Raychem MV Outdoor Surge Arresters - Yakir …

Raychem MV Outdoor Surge 113/05/14 16:03 Raychem pioneered the developmentof polymeric housed Surge Arresters in the early 1980 s and since 1986 have a proven service experience across the globe, operating in the worlds toughest HDA Ethyl Vinyl Acetate (EVA) Surge arrestershave been designed and tested tomeet our customers toughest environ-mental conditions and to meet therequirements of IEC60099-4. The final HDA qualifications are performed by an independent laboratory in is the latest gapless, zinc oxidearrester family from the core of the Raychem HDAdesign is our improved ZnO varistordisk, which has superior thermal andelectrical characteristics and new varistor and HDA design combination results in superior energy handling and TOV crimped structural constructionoffers a light weight product withoptimal mechanical manufacturing process ensuresvoid free construction and optimuminterface sealing.

energy.te.com 2 TE Connectivity Raychem MV Surge Arresters Generic technical data HDA-xxMA series 3-24 kV Uc Rated discharge current (8/20µs) 10 kA

Tags:

  Surge, Surge arrester, Arrester, Mv surge arresters

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of Raychem MV Outdoor Surge Arresters - Yakir …

1 Raychem MV Outdoor Surge 113/05/14 16:03 Raychem pioneered the developmentof polymeric housed Surge Arresters in the early 1980 s and since 1986 have a proven service experience across the globe, operating in the worlds toughest HDA Ethyl Vinyl Acetate (EVA) Surge arrestershave been designed and tested tomeet our customers toughest environ-mental conditions and to meet therequirements of IEC60099-4. The final HDA qualifications are performed by an independent laboratory in is the latest gapless, zinc oxidearrester family from the core of the Raychem HDAdesign is our improved ZnO varistordisk, which has superior thermal andelectrical characteristics and new varistor and HDA design combination results in superior energy handling and TOV crimped structural constructionoffers a light weight product withoptimal mechanical manufacturing process ensuresvoid free construction and optimuminterface sealing.

2 This is achieved bybonding the EVA housing directlyto the ZnO discs and aluminiumfittings using a Raychem proprietarybonding of our new hydrophobicEVA HDA design are: Alternating sheds for superior pollution flash over resistance Superior TERT performance Constant voltage: , >360min - Stepped voltage: >300min - All eventual failures by erosion only, ie no tracking in step voltage test Housing tested to IEC 1000hr salt fog testExcellent hydrophobicitySafe non-shattering failure modeSuperior TERT performanceThe construction of the HDA design comprises of:1 ZnO, (Zinc Oxide) varistors 2 Raychem HDA proprietary EVA housing3 Flame retardant FRP structure4 Corrosion resistant aluminium fittings MV Outdoor Surge ArrestersBenefits Superior TOV performance Safe, non-shattering failure in the short circuit test by pre-failing to higher fault currents High energy handling capability Tested in accordance with IEC60099-4 Superior protection margins Direct molded housing to prevent moisture ingress Safe non-shattering short circuit behavior to higher current levels Maintenance free Hydrophobic EVA housing Excellent cantilever and tensile performance Excellent mechanical.

3 Vibration and impact withstand capability Quality design and manufacturing, ISO 9001 and 14001 213/05/14 16 ConnectivityRaychem MV Surge ArrestersGeneric technical data HDA-xxMA series 3-24 kV UcRated discharge current (8/20 s) 10 kALine discharge class according to IEC 60099-4 Class 1 Operating duty impulse withstand current (4/10 s) 100 kALong duration current impulse (2000 s) 400 A10 second temporary overvoltage, (UTOV/UC) current short circuit: (pre-failing method) 40 kA (Safe non-shattering failure mode) Energy 2 long duration impulses kJ/kV Uc 2 high current impulses kJ/kV UcService conditions Ambient temperature - 60 C to + 60 CSamples are pre-heated to a temperature of 60 C according to IEC 60099-4.

4 Samples were subjected to a pre-stress equivalent to one high current impulse of 100kA, 4/10 s as per switching Surge operating duty test. UTOV = TOV withstand voltage;UC = continuous operating voltageDischarge Class 1 Surge arrester HDA-MAApplicationProtection of MV networks and equipment from lightning and switching surgerelated over-voltages in areas with relatively high iso-keraunic levels. Suitablefor both Outdoor and indoor use to protect transformers and cable end (s)110000100010010 UTOV / UCTOV CurveTemporary overvoltage (TOV) of HDA-xxMA with prior 313/05/14 16:03 HDA-xxMA Standard housing parametersHDA-xxMA Sheds Impulse Power Flash Creepage Height Weight voltage frequency over length L (approx) s withstand distance voltage, wet (kV) (kV) (mm) (mm) (mm) (kg)

5 03 5 106 47 176 380 183 5 106 47 176 380 183 5 106 47 176 380 183 5 106 47 176 380 183 5 106 47 176 380 183 5 106 47 176 380 183 5 106 47 176 380 183 12 190 93 310 830 316 12 190 93 310 830 316 12 190 93 310 830 316 12 190 93 310 830 316 Extended housing parametersHDA-xxML Sheds Impulse Power Flash Creepage Height Weight voltage frequency over length L (approx) s withstand distance voltage, wet (kV) (kV) (mm) (mm) (mm) (kg)03 12 190 93 310 830 316 12 190 93 310 830 316 12 190 93 310 830 316 12 190 93 310 830 316 12 190 93 310 830 316 12 190 93 310 830 316 12 190 93 310 830 316 104 mmDia 123 mmTE ConnectivityRaychem MV Surge ArrestersDischarge Class 1 Surge arrester HDA-MANotes.

