Transcription of Quik-Spec Coordination Panelboard - Data Sheet
1 0212 BU-SB11645 Page 1 of 11 data Sheet : 1171 Quik-Spec Coordination Panelboard - data Sheet600A - 1200A Fusible PanelboardsContentsSpecifications ..2 Enclosure Types and Voltages/Systems ..3 Main, Sub-Feed & Feed Through Lug Specifications ..4 Neutral and Ground Assemblies ..5 Typical Wiring ..6 Dimensions ..7-8 Replacement Parts ..9-10 Fuse & Disconnect Performance data ..11 Low-Peak CUBEFuse Fuse Specifications ..110212 BU-SB11645 Page 2 of 11 data Sheet : 1171 Catalog Symbol: QSCP12 Description:Fuseible panelboards for commercial/industrial branch or service entranceapplications on systems up through QSCP is specifically designed to address the NEC Selective CoordinationRequirements for Emergency, Legally Required Standby, Healthcare EssentialElectrical and Critical Operation Power Systems (COPS) per NEC , , and Not for applications requiring AFCI protected circuits.
2 The QSCP is configured to order for the application. To confirm availability of options and constructions, contact your Cooper Bussmann :Volts: 600 Vac (or less), 125 VdcAmps: 600, 800, 1200 ASCCR: 20kA or 100kA @125 Vdc - See Panelboard Short-Circuit Current Ratingstable for AC ratingsAgency Information: UL 67 Standard for panelboards UL 50/UL 50E Enclosures for electrical equipment CSA , No. 29-M1989 Panelboards and enclosed panelboards UL Listed, Class CTL Panelboard (meets 2002 NEC limit of42 overcurrent devices per panel) and Seismic Qualified, and ApprovedMain Options: Main Lug Only (MLO)Branch Disconnect Options: 1-, 2- and 3-Pole 15, 20, 30, 40, 50, 60, 70, 90, 100, 200, 400and 600A rejecting branch disconnects (see table for details).
3 Branch ampacity on 125 Vdc panels limited to CCPB 80A or Options: Unbonded & Bonded 600, 800, 1200, 1600 and 2400 AGround Options: Isolated & Non-isolatedEnclosures: NEMA 1 Spare Fuse Compartment: Standard on all modelsCCPB Horsepower Ratings:FFuusseeMMaaxxTTiimmee--DDeellaa yyTTiimmee--DDeellaayyFFaasstt--AAccttii nnggBranch* PartAmpCCPBNon-IndicatingIndicatingNon-I ndicatingNumberPolesRangeAmpacityFusesFu ses**FusesCCPB-1-15CF1 TCF1RN, TCF3RN,TCF6 FCF1RN, FCF3RN,CCPB-2-15CF21-1515 TCF6RN, TCF10RN,TCF10,FCF6RN, FCF10RN,CCPB-3-15CF3 TCF15 RNTCF15 FCF15 RNCCPB-1-20CF1 TCF17-1 2RN,TCF17-1 2,CCPB-2-20CF2171 2-2020 TCF20 RNTCF20 FCF20 CCPB-3-20CF3 CCPB-1-30CF1 TCF25RN,TCF25,FCF25RN,CCPB-2-30CF225-303 0 TCF30 RNTCF30 FCF30 RNCCPB-3-30CF3 CCPB-1-40CF1 TCF35RN,TCF35,FCF35RN.
