Example: marketing

Regulator Product Line - Itron

Regulator Product LineDesigned for accuracy, dependability and safety, Itron gas pressure reducing regulators are for use in natural gas distribution systems as well as industrial applications (for example, burners and boilers) with most non-corrosive gases, including air, nitrogen, dry carbon dioxide and propane. Itron s Regulator Product line is based on a building-block approach. The Product range uses common components and parts resulting in an extremely versatile and innovative Product line that provides an economical solution to the most challenging Regulator MODELSS pring Loaded Service RegulatorB42, B57v, B31, B34S, B34, B38 For lower outlet pressure applications (inches through 5 PSIG): Residential and light commercial applications Burner FurnacesConstant Loaded RegulatorCL31, CL231, CL34, CL38 For higher outlet pressure applications (2 PSIG through 60 PSIG): Fixed factor billing applications Larg

diaphragm for commercial and industrial loads. The B34 maintains accurate regulation on applications where frequent sudden load changes can occur. Rugged construction enables the basic B34 model to cover applications with outlet pressures of in. w.c. through 5 PSIG by merely changing adjustment springs. B38 Series

Tags:

  Diaphragm, Spring

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of Regulator Product Line - Itron

1 Regulator Product LineDesigned for accuracy, dependability and safety, Itron gas pressure reducing regulators are for use in natural gas distribution systems as well as industrial applications (for example, burners and boilers) with most non-corrosive gases, including air, nitrogen, dry carbon dioxide and propane. Itron s Regulator Product line is based on a building-block approach. The Product range uses common components and parts resulting in an extremely versatile and innovative Product line that provides an economical solution to the most challenging Regulator MODELSS pring Loaded Service RegulatorB42, B57v, B31, B34S, B34, B38 For lower outlet pressure applications (inches through 5 PSIG): Residential and light commercial applications Burner FurnacesConstant Loaded RegulatorCL31, CL231, CL34, CL38 For higher outlet pressure applications (2 PSIG through 60 PSIG).

2 Fixed factor billing applications Large commercial IndustrialDirect Acting IndustrialRB1700, RB4000 For commercial and industrial applications requiring fast response and high capacities up to 600,000 SCFH: Ovens Boilers FurnacesField Service RegulatorB35, B36, B56 For intermediate and high-pressure applications: First stage regulation Farm taps Suburban taps Compressed air systemsSPECIFICATIONSINTERNAL MONITORFor additional safety, the Internal Monitor (IM) is a unique feature available exclusively in Itron regulators. A secondary orifi ce and valve seat enables the IM Regulator to control the gas fl ow and lockup in a failure event at the main seat and orifi ce.

3 The IM prevents large gas amounts from venting into the atmosphere and does not require manual IM Regulator design specifi cally complies with DOT OPS , paragraph B, which states: If the gas contains materials that seriously interfere with the operation of a service Regulator , there must be suitable protective devices to prevent unsafe overpressuring of the customer s appliance if the service Regulator fails. The code lists the devices, including a Regulator monitor. The code further states that these devices may be installed as an internal part of the service Regulator or as a separate OperationThe IM operates like a standard upstream monitor set; the monitor is wide open under normal conditions.

4 Normal regulation and lockup occur at the main valve seat and orifi ce. (The closing spring causes CL models to lockup at both seats under normal conditions.)IM OperationIf the Regulator fails to control the gas fl ow due to foreign matter or damage at the main seat and orifi ce, the secondary orifi ce automatically takes control at a slightly elevated outlet pressure. The point of regulation moves to the upstream monitor seat and orifi LockupIf the gas demand shuts off during monitor operation, the secondary orifi ce is formed into the monitor seat to provide bubble tight OptionIn installations where a small gas volume can be safely vented to the atmosphere in the event of a failure, the vent signal option (IMRV) is available.

5 Upon lockup at the monitor seat, a bleed hole allows a controlled amount of gas to bleed past the main seat failure. Outlet pressure builds slowly and the excess gas releases to the atmosphere through the internal relief valve serving as a signal that the main seat SizesMax. InletOutlet Pressure RangeResidential & Light CommercialB42B31R, N, HR, N, IM, IMRV , , 1 , 1 , 1 , 1 125 PSIG125 PSIG5 in. to 5 PSIG4 in. to 2 PSIG2,000 SCFH2,500 SCFHC ommercial & Light IndustrialB34SB34B38R, N, HR, N, M, D, IM, IMRVR, N, M, D, IM, IMRV1 , 1 , 2 , 2 FL, 3 FL1 , 1 , 2 , 2 FL, 3 FL1 , 2 , 2 FL, 3 FL125 PSIG125 PSIG125 PSIG4 in.

