Example: bankruptcy

PowerFlex 753 and PowerFlex 755 Pre-engineered FasTrac ...

Technical DataPowerFlex 753 and PowerFlex 755 Pre-engineered FasTrac Packaged DrivesCatalog Numbers 24F, 24 GSummary of ChangesThis publication contains new and updated information as indicated in the following picPageSummary of Changes1 Product Overview2 Catalog Number Explanation3 Specifications7 Options9 Drawings14 Maintenance14 Enclosure Information14 Mechanical Installation32 Electrical Installation34 Output Power Wiring38 Additional Resources41To picPageAdded Fahrenheit to NEMA / UL Type 12 ambient temperature design62 rockwell automation Publication 750-TD002E-EN-P - March 2018 PowerFlex 753 and PowerFlex 755 Pre-engineered FasTrac Packaged DrivesProduct OverviewRockwell automation PowerFlex 753 and 755 drives are now available in a Pre-engineered FasTrac Packaged Drive program.

Pre-engineered FasTrac program, you receive packaged PowerFlex 753 and 755 drives in as little as 20 business days. The Pre-engineered FasTrac program is a separate, centrally managed program. It combines the capabilities of Rockwell Automation low voltage drives with the Local Solution Centers.

Tags:

  Automation, Rockwell automation, Rockwell, Engineered, Powerflex, Powerflex 753

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of PowerFlex 753 and PowerFlex 755 Pre-engineered FasTrac ...

1 Technical DataPowerFlex 753 and PowerFlex 755 Pre-engineered FasTrac Packaged DrivesCatalog Numbers 24F, 24 GSummary of ChangesThis publication contains new and updated information as indicated in the following picPageSummary of Changes1 Product Overview2 Catalog Number Explanation3 Specifications7 Options9 Drawings14 Maintenance14 Enclosure Information14 Mechanical Installation32 Electrical Installation34 Output Power Wiring38 Additional Resources41To picPageAdded Fahrenheit to NEMA / UL Type 12 ambient temperature design62 rockwell automation Publication 750-TD002E-EN-P - March 2018 PowerFlex 753 and PowerFlex 755 Pre-engineered FasTrac Packaged DrivesProduct OverviewRockwell automation PowerFlex 753 and 755 drives are now available in a Pre-engineered FasTrac Packaged Drive program.

2 The Pre-engineered FasTrac Packaged Drives program provides PowerFlex 750-Series drives packaged with a much larger offering of factory-mounted options than what is normally available with a standard drive product. With the Pre-engineered FasTrac program, you receive packaged PowerFlex 753 and 755 drives in as little as 20 business Pre-engineered FasTrac program is a separate, centrally managed program. It combines the capabilities of rockwell automation low voltage drives with the Local Solution Centers. As orders are received, they are immediately released to a manufacturing location based on : A proven and tested design Quality drives and quick turnaround Pre-engineered packages to deliver sizing , wiring , and calculations Some ratings meet CSA requirements (contact rockwell automation for clarification).

3 Available only in Canada. Available in an assortment of environmental protection enclosures: NEMA 1, 12, 3R , or 4X (indoor and outdoor)This document contains information that is related to the rockwell automation PowerFlex 750-Series Pre-engineered FasTrac Packaged Drives program. The document is intended to provide drive catalog numbers, specifications, options and accessories, enclosures, and dimension information can be useful when specifying an application of a Pre-engineered FasTrac Packaged PowerFlex 750-Series AC drive. Be advised that this information is for reference only and subject to change at any automation Publication 750-TD002E-EN-P - March 20183 PowerFlex 753 and PowerFlex 755 Pre-engineered FasTrac Packaged DrivesCatalog Number ExplanationThe following catalog information is for PowerFlex 750-Series Drives Pre-engineered FasTrac packaged drives.

4 Contact your rockwell automation representative for product option rules. aDriveCodeType24 FPowerFlex 75324 GPowerFlex 755bInput TypeCodeType1AC & DC Input with PrechargeAAC Input w/ precharge, no DC terminalscEnclosure Type and Conformal CoatingCodeEnclosure RatingFrameEnclosureStyleConformalCoatin gINEMA 1 / IP20 1 Single driveYesANEMA 1 / driveYesJNEMA 12 / IP54 (fan and filter)1 Single driveYesHNEMA 12 / IP54 (fan and filter) driveYesSNEMA 3R / IP24 1 Single driveYesRNEMA 3R / driveYesX (indoor)NEMA 4X / IP66 (non-vented) driveYesC (outdoor)NEMA 4X / IP66 (fan and filter) driveYesdVersion and Voltage RatingCodeInput VoltageSource TypeDC PrechargeD480V AC3 PHNoE600V AC(1)(1)Only available in Canada.

