Example: bachelor of science

Pressure Regulator 133 / 233 - Peppas Ltd

1 Pressure Regulator133 / 233 Benefits Accurate regulation Exchangeable componenttechnique Easy maintenance Suitable for HTBrequirements DVGW-approval (DIN 3380/81,VP 200).DescriptionThe 133/233 Regulator is adirect-acting, spring loadedregulator with an integratedsafety shut-off lever system ensures exactoutlet Pressure , and fastresponse when the flow are designed forresidential and industrial use,such as industries, and heatingplants, as well as for allinstallations where accuratepressure control, easyadjustment and fast responsetimes are required, such as forburners, industrial ovens,boilers, Regulator 133 / 233 Technical features Inlet Pressure rangePi: bar Outlet Pressure rangePo: 10 mbar 0,7 bar Accuracy classAC5/10, SG10/20, AG10/5 Operating temperature -20 C to +60 C Ambient Temperature -30 C to +60 C Acceptable gases Natural gas, propane, butane, air, nitrogen and all non-corrosive gases.

1 Pressure Regulator 133 / 233 Benefits Accurate regulation Exchangeable component technique Easy maintenance Suitable for HTB requirements DVGW-approval (DIN 3380/81, VP 200). Description The 133/233 regulator is a direct-acting, spring loaded

Tags:

  Pressure, Regulators, Pressure regulator 133 233

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of Pressure Regulator 133 / 233 - Peppas Ltd

1 1 Pressure Regulator133 / 233 Benefits Accurate regulation Exchangeable componenttechnique Easy maintenance Suitable for HTBrequirements DVGW-approval (DIN 3380/81,VP 200).DescriptionThe 133/233 Regulator is adirect-acting, spring loadedregulator with an integratedsafety shut-off lever system ensures exactoutlet Pressure , and fastresponse when the flow are designed forresidential and industrial use,such as industries, and heatingplants, as well as for allinstallations where accuratepressure control, easyadjustment and fast responsetimes are required, such as forburners, industrial ovens,boilers, Regulator 133 / 233 Technical features Inlet Pressure rangePi: bar Outlet Pressure rangePo: 10 mbar 0,7 bar Accuracy classAC5/10, SG10/20, AG10/5 Operating temperature -20 C to +60 C Ambient Temperature -30 C to +60 C Acceptable gases Natural gas, propane, butane, air, nitrogen and all non-corrosive gases.

2 Safety devicesOptional built-in safety shut-off valve: OPSO: Over- Pressure shut-off (SSV-I, 033) UPSO: Under- Pressure shut-off (SSV-II) OptionsSafety diaphragmSafety Relief valveConnections SizesDN 25, DN 40 and DN 50 Dimensionssee table page 6 FlangesPN16 DIN, ANSI 150 ThreadG 3/4, G 1, G1 1/2 BodyGGG 40, DIN 1693 ActuatorGD-Al Si 12, DIN 1725 Body SSVB rassInternal partsBrass/Steel, zinc protected SealsNBR rubber/Viton DiaphragmNBR rubber/NBR rubber, reinforced fabric Construction2 Pressure Regulator133 / 233 The 133/233 regulators aredirect-acting, spring loadedregulators, which can be used for allnon-aggressive gases. The requiredoutlet Pressure can be easily set toanother command range byadjusting the command variable, orby exchanging the spring.

3 Due totheir spring principle, theseregulators operate independently oftheir positions. They offer variousinstallation possibilities as a resultof flange connections between theactuator body and the regulatingunit and, flange connectionsbetween the actuator body and theSSV switching device. The nozzle,regulating unit, and SSV switchingdevice, can be exchanged withoutremoving the actuator body from theregulated member. The safety shut-off valve is equippedwith a thermally working models with a leaking gasblow-off valve (SRV) have a fixedblow-off pressure1). The blow-off Pressure is,independently of the setting of theoutlet Pressure , approximately30 mbar above ventilation/blow-off line has to beconnected to the ventilationconnection of the Regulator .