6 To 2 PSIG5 in. to 5 PSIG5 in. to 5 PSIG3,500 SCFH10,000 SCFH20,000 SCFHI ndustrial (Burner)(Twin Parallel Flow)(Twin Parallel Flow)R B170 0B531B838RB4000R, N, IM, IMRVR, N, M, IM, IMRV, D0, 1, 21 NPT , 1 , 1 , 1 , 2 2 , 2 FL, 3 FL, x 4 FL2 FL, 3 FL275 PSIG125 PSIG125 PSIG275 PSIG7 in. to 30 PSIG5 in. to 2 PSIG5 in. to 5 PSIG5 in. to 30 PSIG120,000 SCFH5,000 SCFH50,000 SCFH600,000 SCFHI ndustrial &Fixed Factor Billing(Twin Parallel Flow)CL31CL231CL34CL38CL838R, N, IMR, N-1, -2, M, IM, D-1, -2, M, IM, D-1, -2, M, IM, D , 1 , 1- 1- , 1- , 2 , 2 FL, 3 FL1- , 1- , 2 , 2 FL, 3 FL1- , 2 , 2 FL, 3 FL2 , 2 F L, 3 F L, 4 F L125 PSIG125 PSIG150 PSIG150 PSIG150 PSIG1 PSIG to 20 PSIG1 PSIG to 20 PSIG1 PSIG to 60 PSIG1 PSIG to 30 PSIG1 PSIG to 30 PSIG4,000 SCFH7, 5 0 0 S C F H25,000 SCFH50,000 SCFH100,000 SCFHHigh PressureField ServiceB36B56B35 RRR, N, M , 1 , 1- , 1 , 1 175 PSIG1000 PSIG1000 PSIG1 PSIG to 60 PSIG5 PSIG to 60 PSIG10 PSIG to 150 PSIG2,500 SCFH5,000 SCFH5.

7 000 SCFHSPRING LOADEDI tron spring loaded service regulators are simple direct-acting regulators designed for accuracy, safety and dependability. spring loaded service regulators are used primarily for fi nal stage lower outlet pressure applications (inches to 2 or 5 PSIG). Typical applications include residential and low outlet pressure commercial and industrial gas supply and all gas-fi red equipment types, including furnaces, boilers, dryers, ovens, and heaters. spring loaded regulators provide extremely fast response to changing downstream fl ow conditions. Itron spring loaded regulators include the following unique features to offset pressure droop at high fl ows caused by the spring and diaphragm effect: Controlled BoostAll regulators are equipped with boosting devices B42: raised lip on valve seat All others: adjustable loading ring Controlled Breather OpeningAll regulators are equipped with a soft seat vent valve to ensure proper breathing and stability under all conditions High Capacity Internal ReliefAll spring loaded regulators are equipped with internal relief as standard.

8 Relief fl ow paths are as large as practical to provide the least resistance to venting gas in the event of an over-pressure situation to minimize pressure buildupB42 SeriesThe B42 service Regulator incorporates a molded diaphragm and increased lever ratio into a conventionally designed Regulator . The result is a lighter, more compact unit that provides the power, capacity and relief performance of much larger regulators. Reduced weight means easier handling and installation. Reduced size means easier installation in limited spaces and a lower profi le meter set. Typical applications include residential services, 2 PSIG systems and small commercial SeriesThe B31 service Regulator is a high-performance Regulator with a large effective diaphragm area and powerful lever ratio.

9 The B31 is designed to maintain accurate regulation over a wide range of fl ows on systems with extreme variations in inlet pressure and to deliver high capacities with very low inlet pressures. Typical applications include demanding residential services and light commercial SeriesThe B34S service Regulator is a compact, cost-effective Regulator designed for mid-range commercial applications. The B34S is particularly well suited for quick on/off applications where shock problems can SeriesThe B57 Regulator is ideally suited for use where inches of water column or pounds delivery pressure are desired for uses including utility services, small boilers, and other similar applications.

10 The B57 is ideal for situations where rapid response is required, such as on/off loads, and can be utilized to avoid shock problems. In situations where complete 360 rotation of the diaphragm case is desired, the B57 can accommodate any position of OperationInlet pressure is reduced to a lower outlet pressure by restricting fl ow through an orifi ce to match a fl uctuating downstream demand. As downstream demand increases, outlet pressure drops slightly and the diaphragm moves downward. The valve seat moves farther away from the orifi ce face to allow an increased fl ow to match the increased demand As downstream demand decreases, outlet pressure increases slightly moving the diaphragm upward.


Related search queries