Service Manual 9. Troubleshooting

23 Installation and MaintenanceService Manual9. Malfunction IndicatorThe error code will be displayed on the wired controller and the main board of the outdoor meaning of each error, as shown in table of malfunctionThe indicator displayIndoor displayYellow lightRed lightGreen lightCompressor runsFlash onceDefrostFlash twiceH1 Anti-freezing protectionFlash 3 timesE2 IPM protectionFlash 4 timesH5AC over-current protectionFlash 5 timesE5 Over-burden protectionFlash 6 timesH4 Compressor exhaust high temperature protectionFlash 7 timesE4 Compressor overload protectionFlash 8 timesH3 Power protectionFlash 9 timesL9 EEPROM reads and write protectionFlash 11 timesLow PN voltage protectionFlash 12 timesPLOver voltage protection for PNFlash 13 timesPHPFC protectionFlash 14 timesHCPFC

If the refrigerant charging amount is too much Charge the refrigerant according to the service manual Eliminate the malfunction Eliminate the malfunction Replace the compressor End Replace the outdoor mainboard The stop duration of the unit is not enough, the high and low pressure of the system is not balanced,restart it after 3min No No No No ...

Tags:

  Refrigerant

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Advertisement

Transcription of Service Manual 9. Troubleshooting

1 23 Installation and MaintenanceService Manual9. Malfunction IndicatorThe error code will be displayed on the wired controller and the main board of the outdoor meaning of each error, as shown in table of malfunctionThe indicator displayIndoor displayYellow lightRed lightGreen lightCompressor runsFlash onceDefrostFlash twiceH1 Anti-freezing protectionFlash 3 timesE2 IPM protectionFlash 4 timesH5AC over-current protectionFlash 5 timesE5 Over-burden protectionFlash 6 timesH4 Compressor exhaust high temperature protectionFlash 7 timesE4 Compressor overload protectionFlash 8 timesH3 Power protectionFlash 9 timesL9 EEPROM reads and write protectionFlash 11 timesLow PN voltage protectionFlash 12 timesPLOver voltage protection for PNFlash 13 timesPHPFC protectionFlash 14 timesHCPFC

2 Module temperature protectionFlash 15 timesoELow pressure protectionFlash 17 timesE3 High pressure protectionFlash 18 timesE1 Limit/decline frequency(electric current)Flash 1 timesFrequency limit(exhaust)Flash 2 timesFrequency limit(Over-burden)Flash 3 timesOutdoor ambient sensor malfunctionFlash 6 timesF3 Outdoor tube sensor malfunctionFlash 5 timesF4 Exhaust sensor malfunctionFlash 7 timesF5 Attain the temperature of switch onFlash 8 timesFrequency limit(power)Flash 13 timesOutdoor fan malfunctionFlash 14 timesFrequency limit(PFC module temperature)Flash 15 timesPFC module sensor malfunctionFlash 16 timesoELiquid pipe temperature sensor malfunction of AFlash 17 times24 Installation and MaintenanceService Manual14/18K:24/28K.

3 43 Communication failure with Unit A 44 Communication failure with Unit B 45 Communication failure with Unit C 46 Communication failure with Unit D 47 Unit A freeze protection 48 Unit B freeze protection 49 Unit C freeze protection 50 Unit D freeze protection 51 Unit A overheating prevention protection 52 Unit B overheating prevention protection 53 Unit C overheating prevention protection 54 Unit D overheating prevention protection 55 Unit A communication wire misconnection or expansion valve malfunction 56 Unit B communication wire misconnection or expansion valve malfunction 57 Unit C communication wire misconnection or expansion valve malfunction 58 Unit D communication wire misconnection or expansion valve malfunction Note: discharge the position in below pictures with discharge resistance after open the top cover and check if the voltage is below 20V with universal meter, then begin to check.

4 1 IPM protection malfunction: Main checking point: If the input voltage of the unit is within normal range? If the connection wire of compressor is connected well? Is it loose? If the connection sequence is correct? If the resistance of compressor coil is normal? If the isolation of compressor coil with copper pipe is good? If the unit is overloaded? If the heat radiation of the unit is good? If the refrigerant charge is suitable? Flow chart: Malfunction Checking and Elimination14/18K:24/28K:43 Communication failure with Unit A 44 Communication failure with Unit B 45 Communication failure with Unit C 46 Communication failure with Unit D 47 Unit A freeze protection 48 Unit B freeze protection 49 Unit C freeze protection 50 Unit D freeze protection 51 Unit A overheating prevention protection 52 Unit B overheating prevention protection 53 Unit C overheating prevention protection 54 Unit D overheating prevention protection 55 Unit A communication wire misconnection or expansion valve malfunction

5 56 Unit B communication wire misconnection or expansion valve malfunction 57 Unit C communication wire misconnection or expansion valve malfunction 58 Unit D communication wire misconnection or expansion valve malfunction Note: discharge the position in below pictures with discharge resistance after open the top cover and check if the voltage is below 20V with universal meter, then begin to check. 1 IPM protection malfunction: Main checking point: If the input voltage of the unit is within normal range? If the connection wire of compressor is connected well? Is it loose? If the connection sequence is correct?