5 3 PHNoeOutput amps, Hp ratings @ 480V AC InputCodeAmpsND HpHD HpFrame or or 25P05331 or 28P08551 or or or 2022221510 2027272015 3034342520 3040403025 3052524030 4065655040 4077776050 5096967560 5125125100756156156125100618618615012562 4824820015063023022502007361361300250741 541535030074774774007(1)(1) PowerFlex 755 5 6 ND- automation Publication 750-TD002E-EN-P - March 2018 PowerFlex 753 and PowerFlex 755 Pre-engineered FasTrac Packaged Drivese (cont d) Output amps, Hp ratings @ 600V AC Input(1)(1)600V AC rating is only available in Canada. CodeAmpsND HpHD HpFrame 3022222015 3027272520 4032323025 4041414030 5052525040 5063636050 6077777560 6099991007561251251251006144144150125619 2192200150724224225020072892893002507fFi ltering and Common Mode Capacitor ConfigurationCodeFilteringDefault CM Cap ConnectionAYesJumper removedJFiltered, CN jumper installedgDynamic BrakingCodeInternal ResistorInternal TransistorANoYesNNoNohHIMCodeVersion0No HIM - Blank plastic inserted (drive mounted)3 Full numeric LCD HIM (drive mounted)5 Programmer only LCD HIM (drive mounted)

6 6 Door mounted full numeric LCD HIM7 Door mounted Programmer only LCD HIMiCodeOptions-NDNormal duty-HDHeavy dutyInput Devices-P3 Circuit breaker-P4 Drive/Bypass mode circuit breaker-P6 Fused disconnect-P7 Drive/Bypass mode fused disconnectP13 Circuit breaker (65 kA)P14 Drive/Bypass mode circuit breaker (65 kA)Reactors-L1 Input reactor, 3%-L2 Output reactor, 3%-L3 Input reactor, 5%-L4 Output reactor, 5%Enclosure Options-H1 Lexan HIM cover (with a viewing window)-H2 Metallic HIM cover (solid door, no window)-E5 Enclosure space heaterLK1212 in. enclosure leg kitAvailable on frames 18 in. enclosure leg kit Available on Frames in. enclosure leg kitAvailable on Frames in. Plinth for frame 6 & 7, Frame 7with bypass and NEMA 1, 12, and 3R onlyPH4A4 in.

7 Plinth for frame 7only without bypass and NEMA 1, 12, and 3R onlyRockwell automation Publication 750-TD002E-EN-P - March 20185 PowerFlex 753 and PowerFlex 755 Pre-engineered FasTrac Packaged Drivesi (cont d)OptionsCodeOptionBypass-B0No bypass-B1 Manual bypassControl Power-C1 Drive only control power, 60 Hz onlyPower Filtering-F5 Transient voltage surge suppressorHFExternally mounted harmonic filterOperator Devices-S51 Hand/Off/Auto selector switch(start/stop/speed reference)-S59 WRun pilot light (white)-S59 GRun pilot light (green)-S59 RRun pilot light (red)-S60 RDrive fault pilot light (red)-S60 ADrive fault pilot light (amber)-S68 Speed potentiometer (1 Turn)-S53 Control power on pilot light (white)-S54 Drive and bypass mode pilot lights (amber)-S55 Local start/stop push buttons-S57 Drive reset push button-S66 Drive/Bypass (B1, if present) disable mushroom push button-S85 Local stop start push buttonsETM1 Elapse time meterETM2 Elapse time meteri (cont d)Control InterfacePS124V DC power supplyS56 Local / remote SEL SWSTOP owerFlex 750 Safe Torque Off cardS67 Motor high temp circuitS87 Motor high temp circuitJ4 Run relay with Aux that is wired to terms(8 A contacts)J42 Run relay with Aux that is wired to terms(8 A contacts)J2 FLT relay with Aux that is wired to terms(8 A contacts)J22 FLT relay with Aux that is wired to terms(8 A contacts)

8 RSEmergency stop circuit W/Safe Torque OffSIBSCADA interface I/O optionSIASCADA interface I/O optionAPApproval DrawingsFeedback-F0 None-F1 Standard encoderI/ONNone-IAStandard-IBStandardCom munication-MNNone-MDDeviceNet-MCControlN et (coax)-MFControlNet (fiber)-MSRS-485 DF1-MHRS-485 HVAC-MPPROFIBUS DPV1-MIINTERBUS-MEEtherNet/IP-MBBACnet/I P-MTDual-port EtherNet/IP6 rockwell automation Publication 750-TD002E-EN-P - March 2018 PowerFlex 753 and PowerFlex 755 Pre-engineered FasTrac Packaged DrivesAdditional Catalog Number NotesFor Position 6/c enclosure types, Pre-engineered FasTrac packaged drives are assembled in NEMA / UL Type 1, 12, 3R, or 4X (indoor) enclosures. Each enclosure type lends itself to a particular type of protection and environment.

9 The enclosures that are detailed here do not normally help protect electrical equipment from condensation, corrosion, or contamination. These conditions can occur within the enclosure or enter via the conduit or unsealed openings. Make adequate provisions to safeguard against such conditions to help protect equipment / UL Type 1 enclosures are intended for indoor use. Primarily, to provide a degree of protection against contact with the enclosed equipment in locations where unusual service conditions do not exist. The enclosures are designed to meet the rod entry and rust resistance design tests. Openings in the enclosure door or sides and/or fans on the doors or sides allow for free exchange of inside and outside air.

10 Design is based on C ( F) ambient temperature during operation. For 400 Hp ND/477 A drive, C ( F) ambient temperature during operation. See the PowerFlex 750-Series drive specifications for storage requirements. A = NEMA / UL Type 1 - with fans if needed (frames ) I = NEMA / UL Type 1 - with fans if needed (frame 1)NEMA / UL Type 12 enclosures are intended for indoor use primarily to provide a degree of protection against dust, dirt that is falling, and noncorrosive liquids that are dripping. They are designed to meet drip, dust, and rust resistance tests. There can be ventilation openings on the enclosure to allow free exchange of inside and outside air. Closed-loop auxiliary cooling can be required for higher horsepower ratings.


Related search queries