Example: barber

Series TY-FRB — 40, 60, 80 and 115 K-factor Upright ...

1 of 10 March, 2007 TFP171_ENGeneral DescriptionThe Series TY-FRB , 40, 60, 80 and 115 K-factor , Upright and Pendent Sprinklers de-scribed in this data sheet are quick response - standard coverage, decorative 3 mm glass bulb type spray sprinklers designed for use in light or ordinary hazard, commercial oc-cupancies such as banks, hotels, shopping malls, etc. The recessed version of the Series TY-FRB Pendent Sprinkler, where applicable, is intended for use in areas with a finished ceiling. It uses either a two-piece Style 10 (1/2 NPT) or Style 40 (3/4 NPT) Recessed Escutcheon with 12,5 mm (1/2 ) of recessed adjustment or up to 19 mm (3/4 ) of total adjustment from the flush pendent posi-tion, or a two-piece Style 20 (1/2 NPT) or Style 30 (3/4 NP)

http://www.tyco-fireproducts.com Page 1 of 10 March, 2007 TFP171_EN General Description The Series TY-FRB, 40, 60, 80 and 115 K-

Tags:

  Series

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of Series TY-FRB — 40, 60, 80 and 115 K-factor Upright ...

1 1 of 10 March, 2007 TFP171_ENGeneral DescriptionThe Series TY-FRB , 40, 60, 80 and 115 K-factor , Upright and Pendent Sprinklers de-scribed in this data sheet are quick response - standard coverage, decorative 3 mm glass bulb type spray sprinklers designed for use in light or ordinary hazard, commercial oc-cupancies such as banks, hotels, shopping malls, etc. The recessed version of the Series TY-FRB Pendent Sprinkler, where applicable, is intended for use in areas with a finished ceiling. It uses either a two-piece Style 10 (1/2 NPT) or Style 40 (3/4 NPT) Recessed Escutcheon with 12,5 mm (1/2 ) of recessed adjustment or up to 19 mm (3/4 ) of total adjustment from the flush pendent posi-tion, or a two-piece Style 20 (1/2 NPT) or Style 30 (3/4 NPT) Recessed Escutcheon with 1/4 (6,4 mm) of recessed adjustment or up to 12,5 mm (1/2 )

2 Of total adjustment from the flush pendent adjust-ment provided by the Recessed Escutcheon reduces the accuracy to which the fixed pipe drops to the sprinklers must be cut. Corrosion resistant coatings, where applica-ble, are utilized to extend the life of copper alloy sprinklers beyond that which would otherwise be obtained when exposed to corrosive atmospheres. Although corrosion resistant coated sprinklers have passed the standard corrosion tests of the applicable approval agencies, the testing is not rep-resentative of all possible corrosive atmos-pheres.

3 Consequently, it is recommended that the end user be consulted with respect to the suitability of these coatings for any given corrosive environment. The effects of ambient temperature, concentration of chemicals, and gas/chemical velocity, should be considered, as a minimum, along with the corrosive nature of the chemical to which the sprinklers will be exposed. Intermediate level versions of the Series TY-FRB Pendent Sprinklers are detailed in Technical Data Sheet TFP356, and Sprinkler Guards are detailed in Technical Data Sheet Series TY-FRB Sprinklers described herein must be installed and maintained in compli-ance with this document, as well as with the applicable standards of the National Fire Protection Association, in addition to the standards of any other authorities having ju-risdiction.

4 Failure to do so may impair the performance of these owner is responsible for maintaining their fire protection system and devices in proper operating condition. The installing contrac-tor or sprinkler manufacturer should be con-tacted with any questions. IMPORTANTA lways refer to Technical Data Sheet TFP700 for the INSTALLER WARNING that provides cautions with respect to handling and installation of sprinkler systems and components. Improper handling and installation can perma-nently damage a sprinkler system or its components and cause the sprin-kler to fail to operate in a fire situa-tion or cause it to operate TY-FRB 40, 60, 80 and 115 K-factor Upright , Pendent, and Recessed Pendent Sprinklers Quick Response, Standard CoverageModel/Sprinkler Identification NumbersTY1131 - Upright 40K, 1/2 NPTTY1231 - Pendent 40K, 1/2 NPTTY2131 - Upright 60K, 1/2 NPTTY2231 - Pendent 60K, 1/2 NPTTY3131 - Upright 80K.

