Specifications are subject to change without 1 -First issue: 5: Sep. 2004No. SS2-SFC100-0100 ( )OVERVIEWThe smart Field Communicator (SFC) allows you to establish communication with a smart Field Instrument over the existing 4-20 mA DC lines on a 1:1 basis, covering the four major process variables of flow rate, pressure, temperature, and liquid With a single unit of SFC, communication can be made with the various types of smart Field Instru-ments. The SFC can be hooked up to a loop simply by con-necting the SFC to the + and - terminals of a 4-20 mA DC signal lines, without requiring to break up the loop even temporarily. The SFC is compact and can be hand-held. The SFC has an LCD display (16 characters 2 lines). The model SFC260 has a printer which provides a Area ApprovalsKEMA/ATEX CertificationModel SFC160 Intrinsic safetyII 1 G EEx ia IIC T3 (Tamb = -20 C to +50 C)Certificate 00 ATEX1074 X Electrical dataUi = 30 V, Ii = 100 mA, Pi = WCi = negligibly small, Li = negligibly smallUo = V, Io = 22 mA, Po = 40 mWCo = F, Lo = 40 mHSpecial conditions for safe use (X)See the CertificationModel SFC160 Intrinsic safetyi3aG4 (Tamb = -10 C to +50 C)Certificate ApprovalModel SFC160 Intrinsically safe for Class I, Division 1, Groups A, B, C and D.

Specifications are subject to change without notice. - 1 - First issue: Apr.1999 Rev. 5: Sep. 2004 No. SS2-SFC100-0100 (Rev.5) OVERVIEW The Smart Field Communicator (SFC) allows you to establish communication with a Smart

Tags:

  Smart

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of SFC - Industrias ControlPro

1 Specifications are subject to change without 1 -First issue: 5: Sep. 2004No. SS2-SFC100-0100 ( )OVERVIEWThe smart Field Communicator (SFC) allows you to establish communication with a smart Field Instrument over the existing 4-20 mA DC lines on a 1:1 basis, covering the four major process variables of flow rate, pressure, temperature, and liquid With a single unit of SFC, communication can be made with the various types of smart Field Instru-ments. The SFC can be hooked up to a loop simply by con-necting the SFC to the + and - terminals of a 4-20 mA DC signal lines, without requiring to break up the loop even temporarily. The SFC is compact and can be hand-held. The SFC has an LCD display (16 characters 2 lines). The model SFC260 has a printer which provides a Area ApprovalsKEMA/ATEX CertificationModel SFC160 Intrinsic safetyII 1 G EEx ia IIC T3 (Tamb = -20 C to +50 C)Certificate 00 ATEX1074 X Electrical dataUi = 30 V, Ii = 100 mA, Pi = WCi = negligibly small, Li = negligibly smallUo = V, Io = 22 mA, Po = 40 mWCo = F, Lo = 40 mHSpecial conditions for safe use (X)See the CertificationModel SFC160 Intrinsic safetyi3aG4 (Tamb = -10 C to +50 C)Certificate ApprovalModel SFC160 Intrinsically safe for Class I, Division 1, Groups A, B, C and D.

2 Ambient Temperature limit-20 C to +60 CEntity parametersVmax = V, Imax = 225 mACi = 0, Li = 0 Voc = V, Isc = mA, Po = mWModel SFC260 Nonincendive for Class I, Division 2, Groups A, B, C and D. Ambient Temperature limit-10 C to +50 CNEPSI CertificationModel SFC160 Intrinsic safetyEx ia IIC T5 (Tamb = -20 C to +60 C)Ambient Temperature for Non-explosion-protected apparatusModel SFC160: -10 C to 50 CModel SFC260: 0 C to 40 CAmbient HumidityModel SFC160: 10 to 90%RHModel SFC260: 10 to 80%RHSFCS mart Field CommunicatorModels SFC160 / SFC260No. SS2-SFC100-0100 ( )Yamatake Corporation- 2 -Terminal Voltage10-45 V DCDisplayLCD, 16 characters 2 linesKeyboardTouch keyCommunication Cable ConnectionHookup cableBattery Charger100V AC, 50 / 60 Hz115 / 120V AC, 50 / 60 Hz200 to 240V AC, 50 / 60 HzPower SourceRechargeable batteryCharge up time: 6 hoursOperable time: 24 hoursCasingMaterialABS resinColorSmoke blackTypePortable type (hand-held type)WeightModel SFC160: Approx.

3 500 gModel SFC260: Approx. 700 gAccessoriesCommunication hookup cable with alligator clipsCommunication hookup cable with easy hookupsBattery chargerRolled thermal paper (model SFC260)Communication FunctionsThe SFC provides the following communicationsCheck and change of configuration parameters Tag No. Type of output Damping time constant Range (Range can be changed without requiring to give any reference input) Pulse output Contact input/output Cold junction temperature, of operation dataInstantaneous input/output values of a smart Field Instrument can be of constant-current outputA smart Field Instrument can be set into a constant current source of 4-20mA DC to check the performance of the Zero adjustment can be made by keying in an input value equivalent to 0% of output. Zero adjustment can be made by applying an input equivalent to 0% of output to the smart Field Instrument and setting that valueDiagnosis Performance check of smart Field Instrument.

