Example: barber

SHEET NO. SPECIFICATION SHEET FOR COOLING …

SPECIFICATION SHEET FOR COOLING TOWERSHEET HWA TECH1 / 3 Project NameCOOLING WATER SYSTEMINFORMATIONAll data set forth herein is in accordance with definitions and standards Published by the COOLING Tower * = minimum information to be filled - in by customer, other items may be specified at customer's DRAFT WATER COOLING TOWERTOWER ROUND(COUNTER FLOW) TYPEDESIGN & OPERATING CONDITIONS* Circulating Water Flow, M3 * Hot(inlet) Water Temp. C37* Cold(outlet) Water Temp. C32 Wet Bulb Temp. Inlet C27 Ambient Temp.

specification sheet for cooling tower sheet no. dae hwa tech 3 / 3 project name cooling water system mechanical equipment fans number 1 type axial flow

Tags:

  Specification, Towers

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Advertisement

Transcription of SHEET NO. SPECIFICATION SHEET FOR COOLING …

1 SPECIFICATION SHEET FOR COOLING TOWERSHEET HWA TECH1 / 3 Project NameCOOLING WATER SYSTEMINFORMATIONAll data set forth herein is in accordance with definitions and standards Published by the COOLING Tower * = minimum information to be filled - in by customer, other items may be specified at customer's DRAFT WATER COOLING TOWERTOWER ROUND(COUNTER FLOW) TYPEDESIGN & OPERATING CONDITIONS* Circulating Water Flow, M3 * Hot(inlet) Water Temp. C37* Cold(outlet) Water Temp. C32 Wet Bulb Temp. Inlet C27 Ambient Temp.

2 C-Relative Humidity %-Tower Pump Head, M-Nominal Capacity, Kcal/Hr78,000 Drift Loss, % of circurating Loss(at design), % * Tower Site(ground level,roof,etc.)GROUND* Elevation Above Sea Level, M-* Tower ExplosureNONEPHYSICAL DETAILSN umber of Cells1 Upper Body, Piece1 Center Body, Piece1 Under Body, Piece1 Overall Tower Dimension, DIA.( ) H, mm1170 1860 Water Basin Dimension, ( ), mm900 Access to Top of Tower-Shipping Weight, Kg117 Operating Weight, Kg226 DOC. : AQSIF-042-05-19 DAE HWA TECH CO., (210 x 297)

3 MmSPECIFICATION SHEET FOR COOLING TOWERSHEET HWA TECH2 / 3 Project NameCOOLING WATER SYSTEMMATERIALS OF CONSTRUCTIONF rame work Members SupportSS400+ Eliminators -Water Distribution - Type Sprinkler Tank-Motor SupportSS400+ Frame-Leg-Ladder-WATER PIPING CONSTRUCTION Water InletNumber1 Size50 AHeight INLET 100mm Water OutletNumber1 Size50 AHeight OUTLET 100mm Center pipeNumber1 Size50A Suction TankNumber-Size- SprinklerNumber1 Size50A Sprinkler PipeNumber4 Size25A DrainNumber1 Size25A OverflowNumber1 Size25A Auto.

4 Make-upNumber1 Size15A Manual Make-up Number-Size-DOC. : AQSIF-042-05-19 DAE HWA TECH CO., (210 x 297)mmSPECIFICATION SHEET FOR COOLING TOWERSHEET HWA TECH3 / 3 Project NameCOOLING WATER SYSTEMMECHANICAL EQUIPMENTFANSN umber 1 TypeAXIAL FLOWM anufacturer DAE HWA TECHD iameter( ). mm600 Number of Blades 4 Blade MaterialAL+ALLOYHub Material-Fan Speed, 1150 Air Volume, m3/min150 Fan Total Efficiency(%)65 SPEED REDUCERN umber -Type -Model -Manufacturer -Reduction Ratio -AGMA Mechanical Rating -Service Factor at Rated of Driver-No.

5 Of Reductions -DRIVEN umber 1 Kind SQUIRREL CAGE INDUCTION MOTORType MAKER Load Speed, 1200 Elec. Char - phase / cycles / volt3/60/220/380/440 "F" CLASS, IP54 Rated / 2HP x 6 PADDITIONAL DATADOC. : AQSIF-042-05-19 DAE HWA TECH CO., (210 x 297)mm