1 SAMPLE BOILER room LOGHot Water Heating BoilersMaintenance, Testing, and Inspection LogHot Water Heating BoilersBuilding :Month :Year :Address :Fuel Type :Person(s) to be Notified in Emergency (Name and Telephone No.) BOILER No. :DAILY CHECKS1234567891011121314151617181920212 2232425262728293031(1) Record Pressure(2) Record BOILER Water Temperature(3) Record Flue Gas TemperatureWEEKLY CHECKSWEEK 1 WEEK 2 WEEK 3 WEEK 4(1) Observe Flame Condition(2) Observe Circulating PumpsMONTHLY CHECKS (Enter Date and Time)Review condition of, check or Test Each Item(A) Flame Detection Devices(H) Check Valves(B) Limit Controls(I) Drain Valves(C) Operating Controls(J) Linkages(D) Floor Drains(K) Expansion Tank Water level(E) Fuel Piping(L) Combustion Air Supply(F) Refractory(M) Relief Valve Try Lever Test(G) Stop Valves(N) Low Water CutoffYEARLY CHECKS (Enter Date and Time)(1) Inspect and Clean Fireside(4) Slow Drain Test of LWCO (2) Inspect and Clean waterside(5)
2 Daily, Weekly, Monthly Checks(3) Dismantle Low Water CutoffAPPENDIX IAPPENDIX IFebruary 9, 2000 Maintenance, Testing, and Inspection LogHot Water Heating BoilersIFill in the name of the building, its location, BOILER number, fuel type used, and the year. Name the person to be contacted in an emergency or Checks(1)Record pressure(2)Record temperature(3)Record the flue gas temperature. (This should be done withe BOILER running and atoperating temperature.)IIIW eekly Checks (Record the date and time the test or check was completed.)(1)Observe Flame Condition(2)Observe circulating pumps for proper operationIVMonthly Checks (Record the date and time the test or check was completed.)Review the condition of, check or test each item(A)Test Flame Detection Devices(B)Test Limit Controls(C)Test Operating Controls(D)Test floor drains to be sure they are draining properly.
3 (E)Check fuel piping for leakage.(F)If possible, without opening the BOILER , check the refractory for cracking anddeterioration.(G)Check stop valves(H)Inspect check valves(I)Check drain valves(J)Check linkages for damage or disconnection.(K)Observe Water level of gauge glass on expansion tank.(L)Check combustion air supply for obstruction and adequacy of air flow.(M)On Relief Valve Lift try-lever to full open and release it to snap shut.(N)Test Low Water Cutoff (if possible)VYearly (Record the date and time of the check and or inspection.)(1)Inspect and clean the fireside of the BOILER . Examine all gaskets and replace asnecessary. (2)Inspect and clean the waterside of the BOILER every two years. Replace ALL handhole gaskets.(3)Perform slow drain test to test low Water cutoffs (with burner running)(4)Dismantle, Inspect and Clean Low Water cutoffs every two (5)Perform daily, weekly and monthly tests noted this log for at least two years.
4