SHUNT TRIP OPERATORS - Boltswitch, Inc.

BULLETIN 104 BSHUNT trip OPERATORS suffix -STFEATURES:6208 COMMERCIAL ROADCRYSTAL LAKE, IL 60014 PHONE: (815) 459-6900 FAX: (815) 455-7788 EASE OF OPERATIONAC AND DC trip COILSACCESSORIES SIMPLE TO WIRE INHANDLE INDICATES SWITCH POSITIONHANDLE PROVIDES MANUAL CONTROLTARGET INDICATOR ON LARGER SIZESSAME DIMENSIONS AS MANUAL SWITCHESHANDLE FALLS BY GRAVITY AS SWITCH OPENSOPTIONAL KEY INTERLOCK MOUNTS BELOW HOUSINGFAST CONTACT trip IS FAST! CONSULT FACTORYO ptional Remote Close Solenoid(suffix -CST) provides a secondsolenoid for closing. Theoperator springs are charged with the switch handle for a singleclose and trip . Energizing theclose solenoid will close theswitch. Energizing the trip coilwill open the are available for 24,48, 125, or 250 VDC input.

bulletin 104b shunt trip operators suffix -st features: 6208 commercial road crystal lake, il 60014 phone: (815) 459-6900 fax: (815) 455-7788 ease of operation

Tags:

  Operator, Trip, Shunt, Shunt trip operators

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of SHUNT TRIP OPERATORS - Boltswitch, Inc.

1 BULLETIN 104 BSHUNT trip OPERATORS suffix -STFEATURES:6208 COMMERCIAL ROADCRYSTAL LAKE, IL 60014 PHONE: (815) 459-6900 FAX: (815) 455-7788 EASE OF OPERATIONAC AND DC trip COILSACCESSORIES SIMPLE TO WIRE INHANDLE INDICATES SWITCH POSITIONHANDLE PROVIDES MANUAL CONTROLTARGET INDICATOR ON LARGER SIZESSAME DIMENSIONS AS MANUAL SWITCHESHANDLE FALLS BY GRAVITY AS SWITCH OPENSOPTIONAL KEY INTERLOCK MOUNTS BELOW HOUSINGFAST CONTACT trip IS FAST! CONSULT FACTORYO ptional Remote Close Solenoid(suffix -CST) provides a secondsolenoid for closing. Theoperator springs are charged with the switch handle for a singleclose and trip . Energizing theclose solenoid will close theswitch. Energizing the trip coilwill open the are available for 24,48, 125, or 250 VDC input.

2 The coils will operate at50% undervoltage. Thecoil remains energizedapproximately 1/10second and will draw:APPLIEDVOLTAGECURRENT(AMPS) DC COILSOPTIONAL REMOTE CLOSECOIL DATAThe standard coil may be used on 120,208, 240 VAC, or with a BoltswitchCapacitor Unit (Cat. Number CAP-2). It will operate at 66 VAC. The resistanceis ohms. The coil remainsenergized approximately 1/10 secondand will draw:APPLIEDVOLTAGEHzCURRENT (AMPS)INRUSHSEALED IN120* * If control transformer is used to obtain 120 volts,it should be rated 50 VA IS OFFPHOTO OF OPTIONAL REMOTE CLOSE SOLENOIDSWITCH IS ONBoltswitch SHUNT trip OPERATORS are stored energy devices. A singleunidirectional movement of the handle closes the switch and charges anopening operator features a spiral closing spring and an independentopening spring.

3 This design results in greatly reduced handle effortwithout sacrificing blade speed. The spring guide is containedcompletely within the housing. Key interlock can be achieved within thesame switch switch blade movement is Quick Make, Quick Break andcompletely independent of handle SHUNT trip operated switches unequivocally meet NEC Article380-7. When the switch is closed, the handle is up and blocks the fusedoor. When the switch is open, the handle is down, allowing easy tripped, the handle may be used for breaking welds, as required by some design handle is trip free. The handle is not driven down, but falls to theopen position by gravity. Blocking the handle does not interfere with themechanism opening the VL, VLB, SL and SLB models have a Position Indicator featurewhich shows the true position of the 104 BPAGE 2 The main switch and branch switches shall be of the fusible bolted pressure type of ampacity as shown on thedrawings.

4 Switches shall be dead front, and equipped with Quick Make, Quick Break tease proof OPERATORS . Anon-metallic insulated bar will be used to connect the operator to the crossbar, in order to keep ground potential outof the arcing zone. The operating handle shall have provisions for padlocking in the open position with at least 600 amp and smaller shall accommodate Class J or R larger than 600 amp shall accommodate Class L or T switches 400 through 4000 amp shall have met the test requirements of UL 98 and/or UL 977, and markedsuitable for use on a circuit capable of delivering 200,000 RMS symmetrical suitable for use with Class I ground fault sensing element shall be equipped with SHUNT trip OPERATORS and shall have a current interrupting rating of 12 times the nameplate rating.

5 The operating mechanism shall be such thatat the moment when the switch contacts close, the operating mechanism shall immediately be in a condition to openthe switch contacts by the electrical tripping means without further operation, manual or bolted pressure contact switches shall be manufactured by BOLTSWITCH, INC. of Crystal Lake, SPECIFICATIONS FOR SWITCHES WITH SHUNT trip OPERATORSSHUNT trip OPERATORSBULLETIN 104 BUL PERFORMANCE REQUIREMENTSA brief description of some of the tests required by the Underwriters Laboratories, Inc., prior to listingswitches with electrical trip mechanisms, are as follows: trip at 75% of coil rating; trip at 55%of coil rating if intended for use withground fault sensing break operations at 10 times ratedcurrent, at rated voltage; 3 breakoperations at 12 times rated currentat rated voltage if intended for usewith Class I ground fault sensingequipment without load endurance test operations:OPERATION:CIRCUITOPENING:ENDU RANCE:SWITCH RATING IN AMPERESNUMBER OFOPERATIONS4006008001200100100505030-12 00 AMP SWITCHES (UL 98) trip at 75% of coil rating; trip at 55%of coil rating if intended for use withground fault sensing equipment.

6 Tripat 85% of coil rating if intended to bepowered from independent break operations at 10 times ratedcurrent, at rated voltage; 3 breakoperations at 12 times rated currentat rated voltage if intended for usewith Class I ground fault sensingequipment without load endurance test operations:OPERATION:CIRCUITOPENING:ENDU RANCE:SWITCH RATING IN AMPERESNUMBER OFOPERATIONS80012001600-25003000-4000350 250200100800-4000 AMP SWITCHES (UL 977)The operating mechanism of an electrically tripped switch shall be such that when the switch contacts are closed, the mechanism shallimmediately be in a condition to open by the electrical tripping means without further operation, manual or :Boltswitch has passed all of the required UL tests for electrically tripped switches suitable for use with Class I ground fault sensingelement without 36208 COMMERCIAL ROAD CRYSTAL LAKE, IL 60014 NOVEMBER 2007H:\ART-CAT\BUL-104B\