1 I56-2769-022 5/22/2019 INSTALLATION AND MAINTENANCE INSTRUCTIONSS electable Output Strobes, Horns, and horn /Strobes3825 Ohio Avenue, St. Charles, Illinois 60174800/736-7672, FAX: 630 use with the following models: P2R, P2RH, P2RK, P2 RHK, P2W, P2WK, P2WH, P2 WHK, P4R, P4RH, P4RK, P4W, P4WK, P4 WHK-P, SR, SRH, SRK, SRHK, SW, SWK, SWH, SWHK, SW-CLR-ALERT, PC2R, PC2RH,PC2RK, PC2 RHK, PC2W, PC2WK, PC2WH, PC2 WHK, PC4R, PC4RH, PC4W, PC4WK, PC4 WHK, SCR, SCRH, SCRK, SCRHK, SCW, SCWK, SCWH, SC-WHK, SCW-CLR-ALERT, HR, HRK, HW, SR-P, SW-P, SRH-P, SWH-P,P2R-P, P2W-P, P2WH-P, P4R-P, P4W-P, SCW-P, PC2R-P, PC2W-P, PC2WH-P, SRK-P, SRHK-P, P2RK-P, P2 RHK-P, SWK-P, SWHK-P, P2WK-P, P2 WHK-P, SR-SP, P2R-SP, PC2W-SP, SRK-R, SWK-R, SRHK-R, SWHK-R, P2RK-R, P2WK-R, P2 RHK-R, P2 WHK-R, SBHK, SBK-R.

1 I56-2769-020R 06-10 INSTALLATION AND MAINTENANCE INSTRUCTIONS Selectable Output Strobes, Horns, and Horn/Strobes 3825 Ohio Avenue, St. Charles, Illinois 60174

Tags:

  Output, Horn, Strobe, Selectable, Selectable output strobes, And horn

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of Selectable Output Strobes, Horns, and Horn/Strobes

1 1 I56-2769-022 5/22/2019 INSTALLATION AND MAINTENANCE INSTRUCTIONSS electable Output Strobes, Horns, and horn /Strobes3825 Ohio Avenue, St. Charles, Illinois 60174800/736-7672, FAX: 630 use with the following models: P2R, P2RH, P2RK, P2 RHK, P2W, P2WK, P2WH, P2 WHK, P4R, P4RH, P4RK, P4W, P4WK, P4 WHK-P, SR, SRH, SRK, SRHK, SW, SWK, SWH, SWHK, SW-CLR-ALERT, PC2R, PC2RH,PC2RK, PC2 RHK, PC2W, PC2WK, PC2WH, PC2 WHK, PC4R, PC4RH, PC4W, PC4WK, PC4 WHK, SCR, SCRH, SCRK, SCRHK, SCW, SCWK, SCWH, SC-WHK, SCW-CLR-ALERT, HR, HRK, HW, SR-P, SW-P, SRH-P, SWH-P,P2R-P, P2W-P, P2WH-P, P4R-P, P4W-P, SCW-P, PC2R-P, PC2W-P, PC2WH-P, SRK-P, SRHK-P, P2RK-P, P2 RHK-P, SWK-P, SWHK-P, P2WK-P, P2 WHK-P, SR-SP, P2R-SP, PC2W-SP, SRK-R, SWK-R, SRHK-R, SWHK-R, P2RK-R, P2WK-R, P2 RHK-R, P2 WHK-R, SBHK, SBK-R.

2 NOTES: Refer to your panel documentation or models listed for use with specific panels. NOTE: All -R models are specifically designed for use with the WTP Series of Weatherproof plates. NOTE: When replacing outdoor units; device and back box must be : Models SBHK, SBK-R are UL listed for General SPECIFICATIONSO perating Temperature:Standard Products32 F to 120 F (0 C to 49 C)K Series 40 F to 151 FHumidity Range:Standard Products10 to 93% Non-condensingK SeriesMeets NEMA 4X requirementsStrobe Flash Rate:1 flash per secondNominal Voltage:Regulated 12 VDC/FWR or regulated 24DC/FWRO perating Voltage Range (includes fire alarm panels with built in sync):8 to (12V nominal) or 16 to 33V (24V nominal)Operating Voltage with MDL3 Sync to (12V nominal) or to 33V (24V nominal)Input terminal wire gauge:12 to 18 AWGNOTE : Strobes will operate at 12 V nominal for 15 & 15/75 candela settings only. Switching between ranges is FOR PRODUCTS AND ACCESSORIESWALL PRODUCTSL engthWidthDepthCEILING PRODUCTSDIAMETERDEPTHS trobe and Horn/Strobes (including lens) " " "Strobes and Horn/Strobes (including lens) " "142 mm119 mm64 mm173 mm64 " " "SA-WBBC Red Weatherproof Back " "142 mm119 mm33 mmSA-WBBCW White Weatherproof Back Box180 mm51 mmSA-WBB Red Weatherproof Back " " "SBBCR Red Surface Mount Box " "SA-WBBW White Weatherproof Back Box145 mm130 mm51 mmSBBCW White Surface Mount Box175 mm135 mmSBBR Red Surface Mount " " "NOTE.

