Product Data - Carrier

Product Data24 VNA9 Infinityr19 VSVariable Speed Air Conditionerwith PuronrRefrigerant1 --- 5 TonsThe Infinity 19VS air conditioner offers high--efficiency variablespeed performance in a remarkably small cabinet and provides upto 19 SEER cooling efficiency. The variable speed invertercapacity control delivers up to 5 stages of operation for exceptionalload matching, dehumidification and zoning Product has been designed and manufactured to provideflexible system matching and work with a wide variety of indoorunits and :Ratings contained in this document are subject tochange at any time. Always refer to the AHRI directory( ) for the most up--to--date LEADINGFEATURES / BENEFITSE nergy EfficiencySUp to 19 SEER / 13 EERSM icrotube Technologytrefrigeration systemSoundSSound level as low as 55 dBA in low speed (Silencer SystemII).SSoft start and smooth ramp to operating speedsComfortSVariable speed compressor operates at 5 stages with capacityrange from as wide as 25--100%SAir cooled Inverter variable speed drive System requires Infinity Touch Control with version 11software or newer for 5 stage operation on sizes 24 -- 60and version 12 or higher on size 13.

Variable Speed Air Conditioner with Puronr Refrigerant 1 --- 5 Tons The Infinity 19VS air conditioner offers high--efficiency variable speed performance in a remarkably small cabinet and provides up to 19 SEER cooling efficiency. The variable speed inverter capacity control delivers up to 5 stages of operation for exceptional

Tags:

  Refrigerant, Variable

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of Product Data - Carrier

1 Product Data24 VNA9 Infinityr19 VSVariable Speed Air Conditionerwith PuronrRefrigerant1 --- 5 TonsThe Infinity 19VS air conditioner offers high--efficiency variablespeed performance in a remarkably small cabinet and provides upto 19 SEER cooling efficiency. The variable speed invertercapacity control delivers up to 5 stages of operation for exceptionalload matching, dehumidification and zoning Product has been designed and manufactured to provideflexible system matching and work with a wide variety of indoorunits and :Ratings contained in this document are subject tochange at any time. Always refer to the AHRI directory( ) for the most up--to--date LEADINGFEATURES / BENEFITSE nergy EfficiencySUp to 19 SEER / 13 EERSM icrotube Technologytrefrigeration systemSoundSSound level as low as 55 dBA in low speed (Silencer SystemII).SSoft start and smooth ramp to operating speedsComfortSVariable speed compressor operates at 5 stages with capacityrange from as wide as 25--100%SAir cooled Inverter variable speed drive System requires Infinity Touch Control with version 11software or newer for 5 stage operation on sizes 24 -- 60and version 12 or higher on size 13.

2 Ratings provided with 2--stage thermostats and suitablenon--communicating indoor products for -- environmentally sound, won t deplete theozone layer and low lifetime service service valvesSInverter control drives compressor and fan motorSNo control module attached to fan motorSInfinity intelligence monitors critical system parametersSPressure equalizer valve for easy compressor startingSHigh pressure switchSSuction pressure transducerSCompressor discharge temperature sensorSSuction temperature sensorSFilter drier (field installed)SInternal crankcase heater standardFlexibility and installation:S2 control wires to outdoor unit in complete Infinity system andTouch ControlSEnergy Tracking capability with the Infinity Touch Control(Energy Tracking has the ability to monitor and estimate theenergy consumption of your Infinity system.)SSmaller and lighter than 2--stage unitsSMinimum and Maximum adjustments with Infinity TouchControlSCompatible with non--communicating thermostatsDurabilityWeatherArmor Ultratprotection package.

3 SSolid, Durable sheet metal constructionSSteel louver coil guardSBaked--on, complete outer coverage, powder paintApplicationsSLine sets up to 100 ft ( m) equivalent lengthSNo long--line accessories NUMBER NOMENCLATURE12 3456 78 910111213 NNAAA/NNNNA/NA/NA/NNN24 VNA9 36 A0030 ProductSeriesProductFamilyTierMajorSerie sSEERC oolingCapacityVariationsOpenOpenVoltageM inorSeries24=ACV=VSHPN=Infinity SeriesA = Puron9 = 19 SEER1,000 Btuh(nominal)A=StandardB=DesignVariation 0=NotDefined0=NotDefined3=208/230---1 0, 1, ModelsOnlySTANDARD FEATURESFEATURESUnit Size --- Voltage, Series1324B253637484960 Puron RefrigerantXXXXXXXXV ariable Speed Rotary CompressorXXXXXXXXAir---Cooled Integrated Inverter DriveXXXXXXXXL ouvered Coil GuardXXXXXXXXF ieldInstalledFilterDrierXXXXXXXXF ront Seating Service ValvesXXXXXXXXI nternal Pressure and Temperature ProtectionXXXXXXXXS uction Pressure TransducerXXXXXXXXHigh Pressure SwitchXXXXXXXXI nternal Crankcase HeaterXXXXXXXXE nhanced Diagnostics with Infinity Touch Control(version 11 software or newer for 5 stage operation on sizes 24 ---60 and version 12 or higher on size 13.)

