REACTV ariable-flow commissioning damperQUICK FACTS Damper for flow regulation Rapid access to readings via the controller display Simple to commission Can be easily anti-condensation insulated in the duct system A factory-insulated model is available for circular duct connection Circular connections: 100-630 mm Rectangular connections: 200x200-1600x700 Other rectangular sizes are also available on request Master/slave control has to have the same dimension Variants: Standard analogue signal Modbus control Spring return type motor F L O W R A N G EREACTMin.*Max. (nom.)Sizel/sm3/hl/sm3/h1005186222312593 3102367160165817663420025902801008250401 4 44561642315632277302628400102367120 0432050016459018506660630300108028921041 0*The minimum flow varies, see page 6 for more informationREACT2 Swegon reserves the right to alter speci cations. 20180705 ContentsTechnical description.

REACT Variable- ow commissioning damper QUICK FACTS Ù Damper for ow regulation Ù Rapid access to readings via the controller display Ù Simple to commission

Tags:

  Fact

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Advertisement

Transcription of REACT - Swegon

1 REACTV ariable-flow commissioning damperQUICK FACTS Damper for flow regulation Rapid access to readings via the controller display Simple to commission Can be easily anti-condensation insulated in the duct system A factory-insulated model is available for circular duct connection Circular connections: 100-630 mm Rectangular connections: 200x200-1600x700 Other rectangular sizes are also available on request Master/slave control has to have the same dimension Variants: Standard analogue signal Modbus control Spring return type motor F L O W R A N G EREACTMin.*Max. (nom.)Sizel/sm3/hl/sm3/h1005186222312593 3102367160165817663420025902801008250401 4 44561642315632277302628400102367120 0432050016459018506660630300108028921041 0*The minimum flow varies, see page 6 for more informationREACT2 Swegon reserves the right to alter speci cations. 20180705 ContentsTechnical description.

2 3 Design ..3 Features ..3 Materials and surface treatment ..3 Accessories ..3 Commissioning and maintenance ..3 Environment ..3 Planning ..4 General ..4 Control ..4 Electrical data ..4 Control Example ..4 Slave control - Example ..4 Installation ..5 Installation circular version ..5 Installation rectangular version ..5 Technical data ..6 Air flows all versions ..6 Measurement accuracy all versions ..6 Sound data circular version ..6 Air flows circular version ..6 Sound power in octave bands ..6 Transmitted sound through uninsulated casing ..6 Transmitted sound through insulated casing - IR ..6 Engineering graphs Circular, all versions ..7 Air flows and measures rectangular version ..9 Engineering graphs rectangular version ..9 Dimensions and weights ..10 Ordering key ..12 Product designation ..12 Accessories ..12 Specification example.

3 12320180705 Swegon reserves the right to alter speci 3. REACT CU, for slave control of REACT 0-10 V 4. Accessories. 1. RTC room thermostat. 2. DETECT Quality carbon dioxide- and temperature sensor. 3. DETECT Occupancy occupancy 1. REACT , circular and rectangular 2. REACT , rectangular design. Explanations of figure 2:1. Mode Edit wheel. 3. Gear release button. Technical descriptionDesign Variable-flow commissioning damper with control and measure-ment function Equipped with a compact regulator (motor included). REACT and REACT MB with compact controller. REACT GUAC with spring return actuator and separate controller. The controller has a display enabling direct reading. Easy commissioning and handling without the need for a sepa-rate hand unit. All you need is screw driver. Available in the following designs: Circular version Rectangular version With Modbus With spring return actuatorFeatures Intended for heated spaces (0 - 50 C).

4 Storage and transportation, -20 - 50 C Ductwork Leakage Classes in accordance with SS-EN 1751 Leakage class C to the surroundings. Circular version: class 4, closed damper Rectangular version: class 3, closed damper Air flow is measured over one or more measuring rods. All settings are displayd in actual values. Changes of min. and max flows are made directly in the control-ler through potentiometers. Distance inbetween the motor shelf and the damper (30 mm) is dimensioned for easy condensation isolation in duct systems. Running time open/close (90 degrees): 5 Nm - 100 s 10 Nm - 150 s 15 Nm - 150 s Spring return actuator, running time electricity: 5 Nm - 100 s 10 Nm - 150 s Running time spring max 20 s (90 degrees)Materials and surface treatment All sheet metal parts are made of galvanised sheet steel. Measurement rods are of extruded RTC Room thermostat for temperature control of a room, (connects to the REACT regulator).