3 SA-WBB, SA-WBBW, SA-WBBC and SA-WBBCW dimensions do not include the two mounting tabsSBBW White Surface Mount Box142 mm119 mm109 mmMOUNTING BOX OPTIONS2-Wire Indoor Products4-Wire Indoor ProductsK Series Products4 4 11/2, Single Gang, Double Gang, 4" Octagon SBBR/W (wall), SBBCR/W (ceiling)4 4 11/2, Double Gang, 4" OctagonSA-WBB/W (wall), SA-WBBC/CW (ceiling)GENERAL DESCRIPTIONThe SpectrAlert Advance series of notification appliances offers a wide range of horns, strobes, and Horn/Strobes , for wall and ceiling applications, indoors and outdoors. They are designed to be used on 12 or 24 volt, DC or FWR (full wave rectified) systems. These products are electrically backward compat-ible with the previous generation of SpectrAlert notification appliances. horn / strobe products are available in two versions. The 2-wire products fit systems where a single NAC controls both horn and strobe . The 4-wire products are in-tended for systems which have separate wiring circuits for the horn and strobe .

4 All SpectrAlert Advance products are suitable for use in synchronized systems. The System Sensor MDL3 module may be used to provide Series products are designed to be used over a wider range of temperatures and are suitable for use in wet environments with outdoor backbox supplied with product. Wall and ceiling products may be used interchangeably (wall products may be used on the ceiling and ceiling products may be used on the wall.)FIRE ALARM SYSTEM CONSIDERATIONSThe National Fire Alarm Code, NFPA 72, requires that all horns, used for building evacuation produce temporal coded signals. Signals other than those used for evacuation purposes do not have to produce the temporal coded sig-nal. System Sensor recommends spacing notification appliances in compli-ance with NFPA DESIGN AND WIRINGThe system designer must make sure that the total current drawn by the de-vices on the loop does not exceed the current capability of the panel supply, and that the last device on the circuit is operated within its rated voltage.

5 The current draw information for making these calculations can be found in the tables within this manual. For convenience and accuracy, use the voltage drop calculator on the System Sensor website ( ).When calculating the voltage available to the last device, it is necessary to consider the voltage drop due to the resistance of the wire. The thicker the wire, the smaller the voltage drop. Wire resistance tables can be obtained from electrical handbooks. Note that if Class A wiring is installed, the wire length may be up to twice as long as it would be for circuits that are not fault : The total number of strobes on a single NAC must not exceed 40 for 24 volt applications or 12 for 12 volt applications. Loop resistance on a single NAC should not exceed 120 ohms for 24 volt and 30 ohms for 12 volt : This manual shall be left with the owner/user of this equipment. 2 I56-2769-022 5/22/2019 CANDELA SELECTIONA djust the slide switch on the rear of the product to the desired candela set-ting in the small window on the front of the unit.

6 All products meet the light Output profiles specified in the appropriate UL Standards. See Figures 1-3. Use Table 1 to determine the current draw for each candela setting. For K series products used outdoors at low temperatures, listed candela ratings must be reduced in accordance with Table 2. NOTE: SpectrAlert products set at 15 and 15/75 candela automatically work on either 12V or 24V power supplies. The products are not listed for 12V op-erating voltages when set to any other candela settings. For 4-Wire products, total current draw may be determined by adding current draw for the specific candela selection and the current draw for the specific horn selection use Table 1 and Table 1. strobe CURRENT DRAW (mA) FOR S, SC, P4 & PC4 SERIESC andela8 Volts16 33 VoltsDCFWRDCFWRS tandard Candela Range15123128667115/75142148778130 NANA949675 NANA15815395 NANA181176110 NANA20219511 5 NANA210205 High Candela Range135 NANA228207150 NANA246220177 NANA2812 51185 NANA286258 TABLE 2.

