter hose line can increase usable flow bydecreasing line friction ,2,3 See back cover for WATER SOURCES IN REMOTE LOCATIONSR ural fire departments need creative solutions to use water sources that are not accessible using typical draftingtechniques.
3 Schutte & Koerting s TurboDraft fire Eductor allowsfire departments to tap into water supplies like lakes, ponds,streams, and rivers, etc. at a distance of up to 200' or more. Usablefire flows of 670 gpm or more may be achieved dependent uponhose layout and elevation SETUPW eighing only 48 lbs., the 5-inch TurboDraft fire Eductor can easilybe put into service with minimal personnel. Setup is quick andsimple utilizing standard fire service hose lines. Once the 21 2" feedline and 5" LDH return line are connected, the TurboDraft isdeployed into the static source. (See Figure 1)TURBODRAFT OPERATIONOnce the TurboDraft fire Eductor has been deployed it can bequickly placed into service.
4 The inlet suction valve of the pumpingengine is left closed and its air bleeder is opened. The 21 2" line ischarged using water from the onboard water tank. The force of thisflow combined with TurboDraft eductor technology creates asuction that draws water from the static source. As this happens,the large diameter hose (LDH) is charged back to the pump suctionvalve. After the air is bled from the LDH, the bleeder valve is closedand the intake valve is opened. At this point the water supply hasbeen established. 200 gpm is re-circulated through the pump tomaintain a continuous flow without the need of the onboard watertank. The balance of the drafted water is now available to supplyhand lines, hose lays, or to fill tanker/tender operations.
5 Usableflows will vary based on elevation and hose friction loss. (See Table 1)Table 1 HARDSUCTIONHOSE 100' TURBODRAFT STATIC WATER SOURCE PORTABLE PUMP OR FIELD/BRUSH TRUCK PORTA-TANK5" or 6" LDHFIRE fighting APPLICATION CHALLENGES2-1/2" 5" or 6" LDH 100' TURBODRAFT STATIC WATER SOURCE Solution ABy stretching a 21 2" supply line and a 5" or 6" return line, usablewater supply of 600 GPM or more can be achieved at a distance of over 100 feet. Actual usable water supply will be determined bydischarge line loss and elevation differences between water sourceand pump BUtilize a portable pump or truck mount pump (minimum rating of200 gpm @ 150 psi) to supply the TurboDraft fire Eductor.
6 Achieveusable fire flows of 800 GPM or "5" or 6" LDH 100'TURBODRAFTSTATIC WATER SOURCEPORTA-TANKHARDSUCTIONHOSEPORTABLE PUMP ORFIELD/BRUSH TRUCKPORTA-TANKPORTA-TANKDUMP-SITETURBOD RAFT IN TANK 100' - 300'5" or 6" LDHHARDSUCTIONHOSEPORTA TANKFIRE SCENETANKERDUMPPORTA-TANK1. Access to a water source is more than 30 feet and typical drafting techniques cannot be implemented2. Due to congestion at the fire scene, portable tanks for tanker delivery need to be set up at remotelocationSolution COne or more TurboDraft units operating to fill a portable tankallowing pumper to have access with hard suction hose. TurboDraftlines are directed into tank while pumper drafts to supply the unitsas well as the fire ground or to fill can be used in conjunction with a portable pump toprovide constant flow between remote tanks and fire scene supplytank.
7 Flow from the remote tanks can be controlled by a gate valvein the 5" or 6" supply line. If discharge line is blocked, supply lineflow is discharged into portable tank and Flood mitigation and water transferTURBODRAFT2-1/2"5" or 6" LDHT urboDraft can also be employed in emergency flood s ability to transfer large volumes of water in a short amount of time makes it a critical piece of equipment for dewatering basements and other low-lying areas where water TECHNOLOGYS chutte & Koerting eductors have been used in thousandsof industrial applications for more than a century. Theyemploy the venturi principle to create flow and increasepressure.
8 Eductors use the kinetic energy of one liquid to create motion in a second liquid. With no moving partsto break, eductors are one of the most reliable technologiesever water eductors for fire fighting have been standardequipment on many Navy ships since WWII. The sameeductor technology has also been used in fire fighting formore than thirty years in foam eductor Metropolitan DriveTrevose, PA 19053tel: (215) 639-0900fax: (215) 639-1597email: PendingTurboDraft is a trademark of Schutte & WATER EDUCTOR FOR fire FIGHTINGT urboDraft Performance for 5 UnitGraph 1 Homeland Security-Municipal EmergenciesISO9001:2008 Certified1 Theoretical, based on test curves of 9/21/99 and hose friction loss per NFPA fire Protection Handbook, 15th Edition, Table 17-7H, actual friction losses may vary depending upon hose and coupling flows achievable with 1,000 GPM rated pumper based on NFPA recommended pump curves.
9 Use larger pumper where maintenance/ performance is available flow from a water source recognized by ISO for grading purposes is 250 GPM. ISO does not recognize drafting sources requiring a liftin excess of 18' (This is not a drafting device as it operates under pressure.)Although the TurboDraft was designed with the rural firedepartment in mind, large municipal departments can alsoutilize the TurboDraft eductor technology. The majority ofcity-based departments are generally not equipped fornon-hydrant water supply operations. During natural orman-made emergencies municipal water supply systemscan be rendered useless.
10 The TurboDraft allowsdepartments with basic hose lines and minimal training toaccess static sources for fire suppression as well as floodmitigation w w. t u r b o d r a f t . n e t11 3/1624 5/85/838 3/4 For more information, please visit our websiteor call us to speak with a representative30201001002003004005006007 00800900180 PSIG Supply Pressure165 PSIG Supply Pressure150 PSIG Supply PressureDischarge Head (ft)Available fire Flow (GPM)Supply flow is 200 GPM at 180 psig truck pressur