Example: air traffic controller

Residual current protective devices, type F - Siemens AG

Siemens AG 2012. s SENTRON. Residual current protective devices , type F. Reliable touch protection for electrical loads with frequency converters All-round protection High operational reliability Highlights Residual current operated circuit breakers RCCBs type F are characterized by a short- type F have been specially developed to time delayed Residual current tripping, 7 Maximum protection thanks to offer protection against electric shock which means they are far less prone to false reliable detection of mixed when using electrical loads with frequency tripping in the event of leakage current frequencies converters in single-phase AC networks. spikes. They also offer an increased current 7 Fewer false trippings thanks to Instead of DC Residual currents, this type of withstand capability of at least 3 kA and short-time delay electrical equipment generates Residual can handle loads of smooth DC Residual 7.

the same applies as for residual current protective devices type A, i.e. electrical loads that can generate smooth DC residual currents in the event of a fault are assigned their own circuit with a universal current-sensitive residual current pro-tective device (type B or type B+).

Tags:

  Devices, Types, Current, Circuit, Protective, Residual, Residual current, Residual current protective devices, Residual current protective devices type

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of Residual current protective devices, type F - Siemens AG

1 Siemens AG 2012. s SENTRON. Residual current protective devices , type F. Reliable touch protection for electrical loads with frequency converters All-round protection High operational reliability Highlights Residual current operated circuit breakers RCCBs type F are characterized by a short- type F have been specially developed to time delayed Residual current tripping, 7 Maximum protection thanks to offer protection against electric shock which means they are far less prone to false reliable detection of mixed when using electrical loads with frequency tripping in the event of leakage current frequencies converters in single-phase AC networks. spikes. They also offer an increased current 7 Fewer false trippings thanks to Instead of DC Residual currents, this type of withstand capability of at least 3 kA and short-time delay electrical equipment generates Residual can handle loads of smooth DC Residual 7.

2 Increased current withstand currents with mixed frequencies. The currents up to 10 mA. The broad range of capability of 3 kA. tripping characteristic of RCCBs type F lies Residual current protective devices type F 7. Higher load rating with smooth between type A and type B, which ensures includes RCCBs, RC units and RCBOs DC Residual currents up to 10 mA. reliable coverage of the type of fault current forms that can arise when using single- phase loads with frequency converters. Answers for infrastructure. Siemens AG 2012. Residual current protective devices Residual current protective devices , type F. Application Residual current protective devices type F not only offer the full Increased current withstand capability of > 3 kA (8/20 s). range of protection and function features provided by type A, The tripping characteristics are not influenced by DC Residual they are also ideal for the detection of Residual currents with currents up to 10 mA.

3 Mixed frequencies, as found on the outgoing terminal of fre- quency converters. This ensures coverage of the type of fault They are suitable for electronic loads with frequency converters, current forms that can arise when using single-phase loads with such as those found in washing machines and heating pumps. frequency converters. The following table offers an overview of which type of They also offer the following characteristics: Residual current protective device is suitable for which electronic Short-time delay in order to prevent unwanted trippings switching operation (in equipment). RCCBs type F are suitable caused by transient leakage currents up to 10 ms. for circuits 1 to 7. Suitable RCCB type Circuits Load current Residual current B F A AC i F1. mX. i F1. B+ mX. i F1. mX. i F1. mX. i F1. mX. i F1.

4 MX. iL iL i F1 i F2. L1 M. N i F1 i F2. t t PE. i F1. mX. i F1. mX. i F1. mX. iL iL i F1 i F2. L1. 11 L2 i F1 i F2. M. N. PE t t i F1. 12. mX. iL iL i F1 i F2. L1. i201_16045. 13 L2. L3 i F1 i F2. M. N t t PE. Table: Possible fault current forms and suitable Residual current devices 2 Siemens 2012. Siemens AG 2012. Residual current protective devices Residual current protective devices , type F. Configuration When using Residual current protective devices type F, When configuring and setting up electrical plants with type F, please note the following: the same applies as for Residual current protective devices They are not suitable for equipment that can generate smooth type A, electrical loads that can generate smooth DC. DC Residual currents (see Table, page 2, circuits 8 to 13). Residual currents in the event of a fault are assigned their own circuit with a universal current -sensitive Residual current pro- They are not suitable for installation in networks with tective device (type B or type B+).

5 Frequencies that deviate from the rated frequency (50 Hz). (not at the outgoing terminal of a frequency converter). Wh Wh Type Type AC/A/F AC/A/F. I n 300 mA S I n 300 mA S. Type Type Type Type AC/A/F B/B+ AC/A/F B/B+. kHz kHz I n 100 mA I n 30 mA I n 100 mA I n 30 mA. i201_18413. i201_18414. It is not permitted to branch off electrical circuits with these types of electrical loads downstream of pulse- current -sensitive Residual current protective devices (type A or type F). Siemens 2012 3. Siemens AG 2012. Residual current protective devices Residual current protective devices , type F. Technical data 5SM3 .. -3 5SM2 .. -3 5SU1 /. RCCBs RC units 5SU1 RCBOs Standards IEC/EN 62423 (VDE 0664-40). Approvals DIN EN 62423 (VDE 0664-40). Versions 1P + N; 3P + N 2P 1P + N. Surge current withstand capability kA >3 >3 >3.