4 XXXXXXXXD eluxe Sound BlanketXXXXXXXXO utdoor Air Temperature SensorXXXXXXXXX=StandardPHYSICAL DATAUNIT SIZESERIES13---3024B---3025---3136---313 7---3048---3049---3060---30 Compressor TypeVariable Speed RotaryREFRIGERANTP uron (R---410A)ControlTXV (Puron Hard Shutoff)Charge lb (kg) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( )COND FANF orward Swept Propeller Type, Direct DriveAir DischargeVerticalAir Qty (CFM)16002500250025004500450048004500 Motor HP1/51/51/31/31/31/31/31/3 Motor RPM65082510501050850850850900 COND COILFace Area (Sq ft) per ( )Vapor5/85/83/43/47/87/87/87/8 Liquid3/8 refrigerant TUBES (In. OD)Rated Vapor*3/43/47/87/81 --- 1/81 --- 1/81 --- 1/81 --- 1/8 Max Liquid Line3/8* Units are rated with 25 ft ( m) of lineset length. See Vapor Line Sizing and Cooling Capacity Loss table when using other sizes and lengths of : See unit Installation Instruction for proper PIPING LENGTH LIMITATIONSM aximum Line Lengths:The maximum allowable total equivalent length for air conditioners can vary depending on the vertical separation.

5 See the tables below forallowable lengths depending on whether the outdoor unit is on the same level, above or below the outdoor Line Lengths for Air Conditioner ApplicationsMAXIMUM ACTUAL LENGTHft (m)MAXIMUM EQUIVALENT LENGTH{ft (m)MAXIMUM VERTICAL SEPARA-TION ft (m)Units on equal level100 ( )100 ( )N/AOutdoor unit ABOVE indoor unit100 ( )100 ( )100 ( )Outdoor unit BELOW indoor unitSee Table Maximum Total Equivalent Length: Outdoor Unit BELOW Indoor Unit {Total equivalent length accounts for losses due to elbows or fitting. See the Long Line Guideline for Total Equivalent Length{-- Outdoor Unit BELOW Indoor UnitSizeLiquid LineDiameterw/ TXVAC with PuronrRefrigerant --- Maximum Total Equivalent Length{Vertical Separation ft (m) Outdoor unit BELOW indoor unit;0 --- 2 0(0 --- )21---30( --- )31---40( --- )41---50( --- )51---60( --- )61---70( --- )71---80( --- )1 --- Ton3/8100*100*100*100*100*100*100*2 --- Ton3/8100*100*100*100*100*100*100*3 --- Ton3/8100*100*100*100*100*100*100*4 --- Ton3/8100*100*100*100*100100--- ---5 --- Ton3/8100*100*100*100*100100--- ---* Maximum actual length not to exceed 100 ft ( m){Total equivalent length accounts for losses due to elbows or --- = o u t s i d e a c c e p t a b l e r a n g eLONG LINE APPLICATIONSUnit is approved for up to 100 ft ( m) equivalent length and vertical separations shown above with no additional line set applications are not CAPACITY LOSS TABLEN ominalSize(Btuh)Line OD (in.)}}}}}

6 24 VNA9 Cooling Capacity Loss (%)Total Equivalent Line Length (ft)25507580100135 Line Size inBOLD4 MIN/MAX AIRFLOW TABLESThe indoor airflow delivered by this system varies significantlybased on outdoor temperature, indoor unit combination, andsystem demand. The airflows on these tables are for duct designconsiderations. Duct systems capable of these ranges will ensurethe system will deliver full capacity at all outdoor and maximum airflows can be adjusted from thesenumbers in the Infinity Control Setup --- Comfort ModeMinimum Cooling(Dehum or Zoning)SizeMax Stage 5 AirflowMax Stage 1 Airflow1 --- Ton4203003002 --- Ton7393003003 --- Ton9903003004 --- Ton13895424575 --- Ton1600700600 Cooling --- Efficiency ModeSizeMax Stage 5 AirflowMax Stage 1 Airflow1 --- Ton4203002 --- Ton8255853 --- Ton10506004 --- Ton14008755 --- Ton1800975 Cooling Max ModeSizeMax Stage 5 AirflowMax Stage 1 Airflow1 --- Ton (550 cfm/ delivered ton)7804342 --- Ton (24)8505852---Ton (25) (550 cfm/ delivered ton)*13505103 --- Ton12006004 --- Ton16008754 --- Ton --- 4914508755 --- Ton2000975* Serial number beginning with 0115E and newerLEGEND::Max Capacity Airflow--- Stage 5 airflow varies depending on conditions.

