Series 2330 MKII Single-Phase Adjustable-Speed DC Motor Controllers (1/6 3 HP) BOOK0958-A BOOK0958-ARev. 05/04 Series 2330 MKIISINGLE-PHASEADJUSTABLE-SPEEDDC Motor Controllers (1/6 - 3 HP)BOOK0958-AiiiTABLE OF CONTENTSSECTIONTITLEPAGEIGENERAL INFORMATION1 Introduction1 General Description1 Model Types1 Motor Selection2 IIINSTALLATION3 Installation Guidelines3 Installing The Controller5 Initial Startup15 IIIOPERATION16 Power On/Off16 Run16 Stop16 speed Control17 Jog17 Reverse17 Inoperative Motor17 IVMAINTENANCE AND REPAIR18 General18 Adjustment Instructions18 Troubleshooting21 VPARTS LIST25 VIRATINGS AND SPECIFICATIONS27 Ratings27 Operating Conditions28 Performance Characteristics28 Adjustments29 Specifications29 VIIDRAWINGS31 INDEX34 BOOK0958-AivLIST OF TABLESTABLETITLEPAGE1 Series 2330 MKII Model Matrix12 Jumper J4 Position53 Dip Switch (SW3)

BOOK0958-A 1 SECTION I GENERAL INFORMATION INTRODUCTION This manual contains installation, operation, and maintenance and repair instructions for Fincor Series 2330

Tags:

  Manual, Controller, Series, Motor, Speed, 3302, Adjustable, Series 2330mkii adjustable speed dc motor controllers, 2330mkii, Fincor

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of Series 2330MKII Adjustable-Speed DC Motor Controllers …

1 Series 2330 MKII Single-Phase Adjustable-Speed DC Motor Controllers (1/6 3 HP) BOOK0958-A BOOK0958-ARev. 05/04 Series 2330 MKIISINGLE-PHASEADJUSTABLE-SPEEDDC Motor Controllers (1/6 - 3 HP)BOOK0958-AiiiTABLE OF CONTENTSSECTIONTITLEPAGEIGENERAL INFORMATION1 Introduction1 General Description1 Model Types1 Motor Selection2 IIINSTALLATION3 Installation Guidelines3 Installing The Controller5 Initial Startup15 IIIOPERATION16 Power On/Off16 Run16 Stop16 speed Control17 Jog17 Reverse17 Inoperative Motor17 IVMAINTENANCE AND REPAIR18 General18 Adjustment Instructions18 Troubleshooting21 VPARTS LIST25 VIRATINGS AND SPECIFICATIONS27 Ratings27 Operating Conditions28 Performance Characteristics28 Adjustments29 Specifications29 VIIDRAWINGS31 INDEX34 BOOK0958-AivLIST OF TABLESTABLETITLEPAGE1 Series 2330 MKII Model Matrix12 Jumper J4 Position53 Dip Switch (SW3)

2 64 Initial Potentiometer Settings155 Dynamic Braking Characteristics166 Troubleshooting21-247 Parts List, Series 2330 MKII Controllers258 Typical Application Data279 Operating Voltages And Signals2810 controller Weights2811 speed Regulation Characteristics2912 Shunt Field Data3013 Tachometer Feedback Voltage Selection30 LIST OF ILLUSTRATIONSFIGURETITLEPAGE1 controller Mounting Configurations72 controller Mounting Dimensions83 Logic Connection Diagram, Run-Stop-Jog9 Switch4 Logic Connection Diagram, Forward-Reverse9 Switch And Run-Stop-Jog Switch5 Logic Connection Diagram, Run-Stop Pushbuttons10 And Run-Jog Switch,6 Logic Connection Diagram, Optional Armature10 Contactor Reversing Using Switches7 Logic Connection Diagram, Optional Armature11 Contactor Reversing Using Pushbuttons And Run-Jog Switch8 Logic Connection Diagram, Line Starting With11 Motor speed Potentiometer9 Signal Connection Diagram, Motor Speed12 Potentiometer10 Signal Connection Diagram, Tachometer Feedback1211 Signal Connection Diagram, Current (Torque)

