Transcription of PKG-DS-6 December 1998 Commercial Self …
1 Commercial self -ContainedAir ConditionersRemote Air-CooledCondensers20 Through 80 Ton - 60 HzSelf-Contained Signature SeriesPKG-DS- 6 pkg -DS-6 December 199822-inch flat filterbox inside unitcasingWaterside economizer(cleanable option shown)Sight glasses withports for viewingwhile unit is runningHinged and removable controlpanel door for easy accessUnit mountedmicroprocessor controlEnergy saving single fanwith inlet guide vanes orvariable frequency drivesInternally trappeddrain for low costinstallationWaterside valvepackage option toenhance systemefficiencyTwo-bolt connection on cleanablecondenser for quick, easymaintenanceTrane 3-D Scroll Compressorfor reliability, effiency andquiet operationAffordable self -Contained Value from TraneTrane s advanced technology brings unmatched reliability.
2 Highperformance and affordable cost3 Features and Benefits4 Application Considerations7 Selection Procedure12 Model Number Description14 General Data16 Performance Data20 Airside Pressure Drops20 Waterside Pressure Drops 26 Water-Cooled Units28 Air-Cooled Units56 Steam Coils64 Electrical Data65 Dimensional Data66 Service Clearances72 Weights74 Controls76 Options82 Mechanical Specifications86 Contents4 FeaturesandBenefits American Standard Inc. 1998 Why Consider self -ContainedFloor-by-Floor Systems?Improved Cash Management Factory installed options and testing:Reduces field labor and installation riskand improves system reliability Requires less sophisticatedmaintenance than built-up systemsTenant Satisfaction Complete HVAC system on each floorminimizes tenant inconvenience duringroutine maintenance Tenants can control system after hoursto increase productivity and minimizeexpenseLow First Cost Factory packaged controls and pipingreduce field labor.
3 Installation time andcost Installed tonnage can be reduced by 20percent taking advantage of buildingdiversity and VAV flexibility Flexible air discharge arrangement tomatch most building configurationsLower Installed Cost Single point power connection Single point water connection Factory commissioned and testedcontrols Factory installed options Internally trapped drain connectionEconomical Operation Free cooling year-round with watersideor airside economizer Floor-by-floor system results in energysavings since only air conditioners onfloors requiring cooling need to operate Annual system energy consumptioncomparable to central chilled watersystem but with significant energyconsumption reduction during partialoccupancy and after-hours Simple heating alternatives includeperimeter radiation and fan poweredVAV Integrated water valve control forenergy savings by pump unloadingAssured Acoustical Performance Flexible, horizontal discharge plenumprovides smooth airflow, reducing staticpressure losses for optimum acousticalperformance Multiple compressor design reducesacoustical levels.
4 Scroll compressordesign smooths gas flow for quieteroperationIAQ Features Sloped drain pan Stainless steel sloped drain pan(Optional) Internally trapped drain connection Double wall construction option Matt-faced fiberglass insulation High efficiency throwaway filters Easily cleanable evaporator,condensers and watersideeconomizers Filter access door for easy removalEnhanced Serviceability self -supporting removable panels Quick access service panel fasteners Eye level control/service center Refrigerant line sight glasses in viewduring operationIntegrated self -Contained Systems:Profitable, SimpleIntegrated Comfort System (ICS)Trane s Integrated Comfort systemimproves job profit and increases jobcontrol by combining Trane self -contained units and a Tracer buildingmanagement system.
5 This integratedsystem provides total building comfortand control. The primary motivation forbuilding owners/managers in makingthe purchasing decision of an HVAC controls system is no longer just savingenergy; it is having the ability toautomate their facilities and theconvenience of interface to The Comfort SystemAt Trane, we think new technology andinnovation should bring you morecapabilities, more flexibility and at thesame time be able to give youequipment and systems that are easierto use, easier to install, commission andservice. The self -contained IntegratedComfort system saves you time andmoney by simplifying system designand system installation.
6 When used withTrane s DDC/VAV boxes (VariTrane ),system balancing almost goes awaybecause each VAV box is commissionedand tested before it leaves the the status information and editingdata from the self -contained units, VAVboxes, lighting and other auxiliaryequipment are available from Tracer forcontrol, monitoring and service supportof your facility. Tracer, a family ofbuilding automation products fromTrane, is designed with robust,application specific software packagesto minimize custom programmingrequirements and enable system setupand control through simple editing ofparameters in the standard applicationssoftware. Should you select anIntegrated Comfort system for yourfacility, the accountability for equipment,automation and controls is Trane s!
7 Typical points available through TracerICS: Compressor on/off status Ventilation status Condenser water flow status Percent FLA supply fan Heat status Heat hours and starts Each compressor operating hours Each compressor starts Supply fan operating hours Supply fan starts Percent RLA of each compressor Supply air pressure Supply air temperature Suction temperature of each circuit Entering condenser water temperature Leaving condenser water temperature Supply air temperature reset signal Morning warmup sensor temperature Entering air temperature Entering economizer watertemperature Zone temperature5 FeaturesandBenefits Phenolic coated unit.
8 And/or evaporatorcoils Double wall construction Stainless steel sloped drain pan Medium efficiency throwaway filters Through-the-door non-fused disconnectswitchField Installed Accessories Airside economizer control with orwithout mixing box Programmable sensors with or withoutnight set back - CV and VAV ICS zone sensors used with Tracer system for zone control Ultra low leak dampers for 0-100percent modulating fresh aireconomizerFC Fans With Inlet Guide VanesTrane s forward-curved fans with inletguide vanes pre-rotate the air in thedirection of the fan wheel. Thisdecreases static pressure andhorsepower, essentially the unloadingcharacteristics of a Trane FC fan withinlet guide vanes result in superior partload Frequency Drives (VFD)Variable frequency drives are factoryinstalled, wired and tested to providesupply fan motor speed s, as compared to inlet guide vanes,are quieter, more efficient, and in someareas are eligible for utility rebates.
9 TheVFD s are available with and without abypass option. Bypass control willsimply provide full nominal airflowwhen manually placed in the bypassmode in the unlikely event of Features 20 through 80 ton industrial/commercialwater-cooled self -contained units 20 through 60 ton industrial/commercialair-cooled self -contained units Fully integrated, factory-installed/commissioned microelectronic controls Improved Trane 3-D scrollcompressors CV or VAV control Low ambient compressor lockoutcontrol input Coil frost protection on all units Morning warmup operation on all unitswith heating options Emergency stop input Occupied/unoccupied switching Timed override activation Refrigeration circuits that arecompletely factory piped and tested(water-cooled)
10 Factory piped and tested, mechanicallycleanable water-cooled condensers Two-bolt removable condenserwaterboxes for quick and easy cleaning Sloped drain pans ensure completecondensate removal for IAQ Internally trapped drain connection withcleanout Internally isolated centrifugal supply fan 14-gauge galvanized steel frameworkwith easily removable painted exteriorpanels of 18-gauge galvanized steel UL listing on standard options Fan belts and grease lines are easilyaccessible Access panels and clearance providedto clean both evaporator and watersideeconomizer coil finsOptional Features Fully integrated, factory-installed/commissioned variable frequency drivecontrol with or without optional bypass Fully integrated, factory-installed/commissioned inlet guide vanes on FCsupply fan Waterside economizer with factoryinstalled piping and controls Waterside modulating condensingpressure control valves on units withouta waterside economizer Removable cast iron headers oncleanable waterside economizer Flexible horizontal discharge with orwithout factory cut holes Heating Options.