Service Information Type VXE Electronic Recloser …

Type VXE Electronic Recloser Control TesterOperation InstructionsReclosersService InformationSafety Statement Definitions ..2 Safety Instructions ..2 Product ..3 Acceptance and Initial Inspection ..3 Handling and Storage ..3 Quality Standards ..3 Description .. of the VXE Recloser andRecloser Control from Service ..6 Recloser Tests ..6 Control Tests ..7 VXE SCADA Tests ..11 ContentsS280-16-4 Printed in USA1 January 2001 Supersedes 2/98 Figure Type VXE Electronic Recloser Control VXE Electronic Recloser Control Tester Operation Instructions2 The instructions in this manual are not intended as a sub-stitute for proper training or adequate experience in thesafe operation of the equipment described. Only compe-tent technicians who are familiar with this equipmentshould install, operate, and Service competent technician has these qualifications: Is thoroughly familiar with these instructions. Is trained in industry-accepted high- and low-voltagesafe operating practices and procedures.

Introduction Service Information S280-16-4 provides operating instructions for the Type VXE Electronic Recloser Control Tester. Before operating this unit, carefully read and

Tags:

  Recloser

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Advertisement

Transcription of Service Information Type VXE Electronic Recloser …

1 Type VXE Electronic Recloser Control TesterOperation InstructionsReclosersService InformationSafety Statement Definitions ..2 Safety Instructions ..2 Product ..3 Acceptance and Initial Inspection ..3 Handling and Storage ..3 Quality Standards ..3 Description .. of the VXE Recloser andRecloser Control from Service ..6 Recloser Tests ..6 Control Tests ..7 VXE SCADA Tests ..11 ContentsS280-16-4 Printed in USA1 January 2001 Supersedes 2/98 Figure Type VXE Electronic Recloser Control VXE Electronic Recloser Control Tester Operation Instructions2 The instructions in this manual are not intended as a sub-stitute for proper training or adequate experience in thesafe operation of the equipment described. Only compe-tent technicians who are familiar with this equipmentshould install, operate, and Service competent technician has these qualifications: Is thoroughly familiar with these instructions. Is trained in industry-accepted high- and low-voltagesafe operating practices and procedures.

2 Is trained and authorized to energize, de-energize,clear, and ground power distribution equipment. Is trained in the care and use of protective equipmentsuch as flash clothing, safety glasses, face shield,hard hat, rubber gloves, hotstick, is important safety Information . For safe instal-lation and operation of this equipment, be sure to readand understand all cautions and InstructionsFollowing are general caution and warning statementsthat apply to this equipment. Additional statements, relat-ed to specific tasks and procedures, are located through-out the INFORMATIONWARNING: This equipment is not intended toprotect human life. Follow all locally approved pro-cedures and safety practices when installing or operat-ing this equipment. Failure to comply can result indeath, severe personal injury and equipment !DANGER: Hazardous voltage. Contact withhazardous voltage will cause death or severepersonal injury.

3 Follow all locally approved safety pro-cedures when working around high and low voltagelines and equipment. !WARNING: Before installing, operating, main-taining, or testing this equipment, carefully readand understand the contents of this manual. Improperoperation, handling or maintenance can result in death,severe personal injury, and equipment !WARNING: Power distribution equipment mustbe selected for the intended application. It mustbe installed and serviced by competent personnel whohave been trained and understand proper safety proce-dures. These instructions are written for such personneland are not a substitute for adequate training and expe-rience in safety procedures. Failure to properly select,install, or maintain this equipment can result in death,severe personal injury, and equipment !SAFETY FOR LIFEC ooper Power Systems products meet or exceed all applicable industry standards relating to product safety.