3 12 Reference Potentiometer12 Signal Connection Diagram, Line Starting Without13 A Motor speed Potentiometer13 Signal Connection Diagram, 4-20mA Interface1314 Signal Connection Diagram, 4-20mA Transducer with Auto/ manual Switch1315 Signal Connection Diagram, Transducer with ExternalBurden Resistor1416 Signal Connection, 0-10 VDC External speed Reference1417 Functional Schematic, Series 2330 MKII3218 Series 2330 MKII Control Board, 1/6 - 3 HP33 BOOK0958-AvBlank PageBOOK0958-AviWARNINGThe following must be strictly adhered to at all YOU AS THE OWNER OR OPERATOR OF fincor EQUIPMENT HAVE THE RESPONSIBILITYTO HAVE THE USERS OF THIS EQUIPMENT TRAINED IN ITS OPERATIONS AND WARNED OFANY POTENTIAL HAZARDS OF SERIOUS THE DRIVE EQUIPMENT SHOULD BE INSTALLED, OPERATED, ADJUSTED, AND SERVICEDONLY BY QUALIFIED PERSONNEL FAMILIAR WITH THE CONSTRUCTION AND OPERATIONOF THE EQUIPMENT AND THE HAZARDS INVOLVED INCLUDING THOSE DESCRIBEDBELOW.

4 FAILURE TO OBSERVE THIS WARNING CAN RESULT IN PERSONAL INJURY, LOSSOF LIFE, AND PROPERTY THE NATIONAL ELECTRICAL CODE REQUIRES THAT AN AC LINE FUSED DISCONNECT ORCIRCUIT BREAKER BE PROVIDED IN THE AC INPUT POWER LINES TO THE DISCONNECT MUST BE LOCATED WITHIN SIGHT OF THE controller . DO NOTOPERATE THE controller UNTIL THIS CODE REQUIREMENT HAS BEEN THE DRIVE EQUIPMENT IS AT AC LINE VOLTAGE WHENEVER AC POWER IS CONNECTEDTO THE DRIVE EQUIPMENT. CONTACT WITH AN ELECTRICAL CONDUCTOR INSIDE THEDRIVE EQUIPMENT OR AC LINE DISCONNECT CAN CAUSE ELECTRIC SHOCK RESULTINGIN PERSONAL INJURY OR LOSS OF BE SURE ALL AC POWER IS DISCONNECTED FROM THE DRIVE EQUIPMENT BEFORETOUCHING ANY COMPONENT, WIRING, TERMINAL, OR ELECTRICAL CONNECTION IN THEDRIVE ALWAYS WEAR SAFETY GLASSES WHEN WORKING ON THE DRIVE DO NOT REMOVE OR INSERT CIRCUIT BOARDS, WIRES, OR CABLES WHILE AC POWER ISAPPLIED TO THE DRIVE EQUIPMENT.

5 FAILURE TO OBSERVE THIS WARNING CAN CAUSEDRIVE DAMAGE AND PERSONAL ALL DRIVE EQUIPMENT ENCLOSURES, Motor FRAMES, AND REMOTE OPERATORSTATIONS MUST BE CONNECTED TO AN UNBROKEN COMMON GROUND CONDUCTOR. ANUNBROKEN GROUNDING CONDUCTOR MUST BE RUN FROM THE COMMON GROUNDCONDUCTOR TO A GROUNDING ELECTRODE BURIED IN THE EARTH OR ATTACHED TO APLANT GROUND. REFER TO THE NATIONAL ELECTRICAL CODE AND LOCAL CODES FORGROUNDING THE ATMOSPHERE SURROUNDING THE DRIVE EQUIPMENT MUST BE FREE OFCOMBUSTIVE VAPORS, CHEMICAL FUMES, OIL VAPOR, AND ELECTRICALLY CONDUCTIVEOR CORROSIVE SOLID-STATE DEVICES IN THE controller CAN BE DESTROYED OR DAMAGED BYSTATIC ELECTRICITY.

