Seismic Design Requirements, H-18-8 - NEHRP

1 2 FOREWORD Background In 1971, after the San Fernando earthquake when two VA buildings collapsed, VA began to undertake a full Seismic safety program. Title 38 - United States Code, section 8105 required the Secretary to assure that each medical facility constructed or altered shall be of construction that is resistant to fire, earthquake, and other natural disasters. This initiated the creation of the Secretary s Advisory Committee on Structural Safety of VA Facilities, which formally approved in 1975 the original VA Seismic Design document, H-08-8, Earthquake Resistant Design Requirements for VA Facilities. These requirements were developed with the concept that all VA Essential Facilities must remain in operation after an earthquake and were far in advance of National Codes. This document is periodically updated and revised. The revision of H-08-8 to H-18-8 in 1995 was a major rewrite to bring VA Seismic Design requirements more in line with the updated national model codes.

Facilities assigned to Seismic Design Categories D, E, or F. a. Building Frame Systems i. Steel eccentrically braced frames (EBF) moment resisting connections at columns away from links ii. Special reinforced concrete shear walls (Building Frame) iii. Special reinforced masonry shear walls (Building Frame) iv. Special steel concentrically ...

Tags:

  Design, Seismic, Special, Concrete, Reinforced, Moment, Frame, Seismic design, Special reinforced concrete, Special reinforced

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of Seismic Design Requirements, H-18-8 - NEHRP

1 1 2 FOREWORD Background In 1971, after the San Fernando earthquake when two VA buildings collapsed, VA began to undertake a full Seismic safety program. Title 38 - United States Code, section 8105 required the Secretary to assure that each medical facility constructed or altered shall be of construction that is resistant to fire, earthquake, and other natural disasters. This initiated the creation of the Secretary s Advisory Committee on Structural Safety of VA Facilities, which formally approved in 1975 the original VA Seismic Design document, H-08-8, Earthquake Resistant Design Requirements for VA Facilities. These requirements were developed with the concept that all VA Essential Facilities must remain in operation after an earthquake and were far in advance of National Codes. This document is periodically updated and revised. The revision of H-08-8 to H-18-8 in 1995 was a major rewrite to bring VA Seismic Design requirements more in line with the updated national model codes.

2 Further updates/revisions of minor nature were made in 1997, 1998, 2000, 2002, 2003, 2005, 2006, 2008, 2010, and 2011. Current Revision Highlights: Reference of ASCE 396 changed to FEMA 396 Modified definition of Ancillary Facilities slightly to define them as non-essential. Modified sections to preclude exemption of non-structural elements in low seismicity and emphasize following section Note: A vertical bar is placed to the right of the revised sections. Lloyd H. Siegel August 2013 Associate Executive Director Office of Facilities Planning 3 TABLE OF CONTENTS Definitions .. 4 General .. 6 Modifications to Requirements of IBC for New Critical and Essential Facilities .. 8 Elements of Structures, Nonstructural Components, and Equipment Supported by Structures .. 11 Site Data for Critical and Essential Facilities .. 12 Commentary .. 14 Tables .. 16 Seismicity Map with Department of Veterans Affairs Medical Centers.

3 25 4 DEFINITIONS ASCE/SEI 41 06: Seismic Rehabilitation of Existing Buildings, American Society of Civil Engineers. AISC 341: Seismic Provisions for Structural Steel Buildings, including Supplement No. 1 dated 2006, American Institute of Steel Construction. ASCE 7: Minimum Design Loads for Buildings and Other Structures, American Society of Civil Engineers, Latest Edition ASCE 31- 02: Seismic Evaluation of Existing Buildings, American Society of Civil Engineers. FEMA 396: Incremental Seismic Rehabilitation of Hospital Buildings, American Society of Civil Engineers. Category of Facilities: a) Critical Facilities: Buildings that are required to remain functional after an earthquake or other natural disaster such as hurricane, tornado, etc. These facilities include, but are not limited to, the occupancy categories listed as Critical Facilities in Table 1, and they shall be assigned to IBC Occupancy Category IV.

4 B) Essential Facilities: Buildings that must remain operational with minor repairs after an earthquake or other natural disaster such as hurricane, tornado, etc. These facilities include, but are not limited to occupancy categories listed as Essential Facilities in Table 2, and they shall be assigned to IBC Occupancy Category III. c) Ancillary Facilities: These facilities include, but are not limited to, the occupancy categories listed as Ancillary Facilities in Table 3. All ancillary facilities shall be designated as non-essential facilities and shall be assigned to IBC Occupancy Category II. IBC: International Building Code, Latest Edition. Occupancy Category: A category used to determine earthquake Design loads based on the nature of the occupancy. OSHPD: Office of Statewide Health Planning & Development, State of California Seismic Design Category: A classification assigned to a structure based on its occupancy category and the severity of the Design earthquake ground motion at the site (as defined in IBC and ASCE 7).

