1 killion Industries, Inc. 1380 Poinsettia Ave., Vista, CA 92081 Phone (760) 727-5102 Toll Free (800) 421-5352 Fax (760) 727-5108 RESETTING THE LAE CONTROL TO FACTORY DEFAULT Figure 1 Detail image of LAE CONTROL Display. Note: The case must be powered on to reset the controller settings. 1. Locate the LAE Controller Display on your specific case. It is typically located near the compressor. 2. Hold down both the i and the x buttons for 5 seconds. The parameter SPL will show on the screen. 3. Tap the button. The screen will show the rES parameter. 4. Hold down the i button.
2 While holding down the button, tap the to change the setting from nO to YES , then release the i button. 5. Tap the x button to return the controller to normal operation. All parameters are now returned to the DEFAULT FACTORY settings. Should you have any questions call killion Customer Service at 1-800-421-5352 or email at . PROGRAMMING THE LAELED Display Codes:dEF =Defrost in = High Temperature AlarmLo = Low Temperature AlarmE1 = Probe T1 (case temp) failureE2 = Probe T2 (evaporator temp) failureLED Symbols: = Compressor Relay = Fan Relay= Defrost ActiveII = Second Setpoint Active= AlarmTo change the SETPOINT:1) Hold down the 'i' button.
3 This will show the current ) While holding the 'i' button use the ' ' and ' ' to change the ) Release the 'i' button to store the new change other settings:1) Hold down both 'i' and 'x' buttons for 5 ) Use the ' ' and ' ' buttons to select the parameter to be ) Hold down the 'i' button to display the current ) While holding down 'i', use the ' ' and ' ' buttons to set the desired ) Release the 'i' button to store the new value and display the next ) To exit the programming mode, tap the 'x' button or wait 30 Menu Codest1 = case temeprature readingt2 = evaporator temperature readingthi = maximum case temp recorded tLo = minimum case temp recordedLoc = keyboard lock stateInformation Menu Access1) To access the menu, tap the 'i' button.
4 2) Use the ' ' and ' ' buttons to select the data to be ) Hold the 'i' button to display the selected ) To exit the menu, tap the 'x' button or wait 10 Menu Reset1) To reset THi and TLO tap the 'i' ) Use the ' ' and ' ' buttons to select the data to be ) Hold the 'i' button to display the selected ) While holding down the 'i' button, tap the 'x' button to reset the ) To exit the menu, tap the 'x' button or wait 10 of 2 LAE DEFAULT ParametersCodeParameterRangeFunctionSPLS etpoint Low-50 to SPH Minimum limit for the Setpoint settingSPHS etpoint HighSPL to 120 Maximum limit for the Setpoint settingSPSetpointSPL to SPHT emperature to be maintained (case setpoint)
5 HYSH ysteresis1 to 10 Thermostat differenetialCRTC ompressor rest to 30 minMinimum off time for the compressor between on to 30 minCompressor run time when temperature probe 1 is off to 30 minCompressor off time when temperature probe 1 is door delay0 to 30 minCompressor stop delay after the door has been opened. Active only if D1 or D2 = DORDFMD efrost start modeNON/TIM/FRONON - Defrost is disabledTIM - Regular timed defrostFRO - Defrost time count is only increased when the conditions occur for frost to form on the evaporator (optimized time increase).DFTD efrost time0 to 99 hrsTimer value for a defrost to time backupNO/YESIf DFB=YES, after a power interruption, the timer will resume the count from where it left off with a 30 min DFB=NO, after a power interruption, the timer will restart the count from 0 DLID efrost end temperature-50 to 120 Temperature read by temperature probe 2 at which defrost will defrost duration1 to 120 minMaximum time limit for typeOFF/ELE/GASOFF - off cycle defrost (compressor and heater off)ELE - electric defrost (compressor off, heater on)GAS - hot gas loop defrost (compressor on, heater on)
6 DPDE vaporator pump down0 to 240 secAt defrost start, defrost outputs are OFF for DPD drip time0 to 30 minAfter defrost end, time before normal cycle display modeRT/LT/SP/DEFRT - during defrost show the real temperature from probe T1LT - during defrost show the last temperature from probe T1SP - during defrost show current setpointDEF - during defrost show "DEF"DDYD efrost Display delay0 to 60 minThe display will show the value from DDM during defrost and for DDY minutes after defrost during defrostNO/YESFans active during defrostFDDFan restart temperature-50 to 120 Evaporator fan will restart below FDD temperature.
7 Read from probe T2 FTOFan restart time0 to 120 minMaximum time delay for evaporator fan restart after a mode during cycleNON/TMP/TIMNON - fans are always - temperature based CONTROL . Fans remain on when the compressor is ON. When the compressor is OFF the fans remain on as long as the temperature difference T2-T1 is greater than FDT. The fans are turned on again with the FDH differential. T1 = air temperature, T2 = evaporator temperatureTIM - time based CONTROL . The fans are on when the compressor is ON. When the compressor is OFF, the fans switch on and off according to parameters F1, F2, air temperature difference-120 to 0 T2 - T1 temperature difference for the fans to turn off when the compressor is difference for fan restart1 to 120 T2 - T1 temperature difference for the fans to stop delay0 to 180 secAfter compressor stops, time in seconds until the fans stop.
8 Used if FCM parameter is set to TIMF2 Fan stop time0 to 30 minTime that fans are off while compressor is off. Used if FCM parameter is set to TIMF3 Fan run time0 to 30 minTime that fans are on while the compressor is off. Used if FCM parameter is set to TIMATMA larm threshold management NON/ABS/RELNON - temperature alarms are - the values programmed into parameters ALA and AHA represent temperature alarm - the values programmed into parameters ALR, AHR, SP, and HYS determine the alarm limits. Lower limit = SP-ALR Upper limit = SP+HYS+AHRALALow temperature alarm limit-50 to 120 Lowest temperature to trigger alarmAHAHigh temperature alarm limit-50 to 120 Highest temperature to trigger alarmALRLow temperature alarm differential-12 to 0 Low temperature alarm differential.
9 If ALR = 0, low limit alarm is temperature alarm differential0 to 12 High temperature alarm differential. If AHR = 0, high limit alarm is probeT1/T2/T3 Probe used for temperature alarm alarm delay0 to 120 minDelay in minutes before temperature alarm is alarm delay0 to 30 minDelay in minutes before door alarm is alarm settingNON/ALR/STPNON - condenser alarm disabledALR - condenser alarm enabled. When alarm occurs, "HC" flashes on the display and the buzzer - in addition to display and buzzer from ALR, condenser power is cut and defrosts are alarm limit-50 to 120 Condenser temperature alarm limit. Temperature read by T3 cleaning0 to 52 weeksWhen the condenser operation time, in weeks, matches the value from ACC, the display will flash "CL".
10 If ACC = 0, the setting is of 2 LAE DEFAULT ParametersCodeParameterRangeFunctionIISM S witch mode to second setpointNON/MAN/DI2 NON - secondary setpoint - button M on display toggles between primary and secondary setpointDI2 - closing switch connected to DI2 inputs switches to secondary setpointIISLS econdary setpoint low-50 to SPH Minimum limit for the Secondary Setpoint settingIISHS econdary setpoint highSPL to 120 Maximum limit for the Secondary Setpoint settingIISPS econdary setpointSPL to SPHT emperature to be maintained (secondary setpoint)IIHYS econdary hysteresis1 to 10 Thermostat differenetial for secondary setpointIIFC Secondary fan controlNON/TMP/TIMNON - fans are always - temperature based CONTROL .