Example: biology

NS8000 Series Network Sensors Catalog Page

NS8000 DescriptionFigure 1: NS8000 Series Network Sensor modelsThe NS Series Network Sensors function directlywith Metasys system Field Equipment Controllers(FECs), Metasys Network and Control Engines(NCEs), Advanced Application Field EquipmentController (FACs), Metasys VAV Box EquipmentControllers (CVM) and General Purpose ApplicationControllers (CGM), VAV Modular Assembly (VMA16)Controllers, and Facility Explorer FX-PC SeriesProgrammable Controllers (FX-PCGs, FX-PCVs, andFX-PCXs). The Sensors are also compatible withVerasys and Johnson Controls Smart NS Series Network Sensors monitor zonetemperature, relative humidity (RH), carbon dioxide(CO2), motion, and local temperature setpointadjustments. The sensor transmits this data to acontroller on the Sensor/Actuator (SA) NS Series Network Sensors models include anonboard passive infrared (PIR) occupancy sensorthat detects motion to determine if a space isoccupied. This feature maximizes up to 30% energysavings in high-energy usage environments such asschools, dormitories, offices, hospitals, and hotelsby adjusting the temperature of the space based onthe occupancy status.

modular phone jacks and screw terminals to terminate wiring connecting the sensors to the controller. Note: To connect the NS Series Network Sensor to the same SA bus segment, use only one of the two connection methods, either the modular phone jack or the screw terminals. Each network sensor includes a SA bus access

Tags:

  Series, Screw, Jack

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of NS8000 Series Network Sensors Catalog Page

1 NS8000 DescriptionFigure 1: NS8000 Series Network Sensor modelsThe NS Series Network Sensors function directlywith Metasys system Field Equipment Controllers(FECs), Metasys Network and Control Engines(NCEs), Advanced Application Field EquipmentController (FACs), Metasys VAV Box EquipmentControllers (CVM) and General Purpose ApplicationControllers (CGM), VAV Modular Assembly (VMA16)Controllers, and Facility Explorer FX-PC SeriesProgrammable Controllers (FX-PCGs, FX-PCVs, andFX-PCXs). The Sensors are also compatible withVerasys and Johnson Controls Smart NS Series Network Sensors monitor zonetemperature, relative humidity (RH), carbon dioxide(CO2), motion, and local temperature setpointadjustments. The sensor transmits this data to acontroller on the Sensor/Actuator (SA) NS Series Network Sensors models include anonboard passive infrared (PIR) occupancy sensorthat detects motion to determine if a space isoccupied. This feature maximizes up to 30% energysavings in high-energy usage environments such asschools, dormitories, offices, hospitals, and hotelsby adjusting the temperature of the space based onthe occupancy status.

2 In addition, the PIR occupancysensor facilitates trending of floor space usage inthese models of the NS Series Network Sensorsare available with a backlit LCD fixed segmentdisplay or a full color graphical LCD interface. Thesemodels allow the user to view zone temperature,RH, CO2, and adjust the zone temperature setpointand fan speed. Graphical models provide asummary of sensor values at the base of the segment models have the capability to set thedefault display to temperature, RH, or user can also choose between degreesFahrenheit (F) and degrees Celsius (C). To preventtampering with the sensor, display models alsoinclude a screen lockout feature. The graphicaldisplay enables the user to choose between a lightor dark color theme and to set the sleep mode todim or turn models also have a Warmer/Cooler interfaceto adjust the zone temperature. Instead of adisplay, these models have two cap touch buttonswith seven LED lights that represent the display models include the followingfan speeds: automatic, off, low, medium, or with the sensor sets the occupancyoverride function to signal to the controller thatthe zone is occupied and to override the scheduledmode.

3 The full color graphical LCD models use theNS8000 Series Network Sensors Catalog PageLIT-1901099 2021-09-20graphical user interface to set a unique BACnet address for applications that require multiplesensors. Other models have DIP switches to seta unique address for applications that requiremultiple Sensors . All models ship standard withmodular phone jacks and screw terminals toterminate wiring connecting the Sensors to : To connect the NS Series Network Sensorto the same SA bus segment, use only oneof the two connection methods, either themodular phone jack or the screw Network sensor includes a SA bus accessport, allowing for accessories to connect to theSA bus. Through this connector, the user can useaccessories to service or commission the connectedcontroller or gain access to any other controller onthe same field controller (FC) : Device programming for the NS8000sensor connected to the controller does notinclude balancing functionality and NS Series Network Sensors can be surfacemounted or vertical wallbox mounted to meet therequirements of the specific application.

4 All displaymodels are optimized for the California Energy Code(Title 24). To suit specific architectural and interiordesign needs, the models come with either black orwhite enclosures in black or white design themesare available in the following styles: LCD fixed segment and LCD full color graphicaldisplays: view zone temperature, RH, CO2,occupancy status, and adjust the zonetemperature setpoint and fan speed. Thesemodels have the capability to set the defaultdisplay to temperature, RH, or temperaturesetpoint. On these display models, you can alsochoose between degrees Fahrenheit (F) anddegrees Celsius (C). Warmer/Cooler interface: this interfaceincorporates cap touch buttons with seven LEDlights that represent the current setpoint status. No display: the NS Series Network Sensors areavailable in high gloss black or white with orwithout the Johnson Controls logo. All Sensors are serialized for quality and warrantypurposes. Based on the serial number, the usercan obtain factory calibration : The LCD full color graphical models areonly available in white.

