Transcription of REFRIGERATED TYPE COMPRESSED AIR DRYERS
1 1 GENERAL SAFETY INFORMATION ..2 RECEIVING, MOVING, UNPACKING .. INSTALLATION .. OPERATION .. MAINTENANCE ..7 SIZING ..7 ENGINEERING DATA ..8 DIMENSIONS / WEIGHTS ..9 TROUBLESHOOTING .. 10 PARTS LIST .. 11 WARRANTY .. 8/99 INSTRUCTION MANUALM odels 8005, 8010, 8015 SERVICE DEPARTMENT: (724) 746-1100 REFRIGERATEDTYPECOMPRESSEDAIR DRYERS For Sales & Service contact: CENTRAIR Air Systems & Supplies 705-722-5747 Sales & Service please contact:CENTRAIR Air Systems & SuppliesPhone: 705-722-5747 Fax: 705-722-5458 Email: PRESSURIZED DEVICES:This equipment is a pressure containing not exceed maximum operating pressure as shown on equipment serial number sure equipment is depressurized before working on or disassembling it for ELECTRICAL:This equipment requires electricity to equipment in compliance with all applicable electrical equipment is supplied with electrical enclosures not intended for installation in hazardous power supply to equipment when performing any electrical service BREATHING AIR:Air treated by this equipment may not be suitable for breathing without further to applicable standards and specifications for the requirements for breathing quality , MOVING, AND UNPACKINGA.
2 RECEIVINGThis shipment has been thoroughly checked, packed and inspected before leaving our was received in good condition by the carrier and was so for Visible Loss or this shipment shows evidence of loss or damage at time of delivery to you, insist that a notation of this loss or damage be madeon the delivery receipt by the carrier s UNPACKINGC heck for Concealed Loss or a shipment has been delivered to you in apparent good order, but concealed damage is found upon unpacking, notify thecarrier immediately and insist on his agent inspecting the damage claims are not our responsibility as our terms are point of MOVING In moving or transporting dryer , do not tip dryer onto its STORAGEIMPORTANT - Do not store dryer in temperatures above 130 F, C.
3 GENERAL SAFETY INFORMATIONFor Sales & Service contact: CENTRAIR Air Systems & Supplies 705-722-5747 typical placement in a COMPRESSED air system, compressor intake - Locate air compressor so thatcontaminants potentially harmful to the dryer ( ammonia)are not drawn into the air air flow - Do not block either side of the 12 inches (305 mm) on each side of cabinet for freeair flow. Standard units are designed to operate inambients from 35 to 110 F (2 to 43 C). in altitudes above 4500 feet (1370 meters) - dryer is adjusted to operate in altitudes up to 4500 feet(1370 meters). If dryer is installed in an altitude above this, and has notbeen preset at the factory for this altitude, contactmanufacturer s Service SEPARATOR OIL RECEIVER REMOVAL FILTER AFTERCOOLER AUTOMATIC dryer DRAIN TYPICAL COMPRESSED AIR SYSTEM155 and 10 )INSTRUCTIONTAGSERIAL NUMBER TAGIMPORTANT:READ PRIOR TO STARTING THIS EQUIPMENTNOTEO utdoor installation- Standard units are designed for indoorinstallation.
4 Contact manufacturer if installing Sales & Service contact: CENTRAIR Air Systems & Supplies 705-722-5747 MountingA. Wall mounting - dryer may be mounted using the wall mounting bracket supplied. Keyhole slots are also provided in the cabinet as an optional mounting Base mounting - dryer may be installed on a suitable shelf or floor Piping connectionsA. Air Inlet - Connect COMPRESSED air line from air source to air inlet. WARNING Refer to Serial Number Tag for maximum working pressure. Do not exceed dryer 's Maximum Working PressureNOTEI nstall dryer in air system at highest pressure possible ( beforepressure reducing valves)NOTEI nstall dryer at coolest COMPRESSED air temperature possible.
5 Maximuminlet COMPRESSED air temperature: 120 F (49 C). If inlet air exceedsthis temperature, precool the air with an Air Outlet - Connect air outlet to downstream air If servicing the dryer without interrupting the air supply is desired, piping should include inlet and outlet valves and an air by-pass air by-pass valve, if ordered with dryer , has been shippedseparately in carton for field mounting. OPTIONALAIR BY-PASS VALVEINOUTD ryer InletDryer OutletFrom CompressorTo Point of UseAIR OUTLETAIR INLETFor Sales & Service contact: CENTRAIR Air Systems & Supplies 705-722-5747 CLOSE( TURN COUNTERCLOCKWISE ) KNURLED FITTINGNOTEC ondensate may contain with applicable laws concerning proper Electrical connectionsA. dryer is designed to operate on the voltage, phase, and frequency listed on serial number dryer is supplied with a cord and plug.
