Example: air traffic controller

NPS/003/001 Technical Specification for 33kV, 66kV and ...

Document reference NPS/003/001 Document Type: Code of Practice Version:- Date of Issue:- February 2015 Page 1 of 25. NPS/003/001 Technical Specification for 33kv , 66kV and 132kV Voltage Transformers 1. Purpose This purpose of this document is to specify the Technical requirements for open terminal voltage transformers (VTs) for use on the distribution networks of Northern Powergrid (the Company). This document supersedes the following documents, all copies of which should be destroyed. Ref Version Title NPS/003/001 3 Technical Specification for 66kV and 132kV Voltage Transformers NPS/003/001 4 Technical Specification for 66kV and 132kV Voltage Transformers 2.

Document reference NPS/003/001 Document Type: Code of Practice Version:-5.0 Date of Issue:-February 2015 Page 1 of 25 CAUTION! - This document may be out of date if printed NPS/003/001 – Technical Specification for 33kV, 66kV and 132kV Voltage Transformers 1. Purpose

Tags:

  Specification, Technical, 33kv, Nps 003 001 technical specification

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of NPS/003/001 Technical Specification for 33kV, 66kV and ...

1 Document reference NPS/003/001 Document Type: Code of Practice Version:- Date of Issue:- February 2015 Page 1 of 25. NPS/003/001 Technical Specification for 33kv , 66kV and 132kV Voltage Transformers 1. Purpose This purpose of this document is to specify the Technical requirements for open terminal voltage transformers (VTs) for use on the distribution networks of Northern Powergrid (the Company). This document supersedes the following documents, all copies of which should be destroyed. Ref Version Title NPS/003/001 3 Technical Specification for 66kV and 132kV Voltage Transformers NPS/003/001 4 Technical Specification for 66kV and 132kV Voltage Transformers 2.

2 Scope This Specification details the requirements for 33kv , 66kV and 132kV Voltage Transformers (VT s) for use in open terminal substations on the distribution networks of Northern Powergrid. The VT's detailed in this Specification are designed for protection, measurement and voltage control of power systems up to 132kV. This Specification shall be used in conjunction with any project specific requirements detailed in Appendix 5, Addendum to Supplier Requirements. CAUTION! - This document may be out of date if printed Document reference NPS/003/001 Document Type: Code of Practice Version:- Date of Issue:- February 2015 Page 2 of 25.

3 Contents 1. Purpose .. 1. 2. Scope .. 1. Contents .. 2. 3 Technical Requirements .. 3. General Design Requirements .. 3. Voltage Transformers .. 3. External Insulation .. 3. Additional material requirements associated with the composite construction external insulation .. 3. Internal arc fault protection requirements .. 4. Secondary Wiring Enclosure .. 5. Design 5. Short Circuit Withstand Capability .. 5. 4. References .. 6. External 6. Internal documentation .. 6. Amendments from Previous Version .. 6. 5. Definitions .. 7. 6. Authority for issue.

4 8. Appendix 1: Electrical Ratings 33kv , 66kV and 132kV VTs .. 9. Appendix 2: Declaration of Technical performance of VT .. 15. Appendix 3 - Pre-commission testing, Routine Inspection and Maintenance requirements .. 18. Appendix 4 - SELF CERTIFICATION CONFORMANCE DECLARATION .. 19. Appendix 5: Addendum to supplier 24. Appendix 6: Technical Information Check List .. 25. CAUTION! - This document may be out of date if printed Document reference NPS/003/001 Document Type: Code of Practice Version:- Date of Issue:- February 2015 Page 3 of 25.

5 3 Technical Requirements The VT's detailed in this Specification are designed for use in outdoor open terminal substations for protection, measurement and voltage control of power systems up to 132kV. The VT's are generally mounted on aluminium or steel support structures and connected to adjacent equipment using copper or aluminium busbars. General Design Requirements Voltage Transformers VT s shall be in accordance with BS EN 61869 parts 1, 3 and 5, the requirements listed below and in Appendix 1 of this document. Two secondary outputs should be provided which shall be either protection or metering class (see Appendix 1).

6 VTs will be connected between line and earth in star configuration with the star point directly earthed. 33 - 66kV VTs shall be Inductive VT's to BS EN 61869-3. 132kV VTs shall be capacitive VTs to BS EN 61869-5. The provision of arcing horns is required. VTs will preferably have been assessed by the Energy Networks Association (ENA) and awarded an ENA Certificate of Conformance. The Technical Specification of VTs must be confirmed using the table in Appendix 2. External Insulation The external insulation of the VTs shall comply with the requirements of BS 3297-2 designation C.

7 And Appendix 1 of this Specification . The external insulation shall be manufactured from either grey silicon rubber hollow core composite material that has been tested in accordance with IEC 61462 and IEC 62217 or from brown porcelain cylindrical material tested in accordance with IEC 60168 and has been proven to satisfy clause of this Specification . Additional material requirements associated with the composite construction external insulation The Hollow composite external insulation consists of an insulating tube manufactured from high strength glass fibre reinforced plastic bearing the mechanical load which is protected by an elastomeric housing.

8 Silicon rubber is a very generic term with many formulations. Variations in the composition of this material can adversely affect its long term performance to provide the following very important properties:- UV resistance Tracking Resistance Hydrophobicity CAUTION! - This document may be out of date if printed Document reference NPS/003/001 Document Type: Code of Practice Version:- Date of Issue:- February 2015 Page 4 of 25. As a result a range of good practice characteristic values have been included within this Specification Material Composition Minimum % per weight Base Rubber consisting of approx.

9 37% Silicone Polymer 47 %. (Polydimethylsiloxane) (PDMS) and 10% Silica Filler (ATH Aluminium tri hydrate and fumed silica) 52 %. Additional parts (pigments, crosslinkers) 1%. Where manufacturers differ from this characteristic composition, they shall provide supporting evidence about the long term experience of their product formulation. The following table provides a list of characteristic properties that result from the above formulation. Manufacturers shall provide details of their characteristic properties for consideration. Minimum acceptable values are detailed below.

10 Property Minimum Value Density Passing Voltage Level of IEC 60587 Flammability Class of IEC 60695-11-10 of 3mm specimen VO. Tensile Strength (Din 53504-S1) 6 N/mm2. Break Elongation (Din 53504-S1) 300%. UV resistance @ 300nm the energy of UV wavelength that equates 445 kJ/Mole to a molecular energy breakdown level of 398 kJ/mole *. * assumed wavelength of UV light (sun) 290 350nm All silicon rubber insulators shall be manufactured using the HTV (high temperature vulcanising) method and shall ensure that the interface between the housing and the core is chemically bonded.


Related search queries