4 We activelypromote safe practices in the use and maintenance of our products through our Service literature, instructional trainingprograms, and the continuous efforts of all Cooper Power Systems employees involved in product design, manufacture,marketing, and strongly urge that you always follow all locally approved safety procedures and safety instructions when workingaround high voltage lines and equipment and support our Safety For Life mission.!SAFETYFOR LIFE!SAFETYFOR LIFEThis manual may contain four types of hazardstatements:DANGER: Indicates an imminently haz-ardous situation which, if not avoided, willresult in death or serious : Indicates a potentially hazardoussituation which, if not avoided, could result indeath or serious : Indicates a potentially hazardoussituation which, if not avoided, may result inminor or moderate : Indicates a potentially hazardous situ-ation which, if not avoided, may result in equip-ment damage only.

5 !!Hazard Statement Definitions!IntroductionService Information S280-16-4 provides operatinginstructions for the Type VXE Electronic Recloser ControlTester. Before operating this unit, carefully read andunderstand the contents of this Information contained in this manual is organizedinto the following major categories: Safety Information ,Product Information , Specifications, Description ofTester, and Operating Procedures. Refer to the table ofcontents for page This Manual FirstRead and understand the contents of this manual and fol-low all locally approved procedures and safety practicesbefore operating this InformationThese instructions cannot cover all details or variations inthe equipment, procedures, or process described, norprovide directions for meeting every possible contin-gency during installation, operation, or additional Information is desired to satisfy a prob-lem not covered sufficiently for the user's purpose,please contact your Cooper Power and InitialInspectionThis test set is completely assembled, inspected, adjust-ed, and tested at the factory.

6 It is in good condition whenaccepted by the carrier for receipt, inspect the test set thoroughly for damageand loss of parts incurred during shipment. If damage ormissing parts are discovered, file a claim immediatelywith the and StorageBe careful during handling and storage of the Type VXER ecloser Control Tester to minimize the possibility of dam-age. If the tester is to be stored for any length of time priorto use, provide a clean, dry storage StandardsThe Quality System at the Cooper Power Systems KyleDistribution Switchgear plant is certified to the followingstandards:ISO 9001, 1994 CAN/CSA ISO 9001, 1994BS EN ISO 9001, 1994 ANSI/ASQC Q9001, 1994 DescriptionThe Kyle Type VXE Electronic Recloser control tester(Figure 1) is designed specifically for testing the Kyle TypeVXE electronically controlled vacuum single-phase reclos-er. The tester has the capability to check the complete thefollowing tests: Recloser Tests Control Tests Battery Test Minimum-Trip Test Control Operation Test Time-Current Curve Characteristics Test Minimum Response Time Time-Current Curve Characteristics Modifier Reclosing Time Test Reset Time Test Cold Load Time Test VXE SCADA TestsThe unit is self-contained and packaged in a carryingcase with detachable cover.

7 Control tester, cable, case,power cable, cable interface, SCADA cable, and exten-der cable are supplied with the tester and stored in thecarrying tester can check the operation of the electronicrecloser control and the electrical operation of the reclos-er with the exception of high voltage closing. However,the control cannot operate the Recloser through Recloser -simulator circuit is built into the tester to simu-late Recloser operation (indicated by red and green LEDindicators on the tester panel labeled Recloser SIMU-LATOR) and to simulate the response time of the reclos-er mechanism to trip and close signals. The RECLOSERSIMULATOR provides a time delay to duplicate the inter-rupting time of a Type VXE Recloser in response to a tripsignal from the control when Recloser clearing time testsare being !SAFETYFOR LIFEPRODUCT INFORMATIONI nput120 Vac, 50/60Hz, single phase (fused for two amp) with10-ft power cord and a three wire grounding , 50/60Hz, single phase (fused for one amp) with10-ft power cord with no plug attached is available as 2000mA continuously adjustable from front panel ScaleAn LED scale meter shows the voltage level supplied tothe control ranging from volts, in increments , and also displays battery MeterAn LCD display for monitoring fault current is providedwhich has a 3% ( 5% at 5 amps) tolerance at full switched ranges are: 0 20/200/ Extender CableNote:Jacks on the tester panel provide the means for con-necting an external ammeter into the circuit.

