R-410A ZS SERIES - UPGNET

R-410 AZS SERIES 6-1/2 - 12-1/2 Ton60 Hertz 518676-BIM-E-1210 TABLE OF CONTENTSG eneral .. 2 Installation .. 5 Preceding Installation .. 5 Limitations.. 6 Location .. 7 Rigging And Handling .. 7 Ductwork .. 15 Condensate Drain .. 16 Compressors .. 16 Filters .. 17 Power And Control Wiring .. 17 Optional Electric Heat .. 30 Optional Gas Heat .. 31 Options/Accessories .. 33 Optional Variable Air Volume (VAV) .. 34 Optional Hot Gas Bypass (HGBP) .. 36 Standard Economizer And Power Exhaust Set Point Adjustments.

518676-BIM-E-1210 2 Johnson Controls Unitary Products General UP ZS units are single package air conditioners with optional gas heating designed for outdoor installation on a rooftop or

Tags:

  Series, 410a, R 410a zs series

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of R-410A ZS SERIES - UPGNET

1 R-410 AZS SERIES 6-1/2 - 12-1/2 Ton60 Hertz 518676-BIM-E-1210 TABLE OF CONTENTSG eneral .. 2 Installation .. 5 Preceding Installation .. 5 Limitations.. 6 Location .. 7 Rigging And Handling .. 7 Ductwork .. 15 Condensate Drain .. 16 Compressors .. 16 Filters .. 17 Power And Control Wiring .. 17 Optional Electric Heat .. 30 Optional Gas Heat .. 31 Options/Accessories .. 33 Optional Variable Air Volume (VAV) .. 34 Optional Hot Gas Bypass (HGBP) .. 36 Standard Economizer And Power Exhaust Set Point Adjustments.

2 36 Airflow Performance.. 41 Air Balance .. 46 Checking Air Quantity .. 46 Operation .. 49 Cooling Sequence Of Operation .. 49No Outdoor Air Options .. 50 Cooling Operation Errors .. 52 Electric Heating Sequence Of Operations .. 53 Electric Heat Operation Errors .. 53 Gas Heating Sequence Of Operations .. 54 Ignition Control Board.. 54 Gas Heating Operation Errors .. 55 Start-Up (Cooling) .. 56 Start-Up (Gas Heat) .. 56 Checking Gas Heat Input .. 57 Charging The Unit .. 59 Troubleshooting .. 59 Unit Control Board Option Setup.

3 61 Option Byte Setup .. 61 Heat Delay Setup .. 61 LIST OF TABLES1 ZS-06 thru -12 Unit Limitations .. 72 Weights and Dimensions .. 83 ZS-06 thru -12 Unit Accessory Weights .. 94 ZS-06 thru -12 Unit Physical Dimensions .. 115 ZS-06 thru -12 Unit Clearances .. 116 Side Duct Dimensions .. 147 Control Wire Sizes .. 198 Electrical Data .. 209 ZS-06 thru -12 Physical Data .. 2810 Electric Heat Minimum Supply Air .. 3011 Gas Pipe Sizing - Capacity of Pipe .. 3112 Gas Heat Minimum Supply Air.

4 3213 Supply Air Limitations .. 3814 Altitude/Temperature Correction Factors .. 4015 Airflow Performance - Side Duct Application .. 4216 Airflow Performance - Bottom Duct Application .. 4417 RPM Selection .. 4518 Indoor Blower Specifications .. 4619 Power Exhaust Specifications .. 4620 Motor Sheave Datum Diameters .. 4821 Additional Static Resistance .. 4922 Electric Heat Limit Setting 50 Cabinet .. 5323 Electric Heat Limit Setting 42 Cabinet .. 5424 Electric Heat Anticipator Setpoints.

5 5425 Gas Heat Limit Control Settings .. 5526 Gas Heat Anticipator Setpoints .. 5627 Gas Rate Cubic Feet Per Hour .. 5828 Gas Heat Stages .. 5829 Unit Control Board Flash Codes .. 6030 Heat Delay .. 6231 Ignition Control Flash Codes .. 6232 VAV Control Board Flash Codes .. 62 LIST OF FIGURES1 Unit Shipping Bracket .. 52 Condenser Covering .. 53 Compressor Section .. 54 ZS Component Location (ZS-10 Shown) .. 65 Unit 4 Point Load Weight .. 86 Unit 6 Point Load Weight .. 87 Center of Gravity.

6 88 ZS-06 thru -10 .. 99 ZS-12 .. 1010 ZS-06 thru -12 Unit Bottom Duct Openings .. 1211 ZS-06 thru -12 Unit Electrical Entry .. 1312 ZS-06 thru -10 Unit Side Duct Openings .. 1313 ZS-12 Unit Side Duct Openings .. 1414 ZS-06 thru -12 Unit Left Duct Opening .. 1415 ZS-06 thru -12 Roof Curb .. 1516 ZS-06 thru -12 Transition Roof Curb .. 1517 Side Panels With Hole Plugs .. 1618 Return Downflow Plenum With Panel .. 1619 Discharge Panel In Place .. 1620 Condensate Drain .. 1621 Field Wiring Disconnect - Cooling Unit With/Without Electric Heat and All Units With VFD Option.

7 1822 Field Wiring Disconnect - Cooling Unit With Gas Heat Without VFD Option .. 1823 Typical Electronic Thermostat Field Wiring .. 1924 Typical Field Wiring 24 Volt Thermostat .. 1925 Side Entry Gas Piping .. 3126 Bottom Entry Gas Piping .. 3127 Simplified VFD Wiring .. 3628 Enthalpy Set Point Chart .. 3829 Honeywell Economizer Control W7212 .. 3830 Belt Adjustment .. 3931 Altitude/Temperature Correction Factors .. 4032 Dry Coil Delta P .. 4733 Occupied Jumper .. 5034 Typical Flame .. 5935 Typical Gas Valve.

8 5936 Unit Control Board .. 6137 Basic Troubleshooting Flowchart .. 6338 Power On Flow Chart .. 6339 Trip Failure Flow Chart .. 64518676-BIM-E-12102 Johnson Controls Unitary ProductsGeneralUP ZS units are single package air conditioners with optional gas heating designed for outdoor installation on a rooftop or slab and for non-residential use. These units can be equipped with factory or field installed electric heaters for heating units are completely assembled on rigid, permanently attached base rails. All piping, refrigerant charge, and electrical wiring is factory installed and tested.

9 The units require electric power, gas supply (where applicable), and duct connections. The electric heaters have nickel-chrome elements and utilize single-point power ConsiderationsThis is a safety alert symbol. When you see this symbol on labels or in manuals, be alert to the potential for personal is a safety alert symbol. When you see this symbol on labels or in manuals, be alert to the potential for personal and pay particular attention the signal words DANGER, WARNING or indicates an imminently hazardous situation, which, if not avoided, will result in death or serious indicates a potentially hazardous situation, which, if not avoided, could result in death or serious indicates a potentially hazardous situation, which, if not avoided may result in minor or moderate injury.

10 It is also used to alert against unsafe practices and hazards involving only property to system pressure, moving parts, and electrical components, installation and servicing of air conditioning equipment can be hazardous. Only qualified, trained service personnel should install, repair, or service this equipment. Untrained personnel can perform basic maintenance functions of cleaning coils and filters and replacing all precautions in the literature, labels, and tags accompanying the equipment whenever working on air conditioning equipment.