2 YASKAWA ELECTRIC SIEP c710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual259 MEMOBUS/MODBUS CONFIGURATION .. COMMUNICATION SPECIFICATIONS .. COMMUNICATION TERMINAL RESISTANCE .. CONNECTING A PLC .. MEMOBUS/MODBUS PARAMETERS .. RELATED PARAMETERS .. MESSAGE FORMAT .. COMMAND/RESPONSE MESSAGE FORMAT.. MEMOBUS/MODBUS DATA TABLE.. ENTER COMMAND .. ERROR CODES .. SLAVE NOT RESPONDING.. SELF-DIAGNOSTICS .. 284260 YASKAWA ELECTRICSIEP c710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming MEMOBUS/Modbus ConfigurationYaskawa drives can be controlled with a PLC using the MEMOBUS/Modbus protocol to conduct serial communication can be configured using one master (PLC) and a maximum of 31 slaves.

YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual 263 2.4 Connecting a PLC MEMOBUS/Modbus Communications 2 2.4 Connecting a PLC Follow the instructions below to connect the drive to a PLC. 1. With the power shut off, connect the communications cable to the drive and PLC.

Tags:

  Ispe, Siepc71060610a, Siep c710606 10a, C710606

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of SIEPC71060610A 05222007 Preliminary

1 2 YASKAWA ELECTRIC SIEP c710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual259 MEMOBUS/MODBUS CONFIGURATION .. COMMUNICATION SPECIFICATIONS .. COMMUNICATION TERMINAL RESISTANCE .. CONNECTING A PLC .. MEMOBUS/MODBUS PARAMETERS .. RELATED PARAMETERS .. MESSAGE FORMAT .. COMMAND/RESPONSE MESSAGE FORMAT.. MEMOBUS/MODBUS DATA TABLE.. ENTER COMMAND .. ERROR CODES .. SLAVE NOT RESPONDING.. SELF-DIAGNOSTICS .. 284260 YASKAWA ELECTRICSIEP c710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming MEMOBUS/Modbus ConfigurationYaskawa drives can be controlled with a PLC using the MEMOBUS/Modbus protocol to conduct serial communication can be configured using one master (PLC) and a maximum of 31 slaves.

2 Serial communication between master and slave are normally started by the master and the slaves respond. The master performs serial communications with only one slave at a time. The address or node for each slave must be set beforehand so that the master can perform serial communications using that address. A slave that receives a command from the master performs the specified function and sends a response back to the Figure Connecting Multiple Drives to a PLCPLC (MEMOCON SERIES OR OTHER)DRIVEDRIVEDRIVEYASKAWA ELECTRIC SIEP c710606 10A YASKAWA AC Drive - V1000 PRELIM.

3 Programming Communication SpecificationsMEMOBUS/Modbus SpecificationsMEMOBUS/Modbus specifications appear in the following table:ItemSpecificationsInterfaceRS-422, RS-485 Communications CycleAsynchronous (Start-stop synchronization)Communication ParametersCommunication Speeds Available12, 24, 48, 96, 192, 384, 576, 768, 1152 kbpsData length8 bits (fixed)ParitySelect even, odd, or bit1 bit (fixed)ProtocolMEMOBUS/Modbus (using RTU mode only)Max Number of Connections31 drives (using RS-485)262 YASKAWA ELECTRICSIEP c710606 10A YASKAWA AC Drive - V1000 PRELIM.

4 Programming Communication Terminal Terminal ResistanceThe MEMOBUS communication uses the following terminals: S+, S-, R+, and R-. Enable the terminating resistance by setting pin 1 of DIP switch S2 to the ON Figure Serial Communications Terminal and DIP Switch S2 Note:Separate the communications cables from the main circuit cables and other wiring and power cables. Use shielded cables for the communications cables, and properly shielded clamps to prevent problems with noise. When using RS-485 communications, connect S+ to R+, and S- to R- as shown in the diagram Figure RS-485 Terminal WiringS1S2S3S4S5S6S7 HC SC H1 RPR+ R S+ S IGP1P2 PC A1A2+V AC AM AC MPMCMBMAR+ R S+ S IGRS-422A or RS-485R+R-DIPswitchS2terminal resistance (1/2 W 110 W)S+S-+-DIP switch S2 in the ON position)OFFONR+R S+S IGYASKAWA ELECTRIC SIEP c710606 10A YASKAWA AC Drive - V1000 PRELIM.

5 Programming Connecting a PLCMEMOBUS/Modbus a PLCF ollow the instructions below to connect the drive to a With the power shut off, connect the communications cable to the drive and Switch the power Set the parameters need for serial communications (H5-01 through H5-12) using the LED Shut the power off, waiting until the display on the LED operator goes out Turn the power back The drive is now ready to begin communicating with the :A timer should be set to watch how long it takes for the slave drive(s) to respond to the master.

6 If no response is received with in a certain amount of time, the master should try resending the ELECTRICSIEP c710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming MEMOBUS/Modbus Parameters MEMOBUS/Modbus Parameters H5-01: Drive Node AddressThis parameter tells the PLC what the node address is for the individual drive.*If the address is set to 0, no response will be provided during serial communciations to work, each individual slave drive must be assigned a unique node address. Setting H5-01 to any value besides 0 assigns the drive its address in the network.

7 Slave address don't need to be assigned in sequential order, but each address needs to be unique so that no two drives have the same address. The power to the drive needs to be cycled after setting the address for the node address to take affect. H5-02: Communication Speed Selection H5-03: Communication Parity SelectionThese parameters set the communication speed and the RangeDefaultMEMOBUS AddressH5-01 Drive Node AddressSelects drive station node number (address) for MEMOBUS/Modbus terminals R+, R-, S+, S-. Cycle power for the setting to take to 20 H* RangeDefaultMEMOBUSA ddressH5-02 Communication Speed SelectionSelects the baud rate for MEMOBUS/Modbus terminals R+, R-, S+ and S.

8 Cycle power for the setting to take : 1200 bps1: 2400 bps2: 4800 bps3: 9600 bps4: 19200 bps5: 38400 bps6: 57600 bps7: 76800 bps8: 115200 bps0 to MEMOBUS/Modbus ParametersYASKAWA ELECTRIC SIEP c710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual 265 MEMOBUS/Modbus Communications2 Detailed DescriptionParameters H5-02 and H5-03 should be set according to the network specifications run by the master controller. Because the power to the drive needs to be cycled in order for these parameter settings to take affect, the application will have to be stopped to change these settings.

9 H5-04: Stopping Method After Communication ErrorTells the drive how it should stop the motor when a communication error occurs. H5-05: Communication Fault Detection SelectionEnables or disables the communications time-out fault (CE).If H5-05 is set to 1, a fault will occur if the master controller does not receive a response from the drive after two seconds. The power to the drive needs to be cycled for the setting in H5-05 to take affect. H5-06: Drive Transmit Wait TimeSets how long the drive should wait to send a response after it receives Parity SelectionSelects the communication parity for MEMOBUS/Modbus terminals R+, R-, S+ and S.

10 Cycle power for the setting to take : No parity1: Even parity2: Odd parity0 to RangeDefaultMEMOBUSA ddressH5-04 Stopping Method AfterCommunication Error0: Ramp to stop (decelerates according to C1-02)1: Coast to stop2: Fast-Stop3: Alarm only0 to RangeDefaultMEMOBUSA ddressH5-05 Communication Fault Detection Selection0: Disabled - A communication loss will not cause a communication : Enabled - If communication is lost for more than two seconds, a CE fault will , MEMOBUS/Modbus Parameters266 YASKAWA ELECTRICSIEP c710606 10