Quick Start Guide00825-0200-4410, Rev EAMay 2018 Emerson Wireless 1410 A/B and 1410D Gateway with 781 Field Page 1 Thursday, May 10, 2018 1:26 PMMay 20182 Quick Start GuideNOTICEThis guide provides basic guidelines for the Emerson Wireless 1410 and 1410D Gateway. It does not provide instructions for diagnostics, maintenance, service, or troubleshooting. Refer to the Emerson Wireless Gateway 1410 Reference Manual for more information and instructions. The manuals and this guide are available electronically on device complies with Part 15 of the FCC Rules. Operation is subject to the following conditions. This device may not cause harmful interference. This device must accept any interference received, including interference that may cause undesired operation. This device must be installed to ensure a minimum antenna separation distance of 20 cm from all hazard Do not make or break any connections to the Gateway while circuits are live unless area is known to be non-hazardous.

May 2018 2 Quick Start Guide NOTICE This guide provides basic guidelines for the Emerson Wireless 1410 and 1410D Gateway. It does not provide instructions for …

Tags:

  1041, Getaways

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of Quick Start Guide: Emerson Wireless 1410 A/B and 1410D ...

1 Quick Start Guide00825-0200-4410, Rev EAMay 2018 Emerson Wireless 1410 A/B and 1410D Gateway with 781 Field Page 1 Thursday, May 10, 2018 1:26 PMMay 20182 Quick Start GuideNOTICEThis guide provides basic guidelines for the Emerson Wireless 1410 and 1410D Gateway. It does not provide instructions for diagnostics, maintenance, service, or troubleshooting. Refer to the Emerson Wireless Gateway 1410 Reference Manual for more information and instructions. The manuals and this guide are available electronically on device complies with Part 15 of the FCC Rules. Operation is subject to the following conditions. This device may not cause harmful interference. This device must accept any interference received, including interference that may cause undesired operation. This device must be installed to ensure a minimum antenna separation distance of 20 cm from all hazard Do not make or break any connections to the Gateway while circuits are live unless area is known to be non-hazardous.

2 Explosions could result in death or serious injury. Installation of this device in an explosive environment must be in accordance with the appropriate local, national, and international standards, codes, and practices. Review the Product Certifications section for any restrictions associated with a safe installation. Avoid contact with the leads and terminals. High voltage that may be present on leads can cause electrical shock. Potential electrostatic charging hazard The Gateway enclosure is plastic. Use care in handling and cleaning when in explosive environments to avoid an electrostatic Wireless planning .. 3PC requirements .. 3 Initial connection and configuration .. 3 Physical installation .. 11 Software installation (optional) .. 20 Verify operations .. 21 Product Certification .. Page 2 Thursday, May 10, 2018 1:26 PMQuick Start Guide3 May up sequenceThe Gateway should be installed and functioning properly before power modules are installed in any Wireless field devices.

3 Wireless field devices should also be powered up in order of proximity from the Gateway beginning with the closest. This will result in a simpler and faster network positionThe antenna should be positioned vertically and be approximately 6 ft. (2 m) from large structures or buildings to allow for clear communication to other heightFor optimal Wireless coverage, the remote antenna is ideally mounted 15 25 ft. ( m) above ground or 6 ft. (2 m) above obstructions or major system (optional software only) Microsoft Windows Server 2008 (Standard Edition), Service Pack 2 Windows Server 2008 R2 Standard Edition, Service Pack 1 Windows 7 Professional, Service Pack 1 Windows 7 Enterprise, Service Pack 1 Windows 8 Enterprise, Service Pack 1 Windows 10 Enterprise, Service Pack of the Gateway is done through a secure web interface. Recent versions of the following browsers are supported: Internet Explorer Chrome browser Mozilla Firefox Microsoft Edge disk space AMS Wireless Configurator: GB Gateway Setup CD: 250 connection and configurationTo configure the Gateway, a local connection between a PC/Mac/laptop and the Gateway needs to be established.

4 The Emerson 1410 and 1410D are operationally equivalent and the following instructions are applicable to both models. Page 3 Thursday, May 10, 2018 1:26 PMMay 20184 Quick Start the GatewayFor both Emerson Wireless 1410A/B and the 1410D , bench top power will be needed to power the Gateway by wiring a 30 VDC (20 30 VDC if a 781 is connected with barriers to the Emerson 1410D ) power source, with a capacity of at least 250 mA to the power 1. Emerson 1410A/B Gateway Housing A. DIN Rail clipB. SMA to N type connectionC. Power light. During normal operation the power indicator will be green. D. Ethernet port 2. When this port is activated, the factory IP address is See Table 1 on page Ethernet port 1. Use for standard communication to the webserver or other protocols enabled on the Gateway. The factory IP address is See Table 1 on page 9. F. Emerson 1410 power and serial connection. Black terminal included in the box.+-A+B-24 VDC (nominal)Power Page 4 Thursday, May 10, 2018 1:26 PMQuick Start Guide5 May 2018 Figure 2.

5 Emerson 1410D Gateway Wiring A. DIN Rail ClipB. Power light. During normal operation the power indicator will be Ethernet port 2. When this port is activated, the factory IP address is See Table 1 on page Ethernet port 1. When this port is activated, the factory IP address is See Table 1 on page Emerson 1410 Power and Serial connections. Black terminal included in the Emerson Wireless 781 Field Link power and data connections. Black terminal included in Page 5 Thursday, May 10, 2018 1:26 PMMay 20186 Quick Start a connectionConnect the PC/laptop to the Ethernet 1 (Primary) receptacle on the Gateway using an Ethernet 71. Click the Internet Access icon on the bottom right of the 3. Internet Access2. Select the Network and Sharing Select Local Area Connection. Figure 4. Local Area Connection4. Select Page 6 Thursday, May 10, 2018 1:26 PMQuick Start Guide7 May 20185. Select Internet Protocol Version 4 (TCP/IPv4) then select 5. Internet Protocol Version 4 (TCP/IPv4)NoteIf the PC/laptop is from another network, record the current IP address and other settings so the PC/laptop can be returned to the original network after the Gateway has been Select the Use the following IP address 6.