6 THEREFORE, PERSONNEL WORKING NEAR THESE STATIC-SENSITIVE DEVICES MUST BE APPROPRIATELY IGENERAL INFORMATIONINTRODUCTIONThis manual contains installation, operation, and maintenance and repair instructions for fincor Series 2330 MKII Single-Phase Adjustable-Speed DC Motor Controllers . A parts list, ratings and specifications, and drawings arealso DESCRIPTIONS eries 2330 MKII Controllers statically convert AC line power to regulated DC for Adjustable-Speed armaturecontrol of shunt-wound and permanent-magnet 2330 MKII Controllers comply with applicable standards established by the National Electrical Code andNEMA for Motor and industrial control equipment. The Controllers are Underwriters Laboratories Listed (File ).

7 MODEL TYPESTABLE 1. Series 2330 MKII MODEL MATRIXMODELFUNCTIONCONFIGURATIONOPERATOR CONTROLSPOWERSOURCEa &HP RANGEa. Units are reconnectableRUN-STOPbb. No armature contactorRUN-STOP-DBcARMATURESWITCHREVER SEbARMATURECONTACTAND DBcARMATURECONTACTREVERSEAND DBcOPENCHASSISENCLOSEDLOCALINTEGRALREMOT E115V230V23312335 XXX1/6 - 1 1/3 - 22331P0 XXX2331P1 XXX2331P2 XXX2331A2335 AXXXX2331AP0 XXXX2331AP3 XXdXX2331 BXXXX2331BP0 XXX X2331BP1 XXXX23322336 XXX1/6 - 1 1/3 - 32332A2336 AXXXX2332 BXXXXBOOK0958-A2 Motor SELECTIONS eries 2331 MKII Controllers control the operation of general purpose DC motors designed for use with solid-state rectified power supplies. The Motor may be shunt-wound, stabilized shunt-wound, or permanent magnet.

8 Formaximum efficiency, the Motor should be rated for operation from a NEMA Code K power supply. BOOK0958-A3 SECTION IIINSTALLATIONB efore starting the installation, read this section thoroughly. In addition, a through review of the Ratings AndSpecifications (Section VI) is recommended. The following installation guidelines should be kept in mind when install-ing the GUIDELINES1. controller MOUNTING - The controller may be mounted either vertically or horizontally. However,never mount the controller upside down, immediately beside or above heat generating equipment, or directlybelow water or steam pipes. The controller must be mounted in a location free of Controllers may be mounted side by side, as close to each other as the mounting feet will allow.

9 The minimum clearance at the top and bottom of the controller may be as narrow as the conduit fittings ATMOSPHERE - The atmosphere surrounding the controller must be free of combustible vapors, chemicalfumes, oil vapor, and electrically conductive or corrosive air surrounding an enclosed controller must not exceed 40 degrees C (104 degrees F), and the air surround-ing an open-chassis controller must not exceed 55 degrees C (131 degrees F). Minimum air temperature is 0degree C (32 degrees F) for enclosed and open-chassis controller CONSTRUCTION - The controller base is made of die-cast aluminum with a poweredepoxy finish, and the cover is made of a die-cast aluminum controller enclosure is totally enclosed, nonventilated, and complies with NEMA Type 4 and 12 is an oil resistant synthetic rubber gasket between the cover and base.

10 Those models with integral opera-tor controls include flexible boots to seal the switches, and a seal for the Motor speed LINE SUPPLY - The controller should not be connected to a line supply capable of supplying more than100,000 amperes short-circuit current. Short-circuit current can be limited by using an input supply trans-former of 50 KVA or less, or by using correctly sized current limiting fuses in the supply line ahead of the con-troller. Do not use a transformer with less than the minimum transformer KVA listed in Table 8, page rated line voltage is not available, a line transformer will be required. If the line supply comes directly froma transformer, place a circuit breaker or disconnect switch between the transformer secondary and the control-ler.