8 They maybe used for verifying the internal LCD digital clock timer with automatic reset is includ-ed with a display ranging from to seconds second increments. Accuracy is 1% with the lastdigit being Cables (10ft.) cable for connecting Electronic control totester. (10ft.) cable for connecting Electronic controlwith SCADA. (10ft.) tester to Recloser extender Power CordA 305m (10ft) power cord is :Connector terminals on all cables are polarized toassure proper interconnection. An internal buzzer willsound if a mismatch between grounds on the VXEtester and wall outlet CaseThe tester is packaged in a carrying case with detachablecover, and has a compartment for storing the power cord,interconnecting cables, and spare fuses (spare fuses arenot included).Dimensions (Approximate)Unit Size (Overall) 254 mm (10 in.) high 457mm (18 in.) wide 305 mm (12 in.) deepWeight (Approximate)Net 15 kg (33 lbs.)

9 Type VXE Electronic Recloser Control Tester Operation Instructions4 SPECIFICATIONST able 1 lists and describes the operating controls andinstrumentation of the tester. All the devices are mounted on the front panel and are keyed to Figure 2, a close-upview of the front panel. Reference designations arelabeled on the front panel of the !SAFETYFOR LIFEI ndex No.(Figure 2)DescriptionPurpose and Use1 Power SwitchEnergizes AC Input to Tester2 Battery Test ButtonChecks Battery Voltage Under Load3AC ConnectionConnection from Tester to Wall Outlet4 Control/Battery VoltageMeasures the Control and Battery Voltage5 Control Current TerminalsTerminals for External Meter6 Recloser Cable ReceptacleInterface for Recloser Test Cable7 Simulated Line Current DisplayMeasures Simulated Line Current and Displays8 TimerMeasures Time of Test9 Control Cable ReceptacleInterface for Control Test Cable10 SCADA Cable ReceptacleInterface for SCADA Test Cable11 Not Lockout LEDI ndicates Control Not Locked Out12 Reclose Mode LEDI ndicates Control in Reclosing Mode13 Close LEDI ndicates Control is Closed14 Lockout LEDI ndicates Control is Locked Out15 Close W/Cold Load ButtonClose Control w/Cold Load via SCADA16 Trip and Lockout ButtonTrip and Lockout Control via SCADA17 External Meter JacksConnecting External Meters for Verification18 Non-Reclose

10 SwitchActivates/Deactivates Non-Reclose via SCADA19 Test Select SwitchSelects use of actual Recloser or Recloser simulator for testing20 Clock Reset ButtonResets Time21 Fault Time Select SwitchReacts on Clearing or Response Curves22 Time Select SwitchSelect Reclose or Fault Timer23 Close ButtonCloses Recloser or Control via Tester24 Open ButtonOpens Recloser or Control via Tester25 Fault SwitchApplies a Fault or Calibrates Current26 Fault LEDI ndicates a Fault Current27 Ammeter RangeSelects Range Dial28 Current AdjusterAdjusts Current Level29 Control Power SwitchInternal Power Supply for TCC Verification30 Meter Fuse (2A-260V)Protects LED Meter31 Close LEDI ndicates Recloser or Control Closed32 Open LEDI ndicates Recloser or Control OpenTABLE 1 Description and Use of Operating Controls, and IdentificationTYPE VXE CONTROL TESTERTO CONTROLTO SCADATO RECLOSERC ooper Power SystemsQuality fromCooper IndustriesKyle Distribution SwitchgearBATTERY TESTCONTROL CURRENT(100 TO 350 mA DC)(CONTROL POWER ON)CONTROL VOLTAGENORMALREPLACEBATTERYVOLTAGECONTRO L (NORMAL) POWER(REQ'D FOR )ONOFF120V (2A)CURRENT ADJUSTAMMETER RANGE 2000A200A20 AMAIN POWER ONOFFIf buzzer soundswall outlet iswired incorrectly(VALID IF T SEC.)