TWIN FANSOPUS PLUSTECHNICAL INFORMATION029 2085 8200222 opus plus TWINFANSCOMPACT & POWERFUL, IDEAL FOR LARGER ROOM APPLICATIONSWHILST MAINTAINING LOW NOISE FANSOPUS PLUSTECHNICAL specification from filter & POWERFULS mall design, high performance up to 150I/s -ideal for larger room VENTILATION Twin fans allow for automatic changeover tostand by fan in event of fan failure. They alsofeature auto duty QUIET OPERATION Acoustically treated case and 'on board' speedcontrol offers high performance with low COMMISSIONING Both high and low speeds can be easily adjustedand set to the design LIFECYCLEFans automatically change over to standby every12 hours of run time, increasing units MAINTENANCE COST Easy clean filters protect motor and fan assembly, reducing maintenance costs and extending fan ATMOSPHEREMI nimum fan speed can easily be adjustedbetween 0% and 50% for co

twin fans opus plus technical information 222 029 2085 8200 opus plus twinfans compact & powerful, ideal for larger room applications whilst maintaining low noise levels.

Tags:

  Plus, Fans, Opus, Opus plus, Fans opus plus

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of OPUS PLUS TWINFANS - Nuaire

1 TWIN FANSOPUS PLUSTECHNICAL INFORMATION029 2085 8200222 opus plus TWINFANSCOMPACT & POWERFUL, IDEAL FOR LARGER ROOM APPLICATIONSWHILST MAINTAINING LOW NOISE FANSOPUS PLUSTECHNICAL specification from filter & POWERFULS mall design, high performance up to 150I/s -ideal for larger room VENTILATION Twin fans allow for automatic changeover tostand by fan in event of fan failure. They alsofeature auto duty QUIET OPERATION Acoustically treated case and 'on board' speedcontrol offers high performance with low COMMISSIONING Both high and low speeds can be easily adjustedand set to the design LIFECYCLEFans automatically change over to standby every12 hours of run time, increasing units MAINTENANCE COST Easy clean filters protect motor and fan assembly.

2 Reducing maintenance costs and extending fan ATMOSPHEREMI nimum fan speed can easily be adjustedbetween 0% and 50% for continuous backgroundventilation without wasting motor background ventilation to be A choice of 'on-board' and 'remote' controloptions are CONTROL INCLUDEDAll units has speed control included as standardto provide a packaged opus plus have a 3 year 908070 50 3060 Speed visual fault speed 2085 8200224 TWIN FANSOPUS PLUSTECHNICAL INFORMATIONPERFORMANCE - opus plus FANS204060801001204 VISO 5801 2007 Tested in ductFan Static Pressure (Pa)Air volume flow rate (l/s) opus 100 - Single and Twin fans 3200150100500012 Fan Static Pressure (Pa)Air volume flow rate (l/s)

3 opus 150 - Dual fans 4200150100500 20 40 60 80 100 120 140 160 01 VISO 5801 2007 Tested in duct230 100 200 300 400 0 m /hr 100 200 300 400 500 3 Code DescriptionsOPUS 100 - 2 B P|||||1234 51. opus - plus range2. Duty indication:100 = 100 l/s150 = 150 l/s3.

4 2 = Twin fanNo reference = Single Unit application:B = Surface mountedM = Duct mounted5. P = integral PIR. Option for surfacemounted models onlyNote: Speeds are 25-50% (1 & 2) 75-100% (3 & 4). Curves are for indication 150 - In event of fan failure, the second fan will continue to run. Performance will be as opus FANSOPUS PLUSTECHNICAL specification from & SOUND 100B/2B Surface Mounted SpeedInputSound Power Levels (dB re 1pW )ControlPowerFLC Octave band mid frequency (Hz)dBACurveFan CodeSetting(watts)amps1252505001K2K4K8K@ 3m1 OPUS10025% Surface Mounted1 OPUS15025% Surface Mounted 1 OPUS10025% Duct Mounted1 OPUS15025% electrical and sound information in the table is nominal.

