Product Guide UL 489 and UL 1077 DIN rail ... - Eaton

Product Guide UL 489 and UL 1077 DIN rail miniature circuit breakersiiEATON UL 489 and UL 1077 DIN rail miniature circuit breakersApplication guidelines for UL 489 circuit breakers and UL 1077 supplementary protec torsUL 489 circuit breakers Used for branch circuit protection, internal /external receptacles, external motors and HACR equipment (heating, air conditioning and refrigeration).UL 1077 supplementary protectors Used for overcurrent protection within appliances or electrical equipment, where branch circuit protection is already provided or not :NUL 489 devices can be used in place of UL 1077; UL 1077 devices cannot be used in place of UL ReceptacleUL 489 BreakerUL 489 BranchUL 1077UL 1077UL 1077UL 489 BranchUL 489 BranchUL 489 BranchExternal ReceptacleExternal Moto

Used for branch circuit protection, internal/external receptacles, external motors and HACR equipment (heating, air conditioning and refrigeration). UL 1077 supplementary protectors Used for overcurrent protection within appliances or electrical equipment, where branch circuit protection is already provided or not required.

Tags:

  Internal, Eaton, Circuit

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of Product Guide UL 489 and UL 1077 DIN rail ... - Eaton

1 Product Guide UL 489 and UL 1077 DIN rail miniature circuit breakersiiEATON UL 489 and UL 1077 DIN rail miniature circuit breakersApplication guidelines for UL 489 circuit breakers and UL 1077 supplementary protec torsUL 489 circuit breakers Used for branch circuit protection, internal /external receptacles, external motors and HACR equipment (heating, air conditioning and refrigeration).UL 1077 supplementary protectors Used for overcurrent protection within appliances or electrical equipment, where branch circuit protection is already provided or not :NUL 489 devices can be used in place of UL 1077.

2 UL 1077 devices cannot be used in place of UL ReceptacleUL 489 BreakerUL 489 BranchUL 1077UL 1077UL 1077UL 489 BranchUL 489 BranchUL 489 BranchExternal ReceptacleExternal MotorMMExternal MotorMotor ControllerOther Sensitive DevicesHACRE xample of UL 489 and UL 1077 Application1 Eaton UL 489 and UL 1077 DIN rail miniature circuit breakersUL 489 and UL 1077 DIN rail miniature circuit breakersUL 489 DIN rail branch circuit breakersProduct overview .. 2 Product selection480/277 VacFAZ-NA B curve (3 5X In current rating).

3 4 FAZ-NA C curve (5 10X In current rating) .. 5 FAZ-NA D curve (10 20X In current rating) .. 6240 VacFAZ-NA B curve (3 5X In current rating) .. 7 FAZ-NA C curve (5 10X In current rating) .. 8 FAZ-NA D curve (10 20X In current rating) .. 9125 VdcFAZ-NA-DC 10 kAIC at 125 Vdc per pole .. 10 Accessories .. 11 Technical data .. 13 Accessory technical data .. 17UL 1077 DIN rail supplementary protectorsProduct overview .. 20 Product selectionFAZ B curve (3 5X In current rating).

4 22 FAZ C curve (5 10X In current rating) .. 23 FAZ D curve (10 20X In current rating) .. 24 FAZ K curve (8 12X In current rating .. 25 FAZ S curve (13 17X In current rating) .. 26 FAZ Z curve (2 3X In current rating) .. 27 Accessories .. 30 Technical data .. 31 Accessory technical data .. 36 Miniature circuit breaker applicationFAZ circuit breakers .. 402UL 489 DIN rail branch circuit breakersFAZ-NA circuit breakersPRODUCT OVERVIEWEATON UL 489 and UL 1077 DIN rail miniature circuit breakersOptimum and efficient protectionOptimum Product quality, tested reliability and safety stand for best protection of personnel, installations and plant.)

5 Eaton s FAZ-NA DIN rail mountable circuit breaker is designed for use in branch service applications. Powerful offering for machine and system buildersThe FAZ-NA is available with B, C and D characteristics in accordance with UL 489, CSA ; UL 1077, CSA and IEC 60947-2. These devices are CE applicationsFeeder and branch circuit protection Convenience receptacle circuits ( internal /external) Motor control circuits Load circuits leaving the equipment (external) HACR equipment (heating, air conditioning, refrigeration) ( internal /external)

6 PLC I/O points Computers Power supplies Control instrumentation Relays UPS Power conditionersFeatures Complete range of UL 489 listed DIN rail mounted miniature circuit breakers up to 63 A current rating Standard ratings of 10 kAIC up to 277/480 Vac Select amperages available at 14 kAIC up to 277/480 Vac and 10 kAIC up to 125 Vdc per pole Current limiting design provides fast short- circuit interruption that reduces the let-through energy, which can damage the circuit Suitable for branch circuit device protection Thermal-magnetic overcurrent protection Three levels of short- circuit protection, categorized by B, C and D curves Single-, two-, three- and four-pole configurations available Trip-free design breaker can not be defeated by holding the handle in the ON position Captive screws cannot be lost SWD (switching duty) suitable for switching fluorescent lighting loads (In 20 A)

7 Fulfill UL 489, CSA and also IEC 60947-2 Standard For use in applications for which UL 1077 or CSA are also allowed Field installable shunt trip and auxiliary switch subsequent mounting Separate version for ring-tongue connection (Type FAZ-RT), terminal screws can be removed (on both sides) Module width of only mm (per pole) Contact Position Indicator (red/green) Easy installation on DIN rail Possibility for sealing the toggle in ON or OFF positionFAZ-NA complies with the latest national and international standardsStandards feeder and branch circuit protectionUL 489 Standard for molded case circuit breakers (MCCB) for feeder and branch circuit meet the requirements of the National Electrical Code (NEC ).

8 CSA for molded case circuit breakers (MCCB) for feeder and branch circuit protection (corresponds closely to UL 489 Standard).Products meet the requirements of the Canadian Electrical Code (CEC).RoHSThese devices are RoHS devices are VDE devices are ABS 489 DIN rail branch circuit breakersFAZ-NA circuit breakersProduct Overview3UL 489 DIN rail branch circuit breakersFAZ-NA circuit breakersPRODUCT OVERVIEWEATON UL 489 and UL 1077 DIN rail miniature circuit breakersTripping curves to choose fromEaton FAZ-NA branch circuit breakers are available with B, C and D tripping characteristics.

9 B-curve devices are suitable for applications where low levels of inrush current are devices are suitable for applications where medium levels of inrush current are expected. Applications include small transformers, lighting, pilot devices, control circuits and coils. C-curve devices provide a medium magnetic trip devices are suitable for applications where high levels of inrush current are expected. The high magnetic trip point prevents nuisance tripping in high inductive applications such as motors, transformers and power FAZ-NA devices are current limiting, which means they interrupt fault currents within one half cycle of the fault.

10 Current limiting devices offer superior protection by reducing peak let-through current and printing on front and sideInstallation optionsThese branch circuit breakers are available in two terminal configurations: standard box terminals that accept multiple conductors and ring-tongue terminals, ideally suited to demanding requirements of the semi-conductor industry. All breakers mount on standard 35 mm DIN rail. Bus connectors and feeder terminal facilitate mounting and wiring of multiple miniature circuit breaker arrays in control panel assemblies.