381333 199 F50 Hanover Road, Florham Park, New Jersey 07932 1591 USA1 800 937 2726 (ASCO), for service call 1 800 800 2726 (ASCO) POWER TECHNOLOGIES CANADA PO Box 1238, 17 Airport Road, Brantford, Ontario, Canada N3T 5T3telephone 519 758 8450, fax 519 758 0876, for service call 1 888 234 2726 (ASCO) SERIESPOWERMANAGERXPO perator sManualCatalog 5220 DPower MANAGER Display, front view typical enclosure door view Catalog 5220D Power ManagerTransducer attached to the back of the 5220 TPower MANAGER Transducer only(withoutthe Display).

1--1 Introduction General Information The ASCO 5200 Series Power Manager Xp collects real–time power system information from ASCO Power Control Systems and 7000 Series Automatic Transfer Switch products (which utilize the Group 5 Controller).

Tags:

  Manual, Manager

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of Operator’s 5200 SERIES Manual P MANAGER XP - …

1 381333 199 F50 Hanover Road, Florham Park, New Jersey 07932 1591 USA1 800 937 2726 (ASCO), for service call 1 800 800 2726 (ASCO) POWER TECHNOLOGIES CANADA PO Box 1238, 17 Airport Road, Brantford, Ontario, Canada N3T 5T3telephone 519 758 8450, fax 519 758 0876, for service call 1 888 234 2726 (ASCO) SERIESPOWERMANAGERXPO perator sManualCatalog 5220 DPower MANAGER Display, front view typical enclosure door view Catalog 5220D Power ManagerTransducer attached to the back of the 5220 TPower MANAGER Transducer only(withoutthe Display).

2 Note:The 5200 SERIES Power MANAGER Xp is providedwith a 7000 SERIES 7 ASLS or 7 ASLB usually without thedisplay. Refer to the drawings provided with the OF CONTENTS section-pageINTRODUCTIONG eneral & Specifications1-3 & & Mounting SETUPP assword Type, Source, & Language 3-2 & , Voltage, & Current & CT Communication Interfaces 3-6 to 3 Energy Level & Reset Event Log Maximum Demand Demand Window 86 Setpoints & Reset Time Delay 3-16 & 3-17 Date & Time Log & Reset3-20 & Run Time Counter & THE POWER MANAGERO peration4-1 & ,burns,ordeath.

3 Deenergize all electricalsources before making anyconnections to the Power protection provided by the equipment may beimpaired if the Power MANAGER is used in a mannernotspecified by ASCO Power Technologies.!1--1 IntroductionGeneral InformationThe ASCO 5200 SeriesPower MANAGER Xpcollects real time power systeminformation from ASCO Power Control Systems and 7000 SERIES AutomaticTransfer Switch products (which utilize the Group 5 Controller). The PowerManager is available in two forms: Catalog 5220D (Accessory 85 on an ATS)Power MANAGER (Display and Transducer) for local data monitoring andcontrol; or Catalog 5220T (Accessory 75 on an ATS) Power ManagerTransducer without the display transmits data serially to a remote networkmanagement product for collection and MANAGER Xpincludes a backlit 4 line LCD display and membranecontrols.

4 All monitoring and control functions can be done from the front ofan enclosure for convenience and universal potential transformer inputs on the Power MANAGER canaccommodate the following three phase and single phase bus types: Three phase 4 wire WYE system Three phase 3 wire Delta system Single phase 3 wire system Single phase 2 wire systemMonitored & Calculated DataSet up parameters as well as the following computed parameters are avail-able both on the local display and through the serial interface.