5 See Table 1 throughTable 6 for ordering to the NS 8000 Series Network Sensors ProductBulletin (LIT-12013113) for important productapplication and single point of contact and benefits BACnet MS/TP protocol communication:provides compatibility with Metasys systemfield controllers, Facility Explorer programmablecontrollers as well as Verasys and JohnsonControls Smart Equipment in a provencommunication Network . Single and multifunctional Sensors : choosetemperature, RH, CO2, and occupancy sensingdepending on HVAC needs. Large backlit LCD fixed segment display or LCDfull color graphical display on some models:provides real-time status of the environment withbacklighting activated during user interaction. Simple temperature setpoint adjustment orWarmer/Cooler mode available on displaymodels: configure simple setpoint adjustment orWarmer/Cooler mode. Onboard occupancy sensor available on PIRmodels: maximizes up to 30% energy savings inhigh-energy usage environments, and facilitatestrending of floor space usage.

6 Temporary occupancy included on all displayand Warmer/Cooler models: provides a timedoverride command, which initiates a temporaryoccupancy state. Field-selectable default display setting on displaymodels: toggle between temperature, RH ortemperature setpoint on the display, and set thedesired default for continuous viewing. Fahrenheit/Celsius ( F/ C) selectable on displaymodels: display temperature in degreesFahrenheit or degrees Series Network Sensors Catalog Page All display models meet California Energy Code(Title 24): displays the required State of CaliforniaTitle 24 economizer fault conditions. All display models include a screen lockout:prevents sensor tampering. Serialized Sensors and calibration certificates:obtain factory calibration certificates for informationIf the NS Series Network Sensor fails to operatewithin its specifications, replace the unit. For areplacement sensor, contact the nearest JohnsonControls informationSee Table 1 through Table 6 for the various NSSeries Network Sensor models available.

7 See Table 7for : The NS Series Network Sensor isintended to provide an input to equipmentunder normal operating conditions. Wherefailure or malfunction of the Network sensorcould lead to personal injury or propertydamage to the controlled equipment orother property, additional precautionsmust be designed into the control and maintain other devices, suchas supervisory or alarm systems or safety orlimit controls, intended to warn of or protectagainst failure or malfunction of the : Keep the Metasys system software upto date as some NS Series Network Sensorfeatures are not supported in previous releasesof Metasys, Facility Explorer, Verasys, orJohnson Controls Smart Equipment chartsTable 1: NS Series Network Sensor ordering information: temperature, humidity and CO2 models (3%RH)Product code numberDisplay and interface informationJohnson Controls logoColorPIR occupancy sensorNSB8 BHC040-0 YesWhiteNoNSB8 BHC041-0 NoWhiteNoNSB8 BHC042-0 YesBlackNoNSB8 BHC043-0 NoBlackNoNSB8 MHC040-0 YesWhiteYesNSB8 MHC041-0 NoWhiteYesNSB8 MHC042-0 YesBlackYesNSB8 MHC043-0No displayNoBlackYesNSB8 BHC240-0 YesWhiteNoNSB8 BHC241-0 NoWhiteNoNSB8 BHC242-0 YesBlackNoNSB8 BHC243-0 NoBlackNoNSB8 MHC240-0 YesWhiteYesNSB8 MHC241-0 NoWhiteYesNSB8 MHC242-0 YesBlackYesNSB8 MHC243-0 Fixed segment displayNoBlackYesNSB8 BHC140-0 YesWhiteNoNSB8 BHC141-0 Warmer/Cooler interfaceNoWhiteNoNSB8 BHC340-0 YesWhiteNoNSB8 BHC341-0 Graphical user interfaceNoWhiteNo3NS8000 Series Network Sensors Catalog PageTable 2: NS Series Network Sensor ordering information.