6 Install in receptacle of proper condensing unit is designed to run continuously andshould NOT be wired to cycle on/off with the air Remote Alarm Remote alarm can be wired at dryer installation site. Connect alarm in parallel to high temperature light terminals in electrical box. Amperage rating of alarm circuit: @ 115 VAC @ 230 VACR esistive load amps .. full load amps .. locked rotor amps .. Moisture separatorA. Separator has an internal drain which automatically discharges collected condensate. It may be desirable to pipe the condensate to a suitable drain. NOTED ischarge is at system pressure. Drain line should be Separator has a knurled fitting with flexible drain tubing attached.
7 Be sure knurled fitting is tightened by turning it counterclockwise before operating Sales & Service contact: CENTRAIR Air Systems & Supplies 705-722-5747 ONHI TEMP Minimum/maximum operating conditionsA. Maximum inlet air pressure: refer to unit serial number tagB. Minimum inlet air pressure: 20 psig ( bar)C. Maximum inlet air temperature: 120 F (49 C)D. Maximum ambient temperature: 110 F (43 C)E. Minimum ambient temperature: 35 F (2 C) Start-up Energize dryer . Power-on light will Operating check points Check the following on a periodic basis:A. Green power-on light is Red high air temperature warning light is out. The high air temperature warning light will illuminate when dryer is energized. Light should go out approximately 15 minutes after start-up.
8 If light remains on after 30 minutes or illuminates after going out, refer to Troubleshooting Condensate is discharging from Sales & Service contact: CENTRAIR Air Systems & Supplies 705-722-5747 Condenser coil - Clean off accumulated dust and dirt Moisture separator - Replace filter sleeve when pressure drop across dryer is Check separator daily to be sure automatic drain is Blow down separator weekly by turning knurled fitting clockwise to dryer capacity at actual oper-ating conditionsTo determine the maximum inlet flow capacity of a dryer atvarious operating conditions, multiply the rated capacity fromTable 1 by the multipliers shown in Table : How many scfm can an air-cooled 10 scfm dryerhandle when COMPRESSED air to be dried is at 80 psig and90 F; ambient air temperature is 80 F; and a 38 F dew pointtemperature is desired?
9 Answer: 10 x x x = 1 Rated capacity and pressure drop @ 100 psig inlet pressure,100 F inlet temperature, and 100 F ambient temperature SEPARATOR HEAD HEAD O-RING CARTRIDGE O-RING SEPARATOR (PERMANENT) FILTER SLEEVE (REPLACEABLE) BOTTOM CAPWING NUT AUTO DRAIN MECHANISM INSULATION SETCOLLARBOWLTUBEFASTENERDRAIN TUBE ELASTIC FASTENER OUTLET DEWPOINT DEW POINT TEMPERATUREMULTIPLIER F COOLING MEDIUMAMBIENT TEMPERATURE MULTIPLIER F INLET COMPRESSED AIR CONDITIONS INLETINLET TEMPERATURES PRESSURES80 F90 F100 F110 F120 Fpsig kgf/cm227 C32 C38 C 43 C49 2 Air capacity correction factors (multipliers)MODEL51015 Rated capacity of @60 Hz51015 air-cooled models (scfm) @50 Pressure drop at @60 rated capacity (psi) @50 x - m3/minPressure DropTo determine pressure drop at increased flows, multiply thepressure drop at rated conditions from Table 1 by the multi-plier shown in Table 3 for the appropriate air flow rate andoperating : What is the pressure drop across a model 10 whenflowing 12 scfm at 100 psig?
10 Answer: 12/10 = ; multiplier from table at x rated flowand 100 psig = ; x psi = 3 Pressure drop correction factors (Multipliers) OPERATING PRESSURE psig / kgf/cm2 AIR FLOW60 / / 7180 / / x rated x rated x rated Sales & Service contact: CENTRAIR Air Systems & Supplies 705-722-5747 Max. Inlet Air Pressure ( COMPRESSED air at inlet to dryer )a) Standard 20 psig ( bar) - 175 psig (12 bar )b) Optional 20 psig ( bar) - 300 psig (21 bar)Max. Inlet Air Temp. ( COMPRESSED air at inlet to dryer ) 120 F (49 C) Ambient Temperature 35 F ( C) - 110 F (43 C) Refrigeration System Data 5 10 15 Compressor Type Hermetic - Resistance Start, Induction Run - Non-CyclingRefrigeration Compressor Horsepower1/20 1/6 1/5 BTU/HR - Refrigeration Only @ 35 F Evaporator & 100 F Ambient 60 Hz / 50 Hz 716 / 596 1010 / 842 1380 / 1150 Outlet Air Temperature (nominal at rated conditions) 40 F ( C) 40 F ( C) 40 F ( C)