6 IP Address7. In the IP address field, enter (DeltaV Ready enter ).8. In the Subnet mask field, enter Page 7 Thursday, May 10, 2018 1:26 PMMay 20188 Quick Start Guide9. Select OK for both the Internet Protocol (TCP/IP) Properties window and the Local Area Connection Properties 10 1. Select the network icon in the lower right Select the Network settings Select Ethernet on the left hand side of the Network Settings Page 8 Thursday, May 10, 2018 1:26 PMQuick Start Guide9 May 20184. Select Change adapter See steps 4-10 from Windows 7 to the Gateway's secondary Ethernet port will require different network settings. Disable proxies1. Open web Navigate Tools >I nternet Options > Connections > LAN Settings (may be a different process for other browsers).3. Under Proxy server, uncheck the Use a proxy 1. TCP/IP Network SettingsGateway PC/laptop/tabletSubnetEthernet Page 9 Thursday, May 10, 2018 1:26 PMMay 201810 Quick Start the GatewayTo complete initial configuration for the Gateway:1.

7 Access the default web page for the Gateway at Log on as Username: adminb. Type in password: default2. Navigate to System Settings > Gateway > Ethernet Communication to enter the Network Configure a static IP Address or set for DHCP and enter a Restart application at System Settings > Gateway > Backup and Restore > Restar t applications will temporarily disable communications with field Disconnect the power and Ethernet cable from the Page 10 Thursday, May 10, 2018 1:26 PMQuick Start Guide11 May 1410A/B and 1410D mountingThe unit can be snapped onto a DIN TS35 or TS35/15 rail system. To clip the unit onto the DIN rail, see Figure Tilt the unit at a slight angle allowing the lower lip of the chassis to catch the bottom of the DIN rail. 2. Apply pressure forward to snap the back of the unit securely onto the DIN 7. InstallingTo remove the unit, see Figure Place a flat or rounded object (such as a screw driver) into the DIN clip and apply a slight pressure downwards on the Once the unit is released from the DIN rail, pull backwards and down to successfully Page 11 Thursday, May 10, 2018 1:26 PMMay 201812 Quick Start GuideFigure 8.

8 RemovingNoteDo not mount the antenna within a metal enclosure. To avoid damage to sensitive RF components, do not remove protective cap from the Gateway SMA connector until ready to install the the Emerson 1410D with 781 There are two main connection configurations for the Emerson 1410D and 781: with and without barriers. The location and hazardous approval option of the Emerson 781 determines whether it needs to be installed with mounting the unit in an electrical enclosure or other location, comply with the appropriate local and national installation codes. Verify that the installer, associated hardware, and installation equipment used have the proper certifications for the specific type of installation being performed. Before installation, verify if local codes require a permit and/or an inspection before energizing. When planning the installation, account for routing the antenna cable within the Page 12 Thursday, May 10, 2018 1:26 PMQuick Start Guide13 May 2018 Installation without barriersA shielded twisted pair cable is needed for connecting the Emerson 1410D and 781 (refer to Figure 9).

9 The Emerson 781 can be located up to 656 ft. (200m) from the Emerson 1410D . Figure 9. Emerson 1410D and 781 without Barriers InstallationA. Emerson Wireless 1410D Gateway B. Attach shield pair cable (Belden 3084A or equivalent)C. Tape back shield wire and foilsD. Short these terminals to enable 250 terminating resistor E. Emerson Wireless 781 Field LinkData A (+)Data B (-)Return (-)24 VDC (+) line means internal Page 13 Thursday, May 10, 2018 1:26 PMMay 201814 Quick Start GuideInstallation with barriersWhen installing the Emerson 781 in a hazardous area there are two barriers that need to be installed: a power barrier and a signal barrier. The signal and the power are two separate circuits so they must comply with proper segregation distance. When using the Emerson recommended barriers the input power of the Gateway should be 20 30 VDC, with current capacity of at least 330 signal barrier needs additional power. You can wire it to the Emerson 1410D terminals or to a separate power supply.

10 Make sure power supply is rated to handle power drawn for the barrier. Figure 10 and Figure 11 show the two variations of powering the signal 10. Emerson 1410D and 781 with Gateway Powered Barrier Installation A. Emerson Wireless 1410D Gateway B. Attach shield pair cable (Belden 3084A)C. Tape back shield wire and foilsD. Short these terminals for 250 E. Emerson Wireless 781 Field LinkF. segregationG. ShieldB+-Data+Data - - + + -Power BarrierSignalBarrierRedBlkBluWht20-30 VDC20-30 VDCData+Data -Safe AreaARedBlkWhtBluGray line means internal connectionBluRedBlkCData A (+)Data B (-)Return (-)24 VDC (+)EWhtDHazardous Page 14 Thursday, May 10, 2018 1:26 PMQuick Start Guide15 May 2018 Figure 11. Emerson 1410D and 781 with Additional Power Supplied Barrier Installation RecommendationSignal barrier GM-International D1016 SPower barrier Stahl 9176 10-16-00A . E m e r s o n W i r e l e s s 1 4 1 0 D G a t e w a y B.