5 5 Seismicity Region of Seismicity SS S1 Very High High < < Moderate High < < Moderate Low < < Low < < Note: Values for SS and S1 at all VA sites are given in Table 4 Soft Story & Extreme Soft Story: As defined in ASCE 7, Table Spectral Response Acceleration: A parameter used to characterize the anticipated earthquake shaking at a given site. (Table 4) Ss: Spectral acceleration parameter at short periods corresponding to the mapped maximum considered earthquake. S1: Spectral acceleration parameter at a period of 1 sec corresponding to the mapped maximum considered earthquake. 6 GENERAL These requirements cover all VA facilities including those of National Cemetery Administration, Veterans Benefits Administration, and Veterans Health Administration. New Critical and Essential Facilities All new Critical and Essential Facilities shall be designed and constructed in full compliance with the earthquake Design and detailing requirements of IBC as modified in these provisions.

6 Critical Facilities shall be assigned IBC Occupancy Category IV and Essential Facilities shall be assigned IBC Occupancy Category III. These buildings are intended to remain operational after an earthquake or other natural disaster such as tornado or hurricane as defined in ASCE 7, Section New Ancillary Facilities All new Ancillary Facilities shall be designed and constructed in full compliance with the earthquake Design and detailing requirements of IBC with no additional modifications. Ancillary Facilities shall be assigned to Occupancy Category II as defined in ASCE 7, Section Existing Facilities - Evaluation a. A Seismic evaluation shall be conducted for existing facilities in areas of Moderate High, High, and Very High Seismicity that meet one or more of the following criteria: i. Facilities selected for renovation as part of a VA classified Major Project ii. Facilities selected for renovation where the area of renovation is greater than 50% of the total area iii A project is planned which significantly extends the building s useful life through alterations or repairs which total more than 30% of the replacement value of the facility.

7 Iv. Facilities under consideration by VA for purchase or lease b. Existing Critical and Essential Facilities shall be evaluated using the procedures in ASCE 31-02 for the Immediate Occupancy Performance Level. c. Existing Ancillary Facilities shall be evaluated using the procedures in ASCE 31-02 for the Life Safety Performance Level. Existing Facilities Rehabilitation a. All Critical and Essential Existing Facilities shall be rehabilitated using nonlinear static procedures described in ASCE 41 to achieve the following rehabilitation objectives. 7 i. Immediate occupancy performance level at BSE-1 (Basic Safety Earthquake Level 1, Earthquake Hazard Level having a probability of exceedance of 10 percent in 50 years) as defined in ASCE 41. ii. Collapse Prevention performance level at BSE-2 (Basic Safety Earthquake Level 2, Earthquake Hazard Level having a probability of exceedance of 2 percent in 50 years) as defined in ASCE 41.

8 B. All Ancillary Facilities shall be rehabilitated using nonlinear static procedures described in ASCE 41 using the requirements to achieve Basic Safety Objectives. Existing Facilities Rehabilitation Alternative Approach An alternative approach may be permitted on a case-by-case basis upon approval by the Office of Construction & Facilities Management (CFM) for Critical and Essential Facilities to be strengthened according to procedures in ASCE 41. Spectral Response Accelerations The selection of Seismic Design Category for use in the Design and analysis of all new and existing facilities shall be based on the spectral response accelerations shown in Table 4 after adjustment for site class effects as specified in ASCE 7. For the Design of buildings in Seismic Design Category A, use ASCE 7 section For all other Seismic Design Categories (B F), use ASCE 7 Chapter 12: Seismic Design Requirements for Building Structures. 8 MODIFICATIONS TO THE REQUIREMENTS OF IBC FOR NEW CRITICAL AND ESSENTIAL FACILITIES ASSIGNED TO HIGH Seismic Design CATEGORIES Structural Irregularities (ASCE 7, Section ) For structures assigned to Seismic Design Categories D, E, or F, the following types of irregularities as defined by ASCE 7 Table & 2 are not allowed: a.

9 Stiffness irregularity Soft Story b. Stiffness irregularity Extreme Soft Story c. Weight (mass) irregularity d. Vertical geometric irregularity Seismic -force-resisting-systems (ASCE 7, Table ) The following structural systems are permitted for new Critical and Essential Facilities assigned to Seismic Design Categories D, E, or F. a. Building frame Systems i. Steel eccentrically braced frames (EBF) moment resisting connections at columns away from links ii. special reinforced concrete shear walls (Building frame ) iii. special reinforced masonry shear walls (Building frame ) iv. special steel concentrically braced frames v. Light frame walls with shear panels-wood structural panels/sheet steel panels (Building frame ) for structures two stories or less vi. Buckling-restrained braced frames, moment -resisting beam-column connections b. moment -Resisting frame Systems, if approved by VA. i. special steel moment -resisting frames (SMRF) ii. special reinforced concrete moment -resisting frames c.

10 Dual Systems i. special reinforced concrete shear walls with SMRF ii. special reinforced masonry shear walls with SMRF iii. Steel EBF with SMRF iv. special steel concentrically braced frame with SMRF v. Buckling-restrained braced frame Other structural systems as permitted by the IBC for Seismic Design Categories D, E or F, including ones that employ Seismic isolation and Seismic damping systems are permitted subject to written approval by the VA. 9 special Provisions for structures assigned to Seismic Design Categories D, E, or F. The provisions of this section shall apply to all new Critical and Essential Facilities. a. Bay spacing essentially shall be equal and uniform throughout. b. Transfer beams or trusses supporting upper level columns shall not be used unless permitted on a case by case basis by VA. c. Seismic joints shall be avoided, in so far as possible. When required, they shall be specifically identified in the schematic Design phase of the project and approved by VA, subject to the following provisions: 1.