4 Abnormality check of process Configuration check Check of communication statePrinterThe model SFC260 has a 24-character printer, which allows the following:To print out date, time, Tag No., and configuration print out date, time, Tag No., and action data as follows: Configuration change events can be printed out in the order of their occurrences. To confirm the operation data, instantaneous input/output values can be printed DevicesSmart Pressure Transmitter .. ST3000 smart Temperature and Pressure Compensation Transmitter ..ST3000 smart Pressure Transmitter ..Model PTGA dvanced Temperature Transmitter .. ThermoPLUSS mart Immersion-type Liquid Level Transmitter .. ALTJ3000 smart Electromagnetic Flow Meter ..MagneW3000 PLUSS mart 2-wire Electromagnetic Flow Meter .. Model MTGS mart Valve Positioner ..SVP3000 AlphaplusYamatake CorporationNo. SS2-SFC100-0100 ( )- 3 -Figure 1 Hookup Method of SFCNote 1)The SFC can be hooked up to a 4-20mA DC loop at any point where its + and - terminals are accessi-ble, readily by means of the alligator clips or easy hooks without requiring to break up to the loop even 2) Each of the 4-20mA DC loops (2-wire type) of smart Field Instruments requires a loop power supply (24 or 42 V DC).

5 Note 3) A load resistance of 250 or more is needed between the DC power source for the loop and the SFC. For details, see Figure 2. smart P/PP TransmitterST3000 smart Pressure-Compensation TransmitterST3000 smart Gas chromatographSGC3000 smart Valve PositionerSVP3000 smart Temperature and Pressure Compensation TransmitterST3000 smart ALTJ3000 smart Electromagnetic Flowmeter MagneW3000 smart 2- wire Electromagnetic Flow meter SMT3000 Advanced Temperature Transmitter ThermoPLUSF igure 2 Supply Voltage vs. Load Resistance CharacteristicsReceiverDC power supply(24V/42V)(Note 2)(Note 3)(Note 1)(Note 1)(Note 1)250 or moreControl room sideLocal sideJunction terminalRedBlackRedBlackBlackRedS-SFCDE READDE DIRSW VERURLACT PRSCR PADTIMENON-VOLAIDBCONFCDAMPDUNITSHNEXTGS ETURVF100%LRVE0%MENUIITEMOUT-JPUTCOR-KRE CTLPREVMN7O8P9QR4S5T6X3W2V1 USTATYSPANZ0 ALPHASHIFTCLR( No )ENTER( Yes )SFC(+)(+)(-)(-)4~20mA DCSmart field voltage (DC V)Load resistance ( )Load resistance ( )Supply voltage - range0 Supply voltage (DC V)Load resistance ( )Load resistance ( )Supply voltage - range0 Supply voltage (DC V)Load resistance ( )Load resistance ( )Supply voltage - range0 Supply voltage (DC V)Load resistance ( )Load resistance ( )Supply voltage - range0 Supply voltage (DC V)Load resistance ( )Load resistance ( )Supply voltage - range0 Supply voltage (DC V)Load resistance ( )Load resistance ( )

6 Supply voltage - range- 4 -Yamatake CorporationNo. SS2-SFC100-0100 ( )MODEL SELECTIONB asic model )*1 Model SFC160 can not be modified and changed to model SFC260 after delivery.*2 Language can not be changed after No. SFC160 / SFC260--Ex SFC160-11X-XCITEMD escriptionBasic Model No. *1 smart Field Communicator (Standard type)SFC160 smart Field Communicator (with printer)SFC260(I)Display *2(Language, measuring unit) English, non-SI unit1 English, SI unit2 English, SI unit set as default3 English, inch/lb4 Japanese, SI unit only7(II)Battery Charger 100V AC, 50 / 60 Hz1115 / 120V AC, 50 / 60 Hz2200 to 240V AC, 50 / 60 Hz3(III)Explosion protectedNon-Explosion-protectedXTIIS Certified Intrinsic Safety (for model SFC160 only)HFM Approval Intrinsic Safety, Class I, Division 1 (Zone 0 and Zone 1), Group A, B,C and D (For model SFC160 only)SFM Approval Nonincendive, Class I, Division 2 (Zone 2), Group A, B, C and DNNEPSI Certified Intrinsic Safety (for model SFC160 only)CATEX Certified Intrinsic Safety (for model SFC160 only)K(IV)OptionNo optionXWithout carrying caseXWith carrying ( ) chargingconnectorCommunicationcable connectionportONOFFP ower switchModel SFC160 ONOFFP ower ( )

7 Battery chargin connectorCommunicationcable connectionport4531 Model SFC260 Totate international Building2-12-19 ShibuyaShibuya-ku, Tokyo 150-8316 JapanTel :Fax :81-3-3486-231081-3-3486-2593 This has been printed on recycled through Automatio