4 CCPB-2-40CF235-4040 TCF40 RNTCF40 FCF40 RNCCPB-3-40CF3 CCPB-1-50CF1 TCF45RN,TCF45,FCF45RN,CCPB-2-50CF245-505 0 TCF50 RNTCF50 FCF50 RNCCPB-3-50CF3 CCPB-1-60CF1 CCPB-2-60CF26060 TCF60 RNTCF60 FCF60 RNCCPB-3-60CF3 CCPB-1-70CF1 CCPB-2-70CF27070 TCF70 RNTCF70 FCF70 RNCCPB-3-70CF3 CCPB-1-90CF1 TCF80 RNTCF80 FCF80 RNCCPB-2-90CF280-9090 TCF90 RNTCF90 FCF90 RNCCPB-3-90CF3 CCPB-1-100CF1 CCPB-2-100CF2100100 TCF100 RNTCF100 FCF100 RNCCPB-3-100CF3 LPJ-110SP, LPJ-125SP, LPJ-110 SPI, LPJ-125 SPI,JKS-110, JKS-125,CFD200J033**110-200200 LPJ-150SP, LPJ-175SP, LPJ-150 SPI, LPJ-175 SPI,JKS-150, JKS-175,LPJ-200 SPLPJ-200 SPIJKS-200 LPJ-225SP, LPJ-250SP, LPJ-225 SPI, LPJ-250 SPI,JKS-225, JKS-250,CFD400J033**225-400400 LPJ-300SP, LPJ-350SP, LPJ-300 SPI, LPJ-350 SPI,JKS-300, JKS-350,LPJ-400 SPLPJ-200 SPIJKS-400 LPJ-450SP, LPJ-500SP, LPJ-450 SPI, LPJ-500 SPI,JKS-450, JKS-500,CFD600J033**450-600600 LPJ-600 SPLPJ-600 SPIJKS-600*CCPB disconnect can accept CUBEF uses with amp ratings less than or equal to the amp rating of the CCPB disconnect.
5 **Correct fit with CCPB disconnect requires time-delay CUBEF uses with date code R38 or later.** 3-Pole switch used for 1 and 2-pole applicationsPanelboard Short-Circuit Current Ratings:AmpHp Rating @ VacCCPB DisconnectRating120240480600 CCPB-(Poles) (Poles) (Poles) (Poles) (Poles) (Poles) (Poles)-70CF703153040 CCPB-(Poles)-90CF805204050 CCPB-(Poles)-100CF1005205050 CFD200J03200 60125150 CFD400J03400 125250350 CFD600J03600 200400500 Branch Disconnects: Panelboard Short-Circuit Current RatingsAC Main OptionsDCMainMainLug OnlyLug OnlySCCR(MLO)*(MLO)* * For panelboards with subfeed main lugs, or panelboards withoptional feed-through lugs, Class J, T or R fuses are required upstream max amps = panel BU-SB11645 Page 3 of 11 data Sheet : 1171 Enclosure TypesNEMA 1 Floor mount Galvanized steel with blank end walls Box sizes.
6 27 W x 15 D x 65 / 38 W x 15 D x 65 or 89 H Enclosure and chassis mounting instructions are found in literaturesupplied with unit Chassis mounts directly onto studs in the enclosure Trim finished with gray powder coat paint over phosphatized steel (ANSI 61) Circuit directory card is located on the inside of the doorAC & DC Voltages & System TypesThree-PhaseSingle-PhaseBusingTin-pl ated copper with sufficient cross section to meet UL 67 temperature 1- & 3-Phase BusingAll CCPB branch disconnects can be mounted in any branch circuit , 3 Wire 120/240V 1-Phase, 3 Wire1-Phase, 2 Wire 120V 1-Phase, 2 Wire 240V 1-Phase, 2 Wire1-Phase, 2 Wire, Wye 277V 1-Phase, 2 Wire1-Phase, 2 Wire, Delta 480V 1-Phase, 2 Wire1-Phase, 3 Wire, Delta 240/480V 1-Phase, 3 Wire3-Phase, 4 Wire, Wye 208Y/120V 3-Phase.
7 4 Wire 480Y/277V 3-Phase, 4 Wire 600Y/347V 3-Phase, 4 Wire1-Phase, 3 Wire, Wye 208Y/120V 1-Phase, 3 Wire 480Y/277V 1-Phase, 3 Wire3-Phase, 4 Wire, Delta 240/120V 3-Phase, 4 Wire 480/240V 3-Phase, 4 Wire3-Phase, 3 Wire, Delta 240V 3-Phase, 3 Wire 480V 3-Phase, 3 Wire 600V 3-Phase, 3 Wire 240V 3-Phase, 3 Wire, Grounded B 480V 3-Phase, 3 Wire, Grounded B 600V 3-Phase, 3 Wire, Grounded BABNCABCANBCABNCABNCABCBNCADC Voltage1-Phase, 2 Wire 125 Vdc, 2 Wire(Up to 125 Vdc, MLO optiononly, CCPB 80A or less)AC VoltagesN+125 Vdc0212 BU-SB11645 Page 4 of 11 data Sheet : 1171 Main Sub-Feed Mechanical LugsWWiirree RRaannggee // TToorrqquuee LLbb--IInn ((NN mm)) 300kcmil - 6 AWG / 275 (31)WWiirree RRaattiinngg::60/75 C, Cu-AlMain Sub-Feed Mechanical LugsMain Barrier Cover OpenWWiirree RRaannggee // TToorrqquuee LLbb--IInn ((NN mm)) 600kcmil-2 AWG/375(42)WWiirree RRaattiinngg::60/75 C, Cu-AlMain Compression (Crimp) Lugs*WWiirree RRaannggee 300kcmil-4 AWGWW iirree RRaattiinngg.
