St CIRED 21 International Conference on Electricity Distribution Frankfurt, 6-9 June 2011. Paper 1137. SOLUTIONS FOR INTERNAL ARC PROTECTION ACC. IEC 62271-200 WITH. PRESSURE RELIEF INTO THE SWITCHGEAR ROOM FOR GAS AND AIR. INSULATED MEDIUM VOLTAGE SWITCHGEARS. Harethe El Ouadhane Mario Haim Helmut Spitzer Schneider Electric-Germany Schneider Electric-Germany Schneider Electric-Germany Dr. Uwe Kaltenborn Dr. Raimund Summer Schneider Electric-Germany Schneider Electric-Germany ABSTRACT tioned above is valid for the vicinity of the switchgear [4]. The described INTERNAL arc test procedure is defined with the INTERNAL Arc Classification (IAC) of medium voltage intention to verify the effectiveness of the design towards switchgear according to IEC and IEEE standards is one of the personal PROTECTION in the worst case of an INTERNAL arc.

C I R E DC I R E D 21st International Conference on Electricity Distribution Frankfurt, 6-9 June 2011 Paper 1137 Paper No 1137 3/5 2 v p 2 ∆ = ξ⋅ρ⋅ (1) with ξ being the empiric pressure loss coefficient, ρ the density of the gas and v the velocity of the gas.

Tags:

  Internal, Solutions, Protection, Paper, 1173, Paper 1137 solutions for internal arc protection

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of Paper 1137 - SOLUTIONS FOR INTERNAL ARC PROTECTION …

1 St CIRED 21 International Conference on Electricity Distribution Frankfurt, 6-9 June 2011. Paper 1137. SOLUTIONS FOR INTERNAL ARC PROTECTION ACC. IEC 62271-200 WITH. PRESSURE RELIEF INTO THE SWITCHGEAR ROOM FOR GAS AND AIR. INSULATED MEDIUM VOLTAGE SWITCHGEARS. Harethe El Ouadhane Mario Haim Helmut Spitzer Schneider Electric-Germany Schneider Electric-Germany Schneider Electric-Germany Dr. Uwe Kaltenborn Dr. Raimund Summer Schneider Electric-Germany Schneider Electric-Germany ABSTRACT tioned above is valid for the vicinity of the switchgear [4]. The described INTERNAL arc test procedure is defined with the INTERNAL Arc Classification (IAC) of medium voltage intention to verify the effectiveness of the design towards switchgear according to IEC and IEEE standards is one of the personal PROTECTION in the worst case of an INTERNAL arc.

2 The most important requirements to guarantee personal It takes into consideration the impact of the overpressure, safety in case of INTERNAL arc faults. During the last years the thermal effect of the arc and ejected hot gases [5]. IAC became a common standard for personal safety. One of It seems appropriate to mention first some crucial test crite- the challenges is the relief of the hot gases from the faulty ria according to IEC 62271-200: switchgear. The most common solution is the relief through Correctly secured doors and covers do not open. a pressure relief duct out of the switchgear building. For Deformations are accepted up to a clearly defined some applications like in the oil and gas industry or for degree (see IEC/IEEE).

3 Other critical industries and utilities more specific require- Projections of small parts, up to an individual mass ments have to be fulfilled. The pressure relief has to be of 60 g, are accepted. coordinated for the switchgear, the switchgear room and Arcing does not cause holes in the accessible areas the building. This Paper presents SOLUTIONS for GIS and AIS up to a height of 2 m. to fulfil IAC requirements. Cotton indicators, simulating the clothes of per- sons in the vicinity of the switchgear, shall not ig- INTRODUCTION nite from the effect of hot gases. INTERNAL arcs occurring in metal-enclosed MV-switchgear Service Continuity for process industries are high current fault arcs. These arcs are initiated by surges in power grids, insulation failures or human errors.