5 1/2 NPTTY3231 - Pendent 80K, 1/2 NPTTY4131 - Upright 115K, 3/4 NPTTY4231 - Pendent 115K, 3/4 NPTTY4831 - Upright 115K, 1/2 NPTTY4931 - Pendent 115K, 1/2 NPTG eneralDescriptionThe Series TY-FRB , , , , K-factor , Upright and PendentSprinklers described in this data sheetare quick response - standard cover-age, decorative 3 mm glass bulb typespray sprinklers designed for use inlight or ordinary hazard, commercialoccupancies such as banks, hotels,shopping malls, recessed version of the SeriesTY-FRB Pendent Sprinkler, where ap-plicable, is intended for use in areaswith a finished ceiling.

6 It uses either atwo-piece Style 10 (1/2 inch NPT) orStyle 40 (3/4 inch NPT) Recessed Es-cutcheon with 1/2 inch (12,7 mm) ofrecessed adjustment or up to 3/4 inch(19,1 mm) of total adjustment from theflush pendent position, or a two-pieceStyle 20 (1/2 inchNPT) or Style 30(3/4inch NPT) Recessed Escutcheon with1/4 inch (6,4 mm) of recessed adjust-ment or up to 1/2 inch (12,7 mm) oftotal adjustment from the flush the Recessed Escutcheon reducesthe accuracy to which the fixed pipedrops to the sprinklers must be resistant coatings, whereapplicable, are utilized to extend thelife of copper alloy sprinklers beyondthat which would otherwise be ob-tained when exposed to corrosive at-mospheres.

7 Although corrosion resis-tant coated sprinklers havepassed thestandard corrosion tests of the appli-cable approval agencies, the testing isnot representative of all possible cor-rosive atmospheres. Consequently, itis recommended that the end user beconsulted with respect to the suitabilityof these coatings for any given corro-sive environment. The effects of ambi-ent temperature, concentration ofchemicals, and gas/chemical velocity,should be considered, as a minimum,along with the corrosive nature of thechemical to which the sprinklers will intermediate level versions of theSeries TY-FRB Pendent Sprinklers aredetailed in Technical Data SheetTFP356, and Sprinkler Guards are de-tailed in Technical Data Sheet TFP780 WARNINGSThe Series TY-FRB Sprinklers de-scribed herein must be installed andmaintained in compliance with thisdocument.

8 As well as with the applica-ble standards of the National Fire Pro-tection Association, in addition to thestandards of any other authorities hav-ing to do so mayimpair the performance of these owner is responsible for maintain-ing their fire protection system and de-vices in proper operating installing contractor or sprinklermanufacturer should be contactedwith any - Upright , 1/2"NPTTY1231 - Pendent , 1/2"NPTTY2131 - Upright , 1/2"NPTTY2231 - Pendent , 1/2"NPTTY3131 - Upright , 1/2"NPTTY3231 - Pendent , 1/2"NPTTY4131 - Upright , 3/4"NPTTY4231 - Pendent , 3/4"NPTT echnicalDataApprovalsUL and C-UL , LPCB, and NYC Approved.

9 (RefertoTable Aforcomplete approvalinformation including corrosion resis-tant status.)Maximum Working Pressure175 psi (12,1 bar)Discharge CoefficientK = GPM/psi1/2(40,3 LPM/bar1/2)K = GPM/psi1/2(60,5 LPM/bar1/2)K = GPM/psi1/2(80,6 LPM/bar1/2)K = GPM/psi1/2(115,2 LPM/bar1/2)Temperature RatingsRefer to Table A and BSeries TY-FRB , , , and K-factorUpright, Pendent, and Recessed Pendent SprinklersQuick Response, Standard CoveragePage 1 of 8 TFP171 JULY, 2004 Technical Services:Tel: (800) 381-9312 / Fax: (800) 791-5500 IMPORTANTA lways refer to Technical DataSheet TFP700 for the INSTALLERWARNING that provides cautionswith respect to handling and instal-lation of sprinkler systems and com-ponents.

10 Improper handling and in-stallation can permanently damagea sprinkler system or its compo-nents and cause the sprinkler to failto operate in a fire situation or causeit to operate 2 of 10 TFP171_ENFinishesSprinkler: Refer to Table A and BRecessed Escutcheon: White Coated,Chrome Plated, or Brass PlatedPhysical CharacteristicsFrame .. BronzeButton .. Brass/CopperSealing Assembly .. Beryllium Nickel w/Teflon Bulb .. GlassCompression Screw .. BronzeDeflector .. Copper/BronzeBushing (K= ) .. BronzeOperationThe glass Bulb contains a fluid whichexpands when exposed to heat.