5 Breakout dBA@3m is spherical, free - opus plus FANS029 2085 8200226 TWIN FANSOPUS PLUSTECHNICAL INFORMATIONDIMENSIONS - SURFACE MOUNTED opus plus UNITSWall Mounted opus PlusKey:1. LED Run and Fail Indicators2. Optional Fascia Cover Fixing Screws4. Fixing Points5. Cable AccessRear ViewEnd ViewView from Mounted opus PlusKey:1. 1 x 150 Dia. Spigot Knockout2. Cable Access3. Single Screw Unit Fixing4. 4 x 100 Dia. Spigot Knockouts5. Access Panel (full length of unit) ViewSide ViewAirflowTop ViewAirflow31NL2 NLUnit terminal blockFuse 2A maxLink for switched liveEarth postWire for full speed operation terminal blockFuse 2A maxEarth postWire for trickle vent/boost andtimed (mm) & WEIGHTSFan UnitABCDEW eight KgOPUS100-2M5003302602005011 OPUS150-M5003302602005011 DIMENSIONS - DUCT MOUNTED opus plus UNITSDIMENSIONS (mm)

6 & WEIGHTSFan UnitABCDEFGW eight KgOPUS100-2B160335320125501602485 OPUS100-B160335320125501602485 OPUS150-B160335320125501602485227 TWIN FANSOPUS PLUSTECHNICAL specification from extract fans shall be as indicated on the drawings and shall be in accordancewith the particular fan schedule in this specification. The vitiated air shall beextracted from each area via ductwork as shown. All necessary ductwork fittingsand ancillaries shall be allowed for by the mechanical sub extract fans shall be operated as it receives signals from one of theinterconnected sensors or an external signal light switch.

7 The opus plus shallhave the facility to increase speed on a trickle and boost principle FAN SPECIFICATIONThe fans are acoustically lined with high density class "O" flame retardantacoustic insulation, giving extremely low noise levels and shall be complete withan integral filter, integral controls and facia mounted run and fail indication. Thebreakout noise level and power requirements shall be in accordance with theschedule and the manufacturer s details. The fans shall have low energy, high efficiency fan/motor assembly with sealedfor life PLUSThe unit shall be supplied complete with automatic fan changeover in the eventof failure, sensed via a "hall effect" airflow sensor, and auto duty share every 12hours of run time.

8 DUCT MOUNTED The unit shall incorporate a low profile single point mounting bracket,incorporating a pre-stressed synthetic anti vibration seal. The bracket shall enablethe unit to be mounted horizontally or vertically. The depth of the unit shall notbe greater than 260mm. The unit shall be constructed with one removable panelallowing full maintenance access. To facilitate the interconnection of branchducts the unit shall have 4x100 dia & 1x 125 dia knockouts on the suction sideof the unit (spigots provided) and 1 x 200 dia discharge shall be the OPUS100- (2) M or the OPUS150-M as manufactured MOUNTED All fan components are manufactured from ABS polymer and pre-coated finish shall be to have the option of an integrated PIR detector to switch the unit fromtrickle or off to full speed.

9 Air inlet grilles are fitted with foam filters to protectthe fan/motor assembly from airborne dust and contaminants. The unit shallhave a 125dia spigot to connect to ductwork or wall mounting kit. Surfacemounted LED indicators shall show the unit operational unit shall be supplied complete with automatic fan changeover in the eventof failure, sensed via a "hall effect" airflow sensor, and auto duty share every 12hours of run versions shall have the following functions integrally mounted within the fanunit on a purpose made PCB, all such components pre-wired and factory fittedby the manufacturer: Integral adjustable background ventilation control/set point (0 50%).

10 Integral adjustable trickle ventilation control/set point (50 100%). Integral adjustable run on timer. Integral S/L terminal for boost trigger from remote switch, light switch. Volt free failure/status indication. 3 years manufacturers unit shall be controlled by one of the following remote options: opus SPD Low voltage (12V) speed control, ON/OFF and speed controlbetween min and max settings. 230-PIR - (passive infra-red) movement detector (includes run-on-timer), 2-30 mins). 230-PIRNT - (passive infra-red) movement detector (without run-on-timer). HUMISEN - Humidity sensor.