5 Line to neutral voltages (VAN,VBN,VCN) Line to neutral voltage average (VAVE) Line to line voltages (VAB,VBC,VCA) Line to line voltage average (VLAVE) Current on each phase (IA,IB,IC) Current in the neutral conductor (IN) Average current (IAVE) Active power, KW per phase and total (WA,WB,WC,WT) Reactive power, KVAR per phase and total(VARA,VARB,VARC,VART) Apparent power, KVA per phase and total(VAA,VAB,VAC,VAT) Watt demand and maximum Watt demand KWHours importing, exporting and net(KWHIMP,KWHEXP,KWHNET) KVARH ours leading, lagging and net(KVARHLEAD, KVARHLAG, KVARHNET) KVAH ours net (KVAHNET) Powerfactor(PF) Signal frequency (Hz)

6 Twelve configurable setponts for Protective Relaying1--2 IntroductionSense Inputs 4 current inputs 3 voltage inputs frequency inputControl Inputs & Outputs transfer switch position input 8 status inputs 4relayoutputsCleaningThe exterior of the 5200 SeriesPower MANAGER Xpshould be cleaned by wipingthe front panel of the display unit with a soft cloth and cleaning agents that arenot alcohol based, and are nonflammable, nonexplosive. All other servicingshould be performed by authorized factory ConventionsThe following diagrams show how the 5200 SeriesPower MANAGER Xpinter-prets and displays signed (+, ) values for power, power factor and energyparameters.

7 Please note that the polarity of the Watts, VARs, Power Factor,energyimport/export, andlag/leadreadings canbe reversedbyreversingthepolarity of the CTs connected to the Power SpecificationsNOTE: The accuracy specifications are subject to ASCO Power Technologies for more : 25 C/77 FSFrequency : Hz or HzSCurrent input : 2 % < IFULL SCALE< 125 %SSensing type: True RMS up to and including the (fullscale)AccuracyDisplayParameter(full scale)Accuracy(% full scale)ResolutionRangeCurrent (I) % %0 299991 Voltage(V)120 % %0 599992 Voltage(V)600 % %0 599992 Active Power(KW)600 % %0 299993(KW)(per element)3000 % %0 299993 Reactive Power(KVAR)600 % %0 299993(KVAR)(per element)3000 % %0 299993 Apparent Power(KVA)600 % %0 299993(KVA)(per element)3000 % %0 299993 Active Energy (KWH)

8 % of % 1 999 999 999to + 1 999 999 999 Reactive Energy (KVARH) % of % 1 999 999 999to + 1 999 999 999 Apparent Energy (KVAH) % of %0 1 999 999 999 PowerFactor(PF) % PF to to +0,0 Frequency (Hz) % Hz40 to 100 HzNOTES:1 Reads in KA ( , KA) for currents over 9,999 in KV ( , KV) for voltages over 9,999 in MW, MVAR, MVA for readings over 9,999 equipment has been tested and found tocomply withthe limits for a Class Adigitaldevice, pursuant to part 15 of the FCC Rules. These limits are designed to providereasonable protection against harmful interference when the equipment is operated ina commercial environment.

9 This equipment generates, uses, and can radiate radiofrequency energy and, if not installed and used in accordance with the instructionmanual, may cause harmful interference to radio communications. Operation of thisequipment in a residential area is likely to cause harmful interference in which case theuser will be required to correct the interference at his own RatingsInput SignalsCurrent (4):0 to 5 A ac nominal. 4000 V ac isolation, : less than 2mV at 5 A ac input ( VA )Voltage (3):0 to 600 V ac nominal, three phase.

10 3750 V ac isolation : less than mA ac at 600 V ac input ( VA ).Frequency:40 Hz to 100 Hz RMS measurements up to and including the outputs (4):Form A dry contact,UL/CSA rated 1 A @ 30 V dc, A @ 125 V ac resistive loadStatus inputs (8):30 V dc maximum, >10 V dc = active, <1 V dc = inactivestatus input burden = 12 mA @ 24 V dcTransfer SwitchPosition input:30 V dc maximum, >10 V dc = active, <1 V dc = inactivePower Requirements: 24 V dc / A maximum / VAPower supply should be UL Risk of explosion if battery is replaced by an incorrect of used batteries according to local (s):Externaldisplay(J2) Class1DB25femaletypeSCI (J5) Class 2 DB9 female typeRS485 (J1) Isolated RS485 Communications interfaceOperating Temp.