6 Mechnical strength data Cantilever Nm 350 Tensile kN 2 Torque Nm 50 For accessory and ordering information, please refer to page 6 HDA-MA Standard electrical dataHDA-xxMA U continuous U rated U residual in kV when tested to the following impulse waveforms kV( ) kV( ) Lightning Steep lightning Switching (8/20 s) (1/20 s) (30/60 s) 5kA 10kA 20kA 10kA 125A 500A03 3 4 5 6 8 10 2109 9 10 31 33 34 12 15 18 20 25 62 66 68 21 5524 24 30 59 : Continous Voltage; Ur: Rated Voltage.

7 Ures: Residual 413/05/14 16 ConnectivityRaychem MV Surge ArrestersGeneric technical dataHDA-xxM series 26-41 kV UcRated discharge current (8/20 s) 10 kALine discharge class according to IEC 60099-4 Class 1 Operating duty impulse withstand current (4/10 s) 100k ALong duration current impulse (2000 s) 400 A10 second temporary overvoltage, (UTOV/UC) current short circuit: (pre-failing method) 40 kA (Safe non-shattering failure mode) Energy 2 long duration impulses 4,2 kJ/kV Uc 2 high current impulses kJ/kV UcService conditions Ambient temperature - 60 C to + 60 CSamples are pre-heated to a temperature of 60 C according to IEC were subjected to a pre-stress equivalent to one high current impulse of 100kA, 4/10 s as per switching Surge operating duty test.

8 UTOV = TOV withstand voltage;UC = continuous operating (s)110000100010010 UTOV / UCTOV CurveTemporary overvoltage (TOV) of HDA-xxM with prior energyDischarge Class 1 Surge arrester HDA-MApplication:Protection of MV networks and equipment from lightning and switching surgerelated over-voltages in areas with relatively high iso-keraunic levels. Suitablefor both Outdoor and indoor use to protect transformers and cable end 513/05/14 16:03 LDia 107 mmDia 137 ConnectivityRaychem MV Surge ArrestersDischarge Class 1 Surge arrester HDA-MNotes: Mechnical strength data Cantilever Nm 250 Tensile kN 2 Torque Nm 50 For accessory and ordering information, please refer to page 6 HDA-xxM Standard housing parametersHDA-xxM Sheds Impulse Power Flash Creepage Height Weight voltage frequency over length L (approx) s withstand distance voltage, wet (kV) (kV) (mm) (mm) (mm) (kg)

9 26 11 204 98 339 970 343 427 11 204 98 339 970 343 429 11 204 98 339 970 343 430 11 204 98 339 970 343 431 13 228 110 378 1125 383 13 228 110 378 1125 383 13 228 110 378 1125 383 15 250 122 418 1279 423 540 15 250 122 418 1279 423 541 15 250 122 418 1279 423 5 HDA-xxML Extended housing parametersHDA-xxML Sheds Impulse Power Flash Creepage Height Weight voltage frequency over length L (approx) s withstand distance voltage, wet (kV) (kV) (mm) (mm) (mm) (kg)26 13 228 110 378 1125 383 13 228 110 378 1125 383 13 228 110 378 1125 383 15 250 122 418 1279 423 531 15 250 122 418 1279 423 533 15 250 122 418 1279 423 536 15 250 122 418 1279 423 5 HDA-M Standard electrical dataHDA-xxM U continuous U rated U residual in kV when tested to the following impulse waveforms kV( ) kV( ) Lightning Steep lightning Switching (8/20 s) (1/20 s) (30/60 s)

10 5kA 10kA 20kA 10kA 125A 500A26 26 64 27 29 7630 30 93 99 102 33 102 36 45 112 131 39 121 142 10240 40 50 124 132 136 10541 41 127 101 107Uc: Continous Voltage; Ur: Rated Voltage; Ures: Residual 613/05/14 16:03 Earth lead accessoriesx D xDisconnect & M accessoryx E xDisconnect & F accessoryx F xExposed stud for lug connectionx H xM12 cap screw & spring washerx L xExposed stud for 2 lug connectionx M xExposed stud for line lead connectionx N xNo stud. No accessoriesEbaaSystem Voltage Um ph/ph (a) ph/ground (b)12 185 16524 315 29536 510 490 Installation RequirementsAccessories for Class 1 Surge arrester (Type HDA)Example: HDA 12MA MEL Uc: 3, 4, 6, 8, 9, 10, 12, 18, 20, 21, 24, 26, 27, 29, 30, 33, 36, 40, 41 Housing creepage:M/MA = standard creepageML/LA = extended creepageAccessory selectionM = Mounting bracketE = Earth connectionL = Line connectionHDA series naming and order query ConnectivityRaychem MV Surge ArrestersHDA0 ABCA dditional accessory options available on request.