7 CANDELA DERATINGL isted CandelaCandela rating at 40 F (K Series Outdoor Applications Only)15Do not use below 32 F15/75307544957011011011 511 5135135150150177177185185 horn SELECTIONTurn the rotary switch on the back of the product to the desired setting. For horn and 4-wire horn / strobe products, the current draw for each setting is listed in Table 3. For 2-wire horn / strobe products (P2 series), current draws are listed in Tables 4 and 5. The sound Output measurement for each horn setting is shown in Table 3. horn CURRENT DRAW (mA) FOR H, P4 & PC4 SERIESPosSound PatterndA Out8 Volts16 33 VoltsDCFWRDCFWR1 TemporalHigh575569752 TemporalMedium444958693 TemporalLow384444484 Non-temporalHigh575669755 Non-temporalMedium425060696 Non-temporalLow414450507 CodedHigh575569758 CodedMedium445156699 CodedLow40465250 NOTE: In positions 7, 8, and 9, temporal coding must be provided by the NAC. If the NAC voltage is held constant, the horn Output will remain constantly on.

8 Positions 7, 8, and 9 are not available on 2-wire horn / strobe 2. LIGHT Output - HORIZONTAL DISPERSIONF igures 1-3 list the minimum light Output requirements per 3. LIGHT Output - VERTICAL DISPERSION, WALL TO *Percent of Rating01005-259030-457550555545604065357 0357530803085259025 Compound 45 to the right24 Compound 45 to the right24 Degrees*Percent of Rating01005-3090356540464534502755226018 651670157513801285129012 Degrees*Percent of Rating01005-259030-457550556045653570357 530803085259025*Tolerance of 1 degree is 1. LIGHT Output - VERTICAL DISPERSION, CEILING TO WALLS TO FLOOR 3 I56-2769-022 5/22/2019 TABLE 4. 2-WIRE horn / strobe CURRENT DRAW (mA) FOR P2 AND PC2 STANDARD CANDELA SERIESDC Input8 Volts16 33 Volts15 cd15/75 cd15 cd15/75 cd30 cd75 cd95 cd110 cd115 cdTemporal High137147799010717619421 221 8 Temporal Medium132144698097157182201210 Temporal Low132143667793154179198207 Non-temporal High1411529110011 61762012 21229 Non-temporal Medium133145758510216318720721 6 Non-temporal Low1 31144687996156182201210 FWR InputTemporal High136155889711 216819021021 8 Temporal Medium1291527888103160184202206 Temporal Low1291 517686101160184194201 Non-temporal High14216110311 21261812032 21229 Non-temporal Medium134155859511016618920821 6 Non-temporal Low1321548090105161184202211 TABLE 5.

9 2-WIRE horn / strobe CURRENT DRAW (mA) FOR P2 AND PC2 HIGH CANDELA RANGE SERIESS ound Pattern16 33 Volts Volts DC16 33 Volts Volts FWR135 cd150 cd177 cd185 cd135 cd150 cd177 cd185 cdTemporal High24525929029721 52 31258265 Temporal Medium235253288297209224250258 Temporal Low2322 512822922072 21248256 Non-temporal High255270303309233248275281 Non-temporal Medium24225929329921 9232262267 Non-temporal Low23825429129521 4229256262 TABLE 6. horn Output (dBA) IN UL REVERBERANT ROOM Switch PositionSound PatternVolume Setting8 Volts**16 33 Volts**24 V Nominal MeasurementsReverberantAnechoicDCFWRDCFW RDCFWRDCFWR1 TemporalHigh78788484888899982 TemporalMedium75758080868596963 TemporalLow71717676817994894 Non-temporalHigh8282888893921001005 Non-temporalMedium78788585908998986 Non-temporalLow73748181868496927*CodedHi gh8282888893921011018*CodedMedium7878858 5908997989*CodedLow7475818185839692* horn & 4-wire horn / strobe only. ** Minimum dBA rating for Operational Voltage Range as per UL 4.

10 WIRING 2-WIRE PRODUCTS+ + INPUT FROM FACPOR PRIOR DEVICE Output TO NEXTDEVICE OR EOLA0367-01 FIGURE 5. WIRING 4-WIRE PRODUCTS+ INPUT FROM FACP OR PRIOR STROBEINPUT FROMFACP OR PRIOR horn + + + Output TO NEXT strobe OR EOLOUTPUT TO NEXT horn OR EOLA0366-00 FIGURE 6. SHORTING SPRINGSHORTING SPRINGA0368-00 For 4-Wire installations, terminals 1, 2, and 3 connect to the strobe ; terminals 4 and 5 connect to the horn . The horn and strobe circuits must be wired in-dependently, and each circuit must be terminated with the appropriate EOL device. Removal of a notification device will result in an open circuit indica-tion on the strobe : A shorting spring is provided between terminals 2 and 3 of the mount-ing plate to enable wiring checks after the system has been wired, but prior to installation of the final product. This spring will automatically disengage when the product is installed, to enable supervision of the final system. Only available on indoor products(non K-series).