6 With current waveform 8/20 s Minimum operational voltage V AC 100 195 100. for test function operation Terminal/conductor cross-sections for 2 MW at In = 25 A, 40 A mm2 .. 16 .. 35. for MW at In = 63 A mm2 .. 25 for 4 MW at In = 25 A, 40 A, 63 A mm2 .. 25. Terminal tightening torques Nm .. Mains connection Top or bottom Mounting position Any Degree of protection acc. to EN 60529 IP20, with connected conductors (VDE 0470-1). Touch protection acc. to EN 50274 Finger and back-of-hand safe (VDE 0660-514). Service life Test cycle acc. to IEC/EN 62423 > 10000 operating cycles Storage temperature C -40 .. +75. Ambient temperature C -25 .. +45, Marked with -25. Resistance to climate acc. to IEC 60068-2-30 28 cycles (55 C; 95 % rel. air humidity). Overvoltage category III. Degree of pollution 2. CFC and silicone-free Yes 4 Siemens 2012.

7 Siemens AG 2012. Residual current protective devices Residual current protective devices , type F. Selection and ordering data (type F). Rated Residual Rated current Max. Mounting DT Order No. Price PU PS*/ PG Weight current permissible width per PU (UNIT, P. unit per PU. short- circuit SET, approx. series fuse M). I n In 10 000. mA A A MW kg RCCBs, type F. 1P + N; 230 V AC, Hz 30 25 63 2 5SM3 312-3 1 1 unit 40 5SM3 314-3 1 1 unit 63 100 5SM3 316-3 1 1 unit 3P + N; 400 V AC, 50 ..60 Hz 30 25 100 4 5SM3 342-3 1 1 unit 40 5SM3 344-3 1 1 unit 63 5SM3 346-3 1 1 unit RC units, type F. For 5SY miniature circuit breakers; not suitable for use with 5SY5, 5SY8 and 5SY6 , 2P, 230 .. 400 V AC, 50 .. 60 Hz 30 .. 40 2 5SM2 322-3 1 1 unit .. 63 2 5SM2 325-3 1 1 unit Tripping characteristic B Tripping characteristic C. Rated Rated Mounting DT Order No.

8 Price PG DT Order No. Price PU PS*/ PG Weight resi- current width per PU per PU (UNIT, P. unit per PU. dual SET, approx. current M). I n In mA A MW kg RCBO, type F. 1P+N, 230 V AC, 50 .. 60 Hz 30 6 2 5SU1 354-3KK06 5SU1 354-4KK06 1 1 unit 10 5SU1 354-3KK10 5SU1 354-4KK10 1 1 unit 13 5SU1 354-3KK13 5SU1 354-4KK13 1 1 unit 16 5SU1 354-3KK16 5SU1 354-4KK16 1 1 unit 20 5SU1 354-3KK20 5SU1 354-4KK20 1 1 unit 25 5SU1 354-3KK25 5SU1 354-4KK25 1 1 unit 32 5SU1 354-3KK32 5SU1 354-4KK32 1 1 unit 40 5SU1 354-3KK40 5SU1 354-4KK40 1 1 unit * This quantity or a multiple thereof can be ordered. Siemens 2012 5. Siemens AG 2012. Residual current protective devices Residual current protective devices , type F. Dimension drawings RCCBs, type F. 1 N 1 N 1 3 5 N. 45. 90. I201_07860c 2 N 2 N 2 4 6 N. 36 45 72 44. 7 64. 1P+N 1P+N 3P+N.

9 25/40 A 63 A 25 .. 63 A. RC units, type F. 45. 90. I201_18486. 36 6,3 44. 10. 71 64. 2P. RCBO, type F. 45. 90. I201_18487. 36 44. 7 70. 1P+N. 6 Siemens 2012. Siemens AG 2012. Residual current protective devices Residual current protective devices , type F. circuit diagrams RCCBs, type F. 1 N 1 3 5 N. I2_13636. I2_13637. 2 N 2 4 6 N. 1P+N 3P+N. RC units, type F. 1 3(N). I201_13640b 2/1 4/3 2 4. 2P. RCBO, type F. 1 N. I201_13645a 2 N. 1P+N. Siemens 2012 7. Siemens AG 2012. Appendix Conditions of sale and delivery Overview Export regulations By using this catalog you can acquire hardware and software Siemens shall not be obligated to fulfill this agreement if such ful- products described therein from Siemens AG subject to the fol- fillment is prevented by any impediments arising out of national lowing terms. Please note!

10 The scope, the quality and the condi- or international foreign trade or customs requirements or any tions for supplies and services, including software products, by embargoes or other sanctions. any Siemens entity having a registered office outside of Germa- If Purchaser transfers goods (hardware and/ or software and/ or ny, shall be subject exclusively to the General Terms and Con- technology as well as corresponding documentation, regardless ditions of the respective Siemens entity. The following terms ap- of the mode of provision) delivered by Siemens or works and ply exclusively for orders placed with Siemens AG. services (including all kinds of technical support) performed by For customers with a seat or registered office in Germany Siemens to a third party worldwide, Purchaser shall comply with all applicable national and international (re-) export control regu- The General Terms of Payment as well as the General Condi- lations.