8 60/75 C, Cu-AlMain Compression (Crimp) Lugs*Main Barrier Cover OpenWWiirree RRaannggee 600-250kcmilWWiirree RRaattiinngg::60/75 C, Cu-AlMain Mechanical LugsWWiirree RRaannggee // TToorrqquuee LLbb--IInn ((NN mm)) 300kcmil-1 AWG / 375 (42) 2-6 AWG / 275 (31)WWiirree RRaattiinngg::60/75 C, Cu-AlMain Mechanical LugsMain Barrier Cover OpenWWiirree RRaannggee // TToorrqquuee LLbb--IInn ((NN mm)) 600kcmil-4 AWG / 500 (56)WWiirree RRaattiinngg::60/75 C, Cu-Al800-1200 Amp Main Lugs600 Amp Main LugsFeed-Through LugsCompression, mechanical and double (sub-feed) lugs are allavailable as feed-through lugs.
9 Lug ampacity ratings will bebased upon Panelboard ampacity rating.* Versa-Crimp VC-6 crimp tool recommended for wire Mechanical LugsMain Sub-Feed Mechanical LugsMain Compression (Crimp) Lugs*0212 BU-SB11645 Page 5 of 11 data Sheet : 1171600A UnbondedWWiirree RRaannggee // TToorrqquuee LLbb--IInn ((NN mm)) Main Terminal 600kcmil-2 AWG / 275 (31) Branch Connections - See table belowWWiirree RRaattiinngg::60/75 C, Cu-AlBBaarr MMaatteerriiaall::Copper, Tin-platedLLuugg MMaatteerriiaall::Aluminum, Tin-plated 600A BondedWWiirree RRaannggee // TToorrqquuee LLbb--IInn ((NN mm)) Main Terminal 600kcmil-2 AWG / 275 (31) Branch Connections - See table belowWWiirree RRaattiinngg::60/75 C, Cu-AlBBaarr MMaatteerriiaall::Copper, Tin-platedLLuugg MMaatteerriiaall::Aluminum, Tin-plated Isolated / Non-isolatedWWiirree RRaannggee // TToorrqquuee LLbb--IInn ((NN mm)) Main Terminal 600kcmil-2 AWG / 275 (31) Branch Connections - See table belowWWiirree RRaattiinngg::60/75 C, Cu-AlBBaarr MMaatteerriiaall::Copper, Tin-platedLLuugg MMaatteerriiaall.
10 Aluminum, Tin-platedNeutral AssembliesGround AssembliesWWiirree** WWiirreess PPeerr OOppeenniinnggAAWWGGLLbb--IInn ((NN mm)) 110000AA BBrraanncchh14 AWG - 4 AWG20-35 ( )223 AWG - 2/0 AWG35-80 ( )11111100 -- 220000AA BBrraanncchh6 AWG - 1/0 AWG35-200 ( )222/0 AWG - 350 kcmil200-375 ( )11222255 -- 440000AA BBrraanncchh4 AWG - 3/0 AWG35-200 ( )224/0 AWG200 ( )11250 kcmil - 600 kcmil275-500 ( )11445500 -- 660000AA BBrraanncchh2 AWG - 3/0 AWG35-200 ( )224/0 AWG200 ( )11250 kcmil - 600 kcmil275-500 ( )11*60/75 C, and Neutral Bars Connection Wire Torques0212 BU-SB11645 Page 6 of 11 data Sheet : 1171 Single-Phase, 2 WireMain Lug OnlyNEUTRALGROUNDGROUNDNEUTRALMain Lug OnlySingle-Phase, 3 WireGROUNDT hree-Phase, 3 WireMa