5 DETECT Quality Carbon dioxide sensor with integrated tempera-ture sensor, for either room or duct installation. DETECT Occupancy Presence detector for switching to mini-mum air flow when a room is unoccupied or two-flow control min-max. REACT CU Sensor unit for slave control of one or more REACT units. 0-10 V signal only. FSR Clamp/quick fit connector for simple dismantling when cleaning a circular and maintenanceSee the separate commissioning of construction materials is available from 123227 VMMade in Germany24 VAC/DC 50/60 +50 C IP 42 Edit10 VnomFlowVminVmaxTestModeAdrDo notopenI/sTe stm /h31234 VnomFlowVminVmaxTestModeAdrI/sTe stm /h3 REACT4 Swegon reserves the right to alter speci cations. 20180705 PlanningGeneral Designed for demand-controlled ventilation in rooms with variable loads. Intended for comfort ventilation.

6 Humid, cold or aggressive environments should be avoided. Environmental and/or air temperatures should be within 0 - 50 C. Can be installed in both supply and extraxt air systems. Pressure-independent but requires a minimum air flow equivalent to the open damper pressure drop to fun-ction properly. Factory calibrated with a nominal air flow (Qnom) When carrying out design work, the minimum air flow required by REACT has to be taken in to Controlled by heat, carbon dioxide or occupancy. The factory setting is always 0-100% = 0 l/s Qnom. Can be forced controlled to: maximum and minimum air flow. fully open or fully closed damper When used for slave control, slave and master units must be of the same dimension. Can be used as a constant flow damper. (Qmax= 0 and Qmin = desired constant flow) Delivered with 0 - 10V set value and actual value signal.

7 Adjustable to 2 - 10V set value and actual value signal. REACT can be analogically connected to Building Management Systems (BMS) Possible to obtain with Modbus control Possibility to obtain REACT with spring return dataNOTE: To obtain the correct functionality of the control and regulating equipment it is of great importance that all interconnected regulating equipment has the same voltage24 VDC/24 VAC , 50-60 HzPower consumption, for transformer rating: REACT 5 W4 VAREACT 10 Nm2,5 W4,5 VAREACT 15 Nm3 W4,5 VAGUAC DM3 controller0,6 W1,3 VASpring return actuator 5 Nm6,5 W (standby 2 W)7, 5 VASpring return actuator 10 Nm5 W (standby 2 W)8 VAFigure 5. Air flow control with temperature sensor or CO2 sensor (supply and extract air controlled in parallell by the temperature sensor).Figure 6. Individual room control with overflow air. Extract air is slave controlled by the total supply air ExampleBelow, a couple of examples are shown of how REACT can work in a demand-controlled ventilation system.

8 When regulation via a CO2 sensor is chosen, the room thermostat is excluded as DETECT Q has an integrated temperature sensor that combines its output with the value from the CO2 sensor. The greatest signal from DETECT Q is sent to REACT to regulate the air flow. With the help of the presence detector DETECT O, the 0-10 V signal can be susopended so that the REACT unit regulates down to a minimum air flow when a room is unoccupied. DETECT O can also be connected so that REACT shuts down control - ExampleA REACT unit can be slave controlled from another REACT or from REACT CU. Slave control can also be achieved by parallel connection, by connecting the room thermostat signal to both the extract and supply air units. Parallel connection is recommended because the control signals are sent to both units at the same time and air flow can be freely set within the working range of REACT .

9 Slave control is limited as the slave unit cannot have a greater air flow than the master unit and because lower flows can only be obtained as a percentage of the master unit air flow. In systems with REACT CU as sensor unit, the slave control principle is always CUREACTREACTRRKMBFKMBFBFBFMKKL egend to figures 5-6:R = RTC or DETECT Q M = DamperK = Controller BF = Flow sensor520180705 Swegon reserves the right to alter speci measurements circular versionSizeA (mm)Inst. measurements (A + 10 mm)1004724821254724821604724822004724822 50522532315552562400695705500*822842630* 120 01220*Size 500, 630 has installation dimension A+20 8. REACT requires a duct of ~2 x D between the VAR and a sound attenuator fitted with Air flow measuring of REACT requires a straight section of duct before the unit (in air flow direction), according to installation figures.

10 Assembly instructions are included with the product on delivery but can also be downloaded from circular versionLegend to figures 7-9:1. Circular Variable-flow damper REACT2. Clamp, FSR3. Sound attenuator with baffleFigure 7. Straight section requirements, circular 9. Installation in a duct system. The ducts must be firmly fixed to the frame of the building on each side of the REACT rectangular versionMeasurement B in the figure and table below can be found on page 9, in the table; "Air flows and measures rec-tangular version". Straight sections before REACT for rectangular ducts Type of obstructionE (m2=5%)E (m2=10%)One 90 -bendE = 3 x BE = 2 x BOne T-pieceE = 3 x BE = 2 x BFigure 10. Straight section requirements, rectangular 11. Straight section requirements, rectangular REACT and sound attenuator with baffles. Installation with a length of straight duct applies to both the supply air and the extract air.