4 The topology of the switchboard has to allow for quick and On average one arc fault happens per 10,000 switchgear and short-term modifications of the network during service. This year. During such a rare event, a considerable amount of shall be possible without loss of operation. Modifications electrical energy up to 70 dissipated in the apparatus are required in case of grid disturbances or in case of ser- within a few 100 ms. The core temperature of the arc rises vice and maintenance. Power availability is often realized up to 30,000 K. The arc roots are able to melt through the by means of redundant assets. As redundancy is a major INTERNAL metallic enclosure of the switchgear within a few cost factor, the reliability of the installed equipment is of milliseconds.

5 In a distance of 1 m the power density of high importance. This target can be achieved by a suitable radiation still reaches 105 W/m , which is about 100 times design and quality of the installed switchgear and by the the value of normal solar radiation at the earth's surface. Up generic network structure with SOLUTIONS like the bus section to 70% of the supplied electrical energy will be dissipated in coupler and multi-bus-bar architectures. High quality the heating of the enclosed gas. This involves a significant switchgear should have a robust and partitioned design, increase of pressure inside the faulty compartment within a independent from environmental impacts like humidity, few ten milliseconds.

6 In GIS a pressure increase up to pollution and small animals [6]. MPa, for AIS up to MPa could be recorded. This In industries it is often a requirement, that an INTERNAL arc causes an expulsion of hot gases, flames and fumes with fault in one cell of the switchgear must not influence the temperatures up to 1000 K. Later on glowing or molten neighbouring cells. If the worst comes to the worst the in- particles of metal and insulation materials can be emitted. fluences should be acceptable for a conceivable period of time allowing further operation of the remaining parts of the Personal safety switchgear-installation. This time period should last at least The major target of the Standards as IEC 62271-200 [1], until the next scheduled maintenance event.

7 IEC 62271-202 [2] or IEEE [3] in consideration of INTERNAL arc fault is to ensure a minimum of PROTECTION for humans, operating personnel or pedestrians. This pro- tection from the perilous effects of the phenomena men- Paper No 1137 1/5. st CIRED 21 International Conference on Electricity Distribution Frankfurt, 6-9 June 2011. Paper 1137. RELEASE INTO THE ROOM nal arc test will be the practical and expensive proof. A non-rigid, completely closed switchgear-installation could The simplest and most common design to comply with the not withstand the pressure rise caused by an INTERNAL arc standards is to enclose the switchgear by a rigid contain- event. For this reason the pressure must be released.

8 As ment and attaching a duct, relieving the projected hot gases explained above there are detailed requirements for a re- and particles out of the switchgear room. These ducts are lease into the installation room. The major technical chal- specially designed add-ons to the switchgear. However this lenges are the significant reduction of the arcing effects: solution can cause a lot of non justifiable difficulties in pressure wave, ejected hot gases and glowing particles. This terms of installation costs, building configurations and com- can be achieved by using energy absorbers. For such a con- pliance with local building codes. Some customers, like cept thermal management at normal operation has to be O&G industries, have developed standardized buildings, taken into consideration.

9 The pressure relief concept should like switchgear containers or pre-fabricated switchgear not influence existing design criteria. buildings. Here the pressure relief concept must comply with these buildings, without influences to the industrial Concept for pressure relief inside the room surrounding. Arc energy absorbers - shortly named absorbers - consist Moreover, other customers such as Chemical and Automo- usually of layers of expanded metal in all sorts of arrange- tive Industries want to get an installation concept, where the ment. Other types of absorbers exist as well, consisting of switchgear room is environmentally independent. Also an ceramics with a high thermal conductivity.

10 Metal-absorbers exchange of accidental contamination of adjacent rooms has are in use since the beginning of the last century, but were to be strictly prevented. For such applications a solution really scientifically investigated only from the eighties. with release inside the switchgear room comes into consid- They are used in electrical installation in order to reduce eration. pressure and thermal stress in relief rooms and form also an Basic design strategies obstacle for effluent flames and glowing particles. Physi- cally speaking - absorbers have two main effects. First, they Basic design strategies of MV-switchgears can be defined absorb heat energy, hence the name and second, which is on the basis of the following objectives: more important, they constitute a resistance to the flow.