6 If the resistance of compressor coil is normal? If the isolation of compressor coil with copper pipe is good? If the unit is overloaded? If the heat radiation of the unit is good? If the refrigerant charge is suitable? Flow chart: Gas pipe temperature sensor malfunction of AFlash 18 timesLiquid pipe temperature sensor malfunction of BFlash 19 timesGas pipe temperature sensor malfunction of BFlash 20 timesLiquid pipe temperature sensor malfunction of CFlash 21 timesGas pipe temperature sensor malfunction of CFlash 22 timesLiquid pipe temperature sensor malfunction of DFlash 23 timesGas pipe temperature sensor malfunction of DFlash 24 timesLiquid pipe temperature sensor malfunction of EFlash 25 timesGas pipe temperature sensor malfunction of EFlash 26 timesExit of the condenser tube sensor malfunctionFlash 27 timesCorrespondence

7 Is normalFlash 7 times(n=indoor unit number)Communication failure between indoor unit and outdoor unit Often bright(indoor unit all Communication failure)Indoor ambient sensor malfunctionF1 Indoor evaporate sensor malfunctionF2 Mode conflictE7 Accept fluorine modeFoJumper cap malfunction protectionC5 Anti-freezing protectionFH25 Installation and MaintenanceService ManualEnergize the unitIf the above cases are existed?Test the isolation impedancebetween the three phases of the compressor and thecopper pipeMalfunction is eliminatedEndIf the wire of compressor is connected well and correctly?Correct according to the Service Manual and then energize the unit to operateTest the resistance betweenthe three phases Reconnect the wire of thecompressor according to the correct wiring method If the resistance is normal?

8 If the resistance is above 500M ?Replace the compressorReplace the outdoor mainboard Please check: 1. if the indoor and outdoor heat exchanges are dirty, if there is obstacle to affect the radiation; 2. if the indoor and outdoor fans are running normally; 3. if the pressure of the system is too high; 4. if the refrigerant is too much which causes the high level of pressure; YesYesYesYesYesNoNoNoNoNo26 Installation and MaintenanceService Manual2. PFC protection malfunction, capacity charging malfunctionMain checking points: If the mainboard is broken;If the wiring of the induction is connected well and if the induction is broken;Flow chart:StartCheck if power supply is normalPower supply is abnormal?

9 Turn on the unitafter power supply resumes normalReplace the outdoor mainboardEndYesNoStartCheck If the power supply is normalPower supply is abnormalCheck if the outdoor induction is brokennoitcudni eht ecalpeRnekorb si noitcudni ehTReplace the outdoormainboardMalfunction is eliminatedEndTurn on the unit after thepower supply resumes tonormal situationYesYesYesNoNoNo27 Installation and MaintenanceService desynchronizing malfunctionMain checking points: If the eletric expansion valve is working normally or it is broken;If the pressure of the system is too high;If the radiation of the unit is good;Flow chart:Eliminate the malfunctionEliminate the malfunctionEliminate the malfunctionReplace the compressorEndThe unit appears desynchronizing as soon as energizing and startingThe stop duration of the compressor is longerthan 3min?

10 The wiring of the compressor is connected properly?Reconnect the wire properlyThe eletric expansion valve is broken?Replace the eletric expansion valveReplace the outdoor mainboardNoNoNoNoNoNoYesYesYesYesYesYes2 8 Installation and MaintenanceService ManualDesynchronizing happens during operationOutdoor unit is working?Unit radiation is good?EndReplace the compressorEliminate the malfunctionReplace the outdoor mainboardReplace the outdoor unitReplace the fan capacitorRefrigerant amount is too much?Input voltage is normal?connected wellCheck if fan terminal is Improve radiation situation of the unit(such as cleaningthe heat exchanger, improve ventilationTurn on the unitafter the power supply voltage resumes normalCharge refrigerant according to the Service manualYesYesYesYesYesNoNoNoNoNo29 Installation and MaintenanceService Manual4.)