8 Temperature and humidity models (3% RH)Product code numberDisplay and interface informationJohnson Controls logoColorPIR occupancy sensorNSB8 BHN240-0 YesWhiteNoNSB8 BHN241-0 NoWhiteNoNSB8 BHN242-0 YesBlackNoNSB8 BHN243-0 NoBlackNoNSB8 MHN240-0 YesWhiteYesNSB8 MHN241-0 NoWhiteYesNSB8 MHN242-0 YesBlackYesNSB8 MHN243-0 Fixed segment displayNoBlackYesNSB8 BHN040-0 YesWhiteNoNSB8 BHN041-0 NoWhiteNoNSB8 BHN042-0 YesBlackNoNSB8 BHN043-0 NoBlackNoNSB8 MHN040-0 YesWhiteYesNSB8 MHN041-0 NoWhiteYesNSB8 MHN042-0 YesBlackYesNSB8 MHN043-0No displayNoBlackYesNSB8 BHN140-0 YesWhiteNoNSB8 BHN141-0 NoWhiteNoNSB8 BHN142-0 YesBlackNoNSB8 BHN143-0 Warmer/Cooler interfaceNoBlackNoNSB8 BHN340-0 YesWhiteNoNSB8 BHN340-1 Graphical user interfaceNoWhiteNoTable 3: NS Series Network Sensor ordering information: temperature and CO2 modelsProduct code numberDisplay and interface informationJohnson ControlslogoColorPIR occupancy sensorNSB8 BTC040-0 YesWhiteNoNSB8 BTC041-0 NoWhiteNoNSB8 BTC042-0 YesBlackNoNSB8 BTC043-0 NoBlackNoNSB8 MTC040-0 YesWhiteYesNSB8 MTC041-0 NoWhiteYesNSB8 MTC042-0 YesBlackYesNSB8 MTC043-0No displayNoBlackYesNSB8 BTC240-0 YesWhiteNoNSB8 BTC241-0 NoWhiteNoNSB8 BTC242-0 YesBlackNoNSB8 BTC243-0 NoBlackNoNSB8 MTC240-0 YesWhiteYesNSB8 MTC241-0 NoWhiteYesNSB8 MTC242-0 YesBlackYesNSB8 MTC243-0 Fixed segment displayNoBlackYesNSB8 BTC340-0 YesWhiteNoNSB8 BTC340-1 Graphical user interfaceNoWhiteNo4NS8000 Series Network Sensors Catalog PageTable 4: NS Series Network Sensor ordering information.

9 Temperature only modelsProduct code numberDisplay and interface informationJohnson Controls logoColorPIR occupancy sensorNSB8 BTN240-0 YesWhiteNoNSB8 BTN241-0 NoWhiteNoNSB8 BTN242-0 YesBlackNoNSB8 BTN243-0 NoBlackNoNSB8 MTN240-0 YesWhiteYesNSB8 MTN241-0 NoWhiteYesNSB8 MTN242-0 YesBlackYesNSB8 MTN243-0 Fixed segment displayNoBlackYesNSB8 BTN040-0 YesWhiteNoNSB8 BTN041-0 NoWhiteNoNSB8 BTN042-0 YesBlackNoNSB8 BTN043-0 NoBlackNoNSB8 MTN040-0 YesWhiteYesNSB8 MTN041-0 NoWhiteYesNSB8 MTN042-0 YesBlackYesNSB8 MTN043-0No displayNoBlackYesNSB8 BTN140-0 YesWhiteNoNSB8 BTN141-0 NoWhiteNoNSB8 BTN142-0 YesBlackNoNSB8 BTN143-0 Warmer/Cooler interfaceNoBlackNoNSB8 BTN340-0 YesWhiteNoNSB8 BTN340-1 Graphical user interfaceNoWhiteNoTable 5: NS Series Network Sensor ordering information: CO2 only models without displayProduct code numberJohnson Controls logoColorNSB8 BNC040-0 YesWhiteNSB8 BNC041-0 NoWhiteNSB8 BNC042-0 YesBlackNSB8 BNC043-0 NoBlackTable 6: NS Series Network Sensor ordering information: temperature and humidity models (2% RH)Product code numberDisplay and interface informationJohnson Controls logoColorNSB8 BPN240-0 YesWhiteNSB8 BPN241-0 NoWhiteNSB8 BPN242-0 YesBlackNSB8 BPN243-0 Fixed segment displayNoBlackTable 7: AccessoriesProduct code numberDescriptionNS-WALLPLATE-0 Wall plates fit seamlessly around the NS8000 Sensor models and enable you to mount a sensorwhere a larger one was previously Series Network Sensors Catalog PageNS Sensors with fault code capability error codesThe fault indication comes through the Network sensor bus when a Network sensor is used in the zone.

10 TheLCD indicates the code number for all the required state of California Title 24 economizer fault textCalifornia Title 24 economizer faultconditionPossible problemE00 Air temperature sensor failure/faultProblem with one of the air temperature Sensors . Check outdoorair, return air, or supply air economizing when it shouldThe economizer is not using outdoor air when it when it should notThe economizer is allowing outdoor air inside when theconditions are not suitable for economizer not modulatingThe economizer damper is not able to modulate properly. Checkdamper, linkage to actuator, or the outdoor airThe economizer is allowing excess outdoor air specificationsTable 8: NS8000 Series Network Sensors technical specificationsSupply VDC to VDC; 15 VDC nominal (from SA bus)Screen off18 mA maximum (non-transmitting)Base currentdraw(graphicalmodels)Screen on45 mA maximumBase current draw (othermodels)3 mA maximum (non-transmitting)LCD graphical13 mA maximum additional current (during measurement)CO2 modelsOther models15 mA maximum additional current (during measurement)Fixed segment display models- backlight on10 mA additional currentWarmer/Cooler models - LEDson8 mA additional currentCurrent consumptionNote: The MAP gateway is connected to the SA bus.