7 This is the highest airflow the system will attempt to deliver in this particular for non---zoned systems should be sized for this airflow to ensure the system can deliver full capacity when needed. Improper duct design mayresultin excessive airflow noise and/or cutback occurrences at max airflow Min. Capacity Airflow--- Stage 1 airflow also varies depending on conditions. In zoned systems, each zone must be capable of delivering this airflowfor the system to deliver full capacity into the zone. Otherwise, airflow may be diverted to other zones or cutback may Cooling (Dehum or Zoning)--- Lowest airflow the system will deliver. May operate down to this airflow in dehumidification mode or in zoning applicationswhere ductwork restrictions have caused the blower to DATAUNITS I Z E ---VOLTAGE,SERIESV/PHOPER VOLTS*COMPRFANMCAMAXFUSE **orCKTBRKAMPSMAXMINLRARLAFLA13---30208- --230---1253197 * Permissible limits of the voltage range at which the unit will operate satisfactorily** Time --- Delay Full Load AmpsLRA--- Locked Rotor AmpsM C A ---Minimum Circuit AmpsRLA--- RatedLoadAmpsNOTE: Control circuit is 24---V on all units and requires external power source.

8 Copper wire must be used from service disconnect to motors/compressors contain internal overload with 2010 requirements of ASHRAE Standards SUBCOOLING (TXV--TYPE EXPANSION DEVICE)UNIT SIZE---VOLTAGE, SERIESIf a Touch Control is installed, subcooling recommendation displayed inCharging Mode must be followed. If not, subcooling chart shown on thecharging label must be followed13---3024B---3025---3136---3137- --3048---3049---3060---305 RPM--CAPACITY--SOUND (dBA)*STAGE #COMP RPMCAPACITY %SOUND (dBA)24 VNA9131150058%582186772%593210081%594235 090%5952600100%6024 VNA924B1150035%552256656%603315069%65439 5087%6654700100%6824 VNA9251120036%562190058%613240073%634260 079%6753300100%6924 VNA9361120025%562240050%613330069%654420 088%6954800100%7124 VNA9371120040%562180060%633220073%674260 087%6753000100%6824 VNA9481150035%622246057%653280065%674365 084%7054320100%7224 VNA9491120038%572184059%623230074%664270 087%6853120100%7324 VNA9601120032%572218055%613285070%644370 090%7054140100%72*Estimated sound for stages 2, 3, and 4 For 2---stage operation.

9 Low = Stage 2, High = Stage 56 SOUND POWER LEVEL (dBA)U n i t S i z e ---Voltage, SeriesTypical Octave BandSpectrum(without tone adjustment)Min SpeedCoolingMax SpeedCooling013---30 Freq (Hz)1500 RPM2600 Rating (dBA)5963024B---30 Freq (Hz)1500 RPM4700 Rating (dBA)5567025---31 Freq (Hz)1200 RPM3300 Rating (dBA)5569036---31 Freq (Hz)1200 RPM4800 Rating (dBA)5572037---30 Freq (Hz)1200 RPM3000 Rating (dBA)6069048---30 Freq (Hz)1500 RPM4320 Rating (dBA)647249---30 Freq (Hz) Rating (dBA) (Hz)1200 RPM4140 Rating (dBA)5772 NOTE: Tested in compliance with AHRI 270---1995 but not listed with NUMBERKIT NAME13---3024B---3025---3136---3137---30 48---3049---3060 KSASF0101 AAASPRT FEET KITXXXKSASF0201 AAASPRT FEET KITXXXXXKSATX0201 PURTXV KITXXXKSATX0301 PURTXV KITXXKSATX0401 PURTXV KITXXKSATX0501 PURTXV KITXKSBTX0201 PURTXV KITXXXKSBTX0301 PURTXV KITXXKSBTX0401 PURTXV KITXXLM10KK003 VAPOR LINE MUFFLERXXXXXXXXx = AccessoryAccessory Description and UsageSupport FeetRaises unit above base pad.

10 2 and 3 ton kit contains 5 feet for stable installation with small base. 4 and 5 ton kit contains 4 Guideline:Recommended for rooftop applicationsThermostatic Expansion Valve (TXV)A modulating flow--control valve which meters refrigerant liquid flow rate into the evaporator in response to the superheat of the refrigerantgas leaving the Guideline:Required if indoor unit does not already contain Puronrrefrigerant TXVV aporLineMufflerAn external muffler installed in the vapor line to minimize vibration transmitted through refrigerant linesUsage Guideline:Recommended if vapor line is not installed per recommendations in the installation instructions and vibration may be transmittedinto the Touch Control (non---Wi---Fi)(version 11 software or newer for 5 stage operation on sizes 24 --- 60 and version 12 or higher on size 13.)SYSTXCCITC01---AInfinity Touch Control (Wi---Fi)(version 11 software or newer for 5 stage operation on sizes 24 --- 60 and version 12 or higher on size 13.)