Example: bachelor of science

Recommended ABMA & ASME Boiler Water Limits Boiler …

Recommended ABMA & asme Boiler Water Limits Boiler Water Treatment Products Recommended ABMADRUM. & asme Boiler . OPERATING PRESSUREWATER. (psig) Limits *. 0-300 301-450 451-600 601-750 751-900 901-1000 1001-1500 1501-2000. STEAM. TDS max (ppm) Boiler Water . TDS max (ppm) 700-3500 600-3000 500-2500 200-1000 150-750 125-625 100 50. ALK max (ppm) 350 300 250 200 150 100 Not specified Not specified TSS Max (ppm) 15 10 8 3 2 1 1 n/a conductivity max ( mho/cm) 1100-5400 900-4600 800-3800 300-1500 200-1200 200-1000 150 80. Silica max (ppm Si02) 150 90 40 30 20 8 2 1. FEEDWATER (CONDENSATE & MAKEUP, AFTER DEAERATOR).

Conductivity max (µmho/cm) Silica max (ppm Si0 2) 700-3500 350 15 1100-5400 150 600-3000 300 10 900-4600 90 500-2500 250 8 ... 200-1000 8 100 Not specified 1 150 2 50 Not specified n / a 80 1 FEEDWATER (CONDENSATE & MAKEUP, AFTER DEAERATOR) Dissolved Oxygen (ppm 0 2) Total Iron (ppm Fe) Total Copper (ppm Cu) Total Hardness(ppmCaco3) pH@25 C0 ...

Tags:

  Asme, Water, Total, Recommended, Boiler, Limits, Conductivity, Dissolved, Mabas, Recommended abma amp asme boiler water limits boiler

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of Recommended ABMA & ASME Boiler Water Limits Boiler …

1 Recommended ABMA & asme Boiler Water Limits Boiler Water Treatment Products Recommended ABMADRUM. & asme Boiler . OPERATING PRESSUREWATER. (psig) Limits *. 0-300 301-450 451-600 601-750 751-900 901-1000 1001-1500 1501-2000. STEAM. TDS max (ppm) Boiler Water . TDS max (ppm) 700-3500 600-3000 500-2500 200-1000 150-750 125-625 100 50. ALK max (ppm) 350 300 250 200 150 100 Not specified Not specified TSS Max (ppm) 15 10 8 3 2 1 1 n/a conductivity max ( mho/cm) 1100-5400 900-4600 800-3800 300-1500 200-1200 200-1000 150 80. Silica max (ppm Si02) 150 90 40 30 20 8 2 1. FEEDWATER (CONDENSATE & MAKEUP, AFTER DEAERATOR).

2 dissolved Oxygen (ppm 02) E W. D. total Iron (ppm Fe) total Copper (ppm Cu) total Hardness(ppmCaco3). pH@25 0 C. None detected None detected DEW. Nonvolatile TOC (ppm C) 1 1 Chemical Division Oily Matter (ppm) 1 1 MAKE-UP AT % BLOWDOWN. TDS SILICA (ppm Si02) MAKE-UP AT 1% BLOWDOWN. TDS 13 1 SILICA (ppm Si02) MAKE-UP AT 2% BLOWDOWN. TDS 39 26 13 2 SILICA (ppm Si02) 3 MAKE-UP AT 3% BLOWDOWN. TDS 39 3 2. SILICA (ppm Si02) Manufacturing Location : K-47, UPSIDC Site - V, Greater Noida India Dew Speciality Chemicals (P) Ltd. F-38/5A, SN-II, Palam, New Delhi-110045, (India). Telephones : +91 (11) 25035365 & 25038160.

3 Fax : +91 (11) 25052307. E-mail : Web : Steamplan Complete Solutions for Steam Generator (Boilers).. DEWTREAT DEWTEX DEWTRAK DEWFLOC are the registered trademark of DEW . Problems STEAMPLAN Solutions Water used to generate steam contains various impurities, the most typical being compounds of calcium, magnesium, silica and iron. In an Control of Boiler - Water chemistry, before and after the Water enters system where impurities are allowed to reach excessive the steam generating system, is vital to efficient operation, acceptable maintenance costs, and satisfactory equipment concentrations, steam quality can be impaired.

4 In addition, hardness service-life. salts can precipitate from the Boiler Water to form sludge and eventually scale, which deposits on the internal surfaces of the Boiler . All-In-One Programs - Liquid blends of alkalinity The result: a serious loss of Boiler efficiency, and possibly Boiler builders/polymers and sulfite designed as one of the single drum failure. and advanced treatment for high pressure boilers (AVT). Scale is a buildup of solid material formed on internal Boiler surfaces when the concentration of impurities in the Boiler Water exceeds their Oxygen Scavengers - Products in this group represent inorganic solubility limit and precipitation occurs.

5 Hardness compounds and organic catalyzed oxygen scavengers. These products cover all pH ranges and concentrations, and are available in liquids and predominantly calcium and magnesium salts collect on heat-transfer powders. Also, more effective products for Boiler lay-ups are surfaces in the form of a sludge that typically also contains iron, available. organics and other impurities. Corrosion is the destruction of a metal by electromechanical reaction Alkalinity Builders - Liquid alkalinity builders to prevent acid attack with its environment. In Boiler systems, that environment includes hot and amine based product with higher distribution ratio for Water with a low pH or slightly acid condition and some degree of condensate treatment.

6 Oxygen entrainment. Those conditions are ideal for corrosive action. Removal of carbon dioxide and oxygen from Boiler feedwater is Scale Prevention - Products in the group consist of the newest Tracer all polymers and phosphate technologies for effective scale essential to preventing Boiler -system corrosion. Condensation of CO2 in inhibition, crystal modification and sludge dispersion to ensure clean the condensate system results in the formation of highly corrosive surfaces. carbonic acid (H2CO3). Much more importantly, the presence of oxygen in the feedwater leads to oxygen pitting.

7 Condensate Treatment - Neutralizing and Filming amines are Foaming and Carryover are caused due to high dissolved solid and provided in a wide variety, utilizing formulation based on standards caustic alkalinity in combination with leakages, load changes and organic amines. matter ( oil). A complete range of Food Grade Product . ( FDA ).


Related search queries