4 Themodels with safety diaphragms arenot equipped with the SBV and theventilation/blow-off line. If theworking diaphragm is damaged, thesafety diaphragm prevents gas fromleaking in unacceptable amounts. 1) See accuracy class SRV page 8diaphragm compartmentfeeler (1)(diaphragm)ventilationconnectiondesir ed-value settingloaded springloaded spring (10)flange connectionflange connectionactuator bodyactuator (4,7)(exchangeable nozzles)valve diskmeasuring unitwith lever system (34)valve rodreset with cap(26,35)SSV withthermal shutoffclosing spring (14)lever system (3)with actuatorregulating unit bodydesign withleaking-gas blow-off valve SRV(8)(6)(5)ventilation connectionwith sievedesign withintegrated safetydiaphragm3 Pressure Regulator133 / 233 Technical Data and Type DesignationType 133, Pi - bar Pressure rateInlet Pressure PN - bar PN - bar Outlet pressure8 - 420 mbar Flow rate, up to 65 m3/h Natural gas Working temperature-20 bis +60 C Connection / Sizesee page 5 Type 233, Pi - bar Pressure rateInlet Pressure PN - bar PN - bar Outlet pressure8 - 700 mbar Flow rate, up to 400 m3/h Natural gas Working temperature-20 bis +60 C Connection / Sizesee page 5 Type 133, Pi > - bar Pressure rateInlet Pressure PN - bar Max.

5 Orifice- 3/16 ( ) Outlet pressure20 - 420 mbar Flow rate, up to 65 m3/h Natural gas Working temperature-20 bis +60 C External impulse Connection / Sizesee page 5 Designation of Regulator 133 and 2331for Pe - according VP 200,DIN 3380 / 81 with DVGW-Reg. No.,with t (HTB):- 31 without safety devices - 32 with SRV- 61 SSV Pso 400 mbar- 62 SSV Pso 400 mbar and SRV- 64 SSV Pso and Psu- 66 SSV Pso and Psu and SRV- 71 SSV Pso 450 mbar- 72 SSV Pso 450 mbar and SRV- 77 SSV Pso 450 mbar, SRV andgas loss protection, PN 1 (only 133) - 630 SSV Pso 400 mbar and safetydiaphragm, PN 1(133 and 233-8 /-12 )- 650 SSV Pso and Psu, as well assafety diaphragm, PN 1(133 and 233-8 /-12 )- 730 SSV Pso 450 mbar and safetydiaphragm, PN 1(133 and 233-8 /-12 ) - 770 SSV Pso 450 mbar, gas lossprotection and safety diaphragm,PN 1 (only Regulator 133)(1) select the diaphragm housing -8" or -12"(2) note the max.

6 Orifice- 4 Pressure Regulator133 / 233 Type 233, Pi > - bar Pressure rateInlet Pressure PN - bar Max. orifice- 3/8 (10mm) Outlet pressure20 - 700 mbar Flow rate, up to 400 m3/h Natural gas Working temperature-20 bis +60 C External impulse Connection / Sizesee page 5 Designation of Regulator 133 and 2331for Pe > - according DIN 3380 / 81with DVGW-Reg. No., without t :- 32 with SRV- 66 SSV pso and psu, as well as SRV(1) select the diaphragm housing -8" or -12"(2) note the max. orifice- Designation of Regulator 133 and 2331for Pi up to without DVGW-Reg N .- 31 without safety devices- 32 with SRV- 34 with gas loss protection- 36 with gas loss protectionand SRV- 61 SSV Pso- 62 SSV Pso and SRV- 64 SSV Pso and Psu- 66 SSV Pso and Psu and SRVType DesignationExample: Regulator type 233, Pressure stagePN 4, 12 diaphragm housing, SSV for upper shut off 450 mbar, withsafety relief valve (SRV).

7 (1) no digit for Pressure rate PN 1(2) no diaphragm housing sizefor type 133(3) Type 133 single pipe marked 133-EType 233 12 4 72 Type3 Diaphragm housing2 Pressure rate1 Safety shut-off valve (see table)BodyGGG 40, DIN 1693 Diaphragm housing GD-Al Si 12 DIN 1725 SSV-BodyBrass, hot pressedOrificeBrassDiaphragmNBR/NBR reinforcedO-ringsNBR/VitonValve disk regulatorAluminium/NBRV alve disk SSVB rass/NBRC onstruction5 Pressure Regulator133 / 233 Regulator variantsInstallationPlease indicate desired installatingposition when you order. If nototherwise stated, the regulators areassembled and adjusted for normal installation (position 2): Regulator 133-vent pointing outward, Regulator 233-vent pointing inward.

