Transcription of SCOUT S Station Controller - Survalent Technology
1 SCOUT -S Station ControllerSubstation AutomationCommunication CapabilitiesExtensive communications capabilities allow the SCOUT -S to connect to IEDs either on multiple ports with multi-drop configurations or over three Ethernet ports. communication to the master(s) can be configured to occur via serial ports or Ethernet connected to an Ethernet LAN, one or more serial ports can be configured to act as terminal server ports. This allows a remote device (the master or other appropriate computer on the LAN) to access this port and exchange data with an external device.
2 As an example, this feature can be used to remotely configure IEDs or upload historical data SCOUT -S has a dedicated serial port for configuration, point monitoring and diagnostics. A simple terminal connected to this port will act as the human interface. When connected to an Ethernet LAN, the same configuration and diagnostic operations can be performed remotely on the RTU via Telnet or a web browser. A powerful web server is also integrated within the SCOUT -S, allowing operation, maintenance, and configuration of the RTU without the need of proprietary software.
3 Any standard web browser allows direct access to the web server built-in within the configuration is provided by the Points Mapping Wizard which allows points mapping of third party IEDs and I/O cards in a graphical environment. An extensivelibrary of point maps is available for the most common IEDs available on the market, making IED point mapping a few clicks of the Station Controller features multiple IED ports and modular I/O architectureStation Controllers not only combine the functions of a traditional RTU with the functionality of a Data Concentrator, but also includes a Terminal Sever and a Web communications capabilities are available over both serial and Ethernet networks.
4 Modular I/O architecture allows the SCOUT -S to be scaled to the desired point size up to256 I/O points of each type per SCOUT -S module up to a database size of 16,000 innovative architecture allows the SCOUT -S to monitor and control points connected directly to the RTU. The modular I/O boards are compatible with those used on previous Survalent RTUs, ensuring that the SCOUT -S unit can replace the main electronic circuits in previous RTUs such as the capability also enables a customer to upgrade to a more feature-rich RTU while leaving the external wiring untouched.
5 This upgrade capability also applies to the older 6 CPP4 and 6 CPP6 RTU Station ControllerProcessing NXP P1020 800 MHz Dual Core Processor 64 MB FLASH Memory 1 GB DDR3 RAM Nonvolatile EEPROM for system configuration parametersCommunications 11 serial RS232/RS485 for master, IED, or terminal server 1 serial RS232 for diagnostic and configuration 1 serial RS485 for inter module LAN 3 Ethernet: 10/100 BaseTX and 10/100/1000 Base-T (Gigabit)Environmental 0 C to 60 C operating -40 C to 70 C operating (optional) 0 C to 85 C storage Humidity 10-90% relative noncondensing Surge Protection per ANSI on all I/OsTime Synchronization Demodulated IRIG-B input Simple Network Time Protocol SCADA systemInput/Output Boards Compact and rack mountable I/O boards are available for Digital & Analog Inputs & Digital OutputsDigital Inputs (per SCOUT -S module)
6 256 Alarm/Status/Accumulator Inputs via 16 I/O expansion boards Optically Isolated Inputs Scan Time 1ms for SOE, 10 ms for others Configurable for dry or wetted field contacts 24 Vdc wetting voltage @ 5mA (12, 48, and 125 Vdc)Large Points Database Capacity Maximum Database Size of 16,000 PointsAnalog Inputs (per SCOUT -S module) 256 via 16 I/O expansion boards Configurable Input ranges: +/-1mA, +/-20mA, +/-5V, +/-10V Sampling rate 2sec Accuracy of full scale Configurable dead band per point (protocol dependent)Digital Outputs (per SCOUT -S module) 256 Control Outputs Select Check Operate sequence Momentary, pulsed or latched outputs supported Interposing Relays (Single Form A or dual Form C)
7 Form A - Potter & Brumfield Series KUP or KUEP Form C - Potter & Brumfield Series KULM aster Station Protocols over TCP/IP IEC 60870-5-101 IEC 6870-5-104 Modbus Modbus TCPIED Protocols DNP DNP over TCP/IP Modbus RTU Modbus TCP SEL Protocol Cooper 2179 IEC 60870-5-103 IEC 60870-5-101 SCOUT -S Station ControllerType TestsElectromagnetic Compatibility EmissionsConducted Emissions: IEC 61000-6-4 or EN 61000-6-4 CISPR 11, EN 55011 Class A, Group 1 Radiated Emissions: IEC 61000-6-4 or EN 61000-6-4 CISPR 11, EN 55011 Class A, Group 1 Electromagnetic Compatibility ImmunityTested in accordance with IEC/EN 61000-6-5: 2015 - Electromagnetic Compatibility (EMC) - Part 6-5: Generic standards immunity for equipment used in power Station and substation Discharge: IEC 61000-4-2, EN 61000-4-2 +6 kV Contact Discharge, +8 kV Air DischargeRadiated RF Immunity: IEC 61000-4-3, EN 61000-4-3, ENV 50204 10 V/m, GHz, 3 V/m, 1-6 GHzElectrical Fast Transient.
8 IEC 61000-4-4, EN 61000-4-4 + kV + 1 kV + 2 kV on AC lines, + kV + 1 kV + 2 kV on DC, I/O linesSurge Withstand Immunity: IEC 61000-4-5, EN 61000-4-5 + kV + 1 kV Differential Mode, + kV + 1 kV + 2 kV Common ModeConducted Disturbances Immunity: IEC 61000-4-6, EN 61000-4-6 10 V, MHz, on AC, DC 3 V, MHz, on I/O LinesMagnetic Field Immunity: IEC 61000-4-8, EN 61000-4-8 100A/m - Continuous, 1kA/m for 1 sec AC Voltage Dips/Short Interruption: IEC 61000-4-11, EN 61000-4-11 60% UT during 60 cycles, 30% UT during 1 cycleConducted RF Immunity, 15-150 KHz: IEC 61000-4-16, EN 61000-4-16 30 Vrms Continuous Disturbance on DC, I/O, 300 Vrms 1 sec Disturbance DC, I/ODamped Oscillatory Wave Immunity: IEC 61000-4-18, EN 61000-4-18 kV Common Mode (1 MHz) on AC/DC/I/O line, 1 kV Differential Mode (1 MHz) on AC/DC/I/O linesHarmonic Current Emissions.
9 IEC 61000-3-2, EN 61000-3-2 Class A (Other), Class B (Portable Equipment), Class C (Lighting Equipment)Voltage Fluctuation and Flicker: IEC 61000-3-3, EN 61000-3-3 EnvironmentalCold: IEC 61000-2-1, 18 hours at -40 CDamp Heat, Cyclic: IEC 61000-2-30, 25 C to 55 C, 6 cycles, Relative Humidity: 95%Dry Heat: IEC 61000-2-2, 18 hours at +70 CControl your critical network operations with confidenceWith Survalent , you can control your critical network operations with confidence. We re the most trusted provider of advanced distribution management systems (ADMS) for electric, water/wastewater, gas, and transit utilities across the globe.
10 Over 600 utilities in 30 countries rely on the SurvalentONE platform to effectively operate, monitor, analyze, restore, and optimize operations. By supporting critical utility operations with a fully integrated solution, our customers have significantly improved operational efficiencies, customer satisfaction and network unwavering commitment to excellence and to our customers has been the key to our success for over 50 years. 2018 Survalent Technology Corporation. All rights reserved. Product & company names mentioned herein may be trademarks or registered trademarks of their respective owners.