8 Type 133DN 25, PN 16 ANSI 150 Female threadMale threadDN 25, PN 16G 3/4 , G1 3/4 -, 1 -NPT3/4 -, 1 -BSPTG1 1/2 (140 mmlength)G1 1/2 (160 mmlength)DN 50, PN 16 ANSI 150DN 40, PN 16 ANSI 150 Female threadG1 1/2 , 1 1/2 NPT1 1/2 -BSPTSSVDN 25, 133-ESSVType 233-12 Type 233-8 Pos. 1 Pos. 2 Pos. 4*Pos. 6 Pos. 7 Pos. 8 Pos. 9 Pos. 10 Pos. 3*Pos. 5 Regulator 233-ventpointing outwardRegulator 233-ventpointing outward*) Pos. 3 and 4: Not to use for 233-8 (-12) -71/ -72/ -7306 Dimension, Type 133-ERL NRp 111041Rp 1-1/2 14050 Pressure Regulator133 / 233 Dimensions ModelThreadFlangeABC CDEFGHJKW eight in kgTypeSizeVentilation(approx.)(1)(2)Conn ection(1)(2)133-3/4 /1 DN 25 190 155100 16017010010075120Rp 3/47446233-121 1/2 DN 40 350 250150 20026515511575120Rp 11101115233-12-DN 50 350 250-20026515511575120Rp 1110-16233-81 1/2 DN 40 260 250150 20022012511575120Rp 1105913233-8-DN 50 260 250-20022012511575120Rp 1105-14JJ7 Pressure Regulator133 / 233 Command and adjustable rangeCommand ranges for Pressure SpringsRegulator TypeCommand rangePart marking9 15 mbar955-200-08red13314 20 mbar955-200-09bluewith gas loss18 26 mbar955-201-06silverprotection24 40 mbar955-202-98yellow38 53 mbar955-200-11orange8 16 mbar955-200-08red12 20 mbar955-200-09blue15 35 mbar955-200-10green13330 70 mbar955-200-11orange50 140

9 Mbar955-200-12black-white100 210 mbar955-200-83silver133 HP140 420 mbar955-200-84black8 16 mbar955-200-13red12 20 mbar955-200-14blue15 35 mbar955-200-15green233-1230 70 mbar955-200-16orange70 140 mbar955-200-17black100 210 mbar955-200-18metal blank30 70 mbar955-200-15green70 140 mbar955-200-16orange233-8140 300 mbar955-200-17black210 450 mbar955-200-18metal blank420 700 mbar955-200-69silver233-8 HP955-200-18metal blankAdjustable ranges for SSV, Type 033 for upper shut-offShut-offAdjustable rangePart markingUpper40 70 mbar955-200-22red(overpressure)50 150 mbar955-200-23bluePso140 450 mbar955-200-24greenAdjustable ranges SSV -I,-II for upper and lower shut-offShut-offAdjustable rangePart markingUpper20 60 mbar955-200-22red(overpressure)50 120 mbar955-200-23blue100 400 mbar955-200-24greenPso300 600 mbar955-200-52brown400 1000 mbar955-202-42silverLower8 50 mbar955-200-32red(underpressure) Psu8 Pressure Regulator133 / 233 Accuracy class and closing groupregulator (AC, SG):Outlet Pressure po:8 mbar - 20 mbar:AC 20 / SG 30>20 mbar - 50 mbar:AC 10 / SG 20> 50 mbar - 420 mbar:AC 5 / SG 10 Response closing group SSV:Upper response Pressure Pso,40 1000 mbar:AG 10 Lower response Pressure Psu,8 20 mbar:AG 30>20 50 mbar.

10 AG 10 Accuracy class SRV:(Po + approx. 30 mbar) 10% Pressure difference minimal,between outlet Pressure Po and SSV shut-off:SSV 033: 20 mbar between Po and PsoSSV II, lower: 14 mbar between Po and PsuSSV II, upper: 20 mbar between Po and PsoVentilation:Gas Pressure regulators without asafety diaphragm, and gas pressureregulators with an integrated safetyreliev valve (SRV), requireventilation and blow-off minimum diameters stipulatedby the DIN 3380 standards are DN order to ensure disturbance-freeregulation and a sufficiently quickresponse for load changes, thefollowing nominal widths andinstallation lengths have to beobserved:up to 3 m ventilation line: DN 20up to 5 m ventilation line: DN 25 For longer lengths, at least DN 40 DataInletOutlet PressurePressureOrifice InsertsPo (mbar)Pi (bar)Spring range / mm 10 mm 8 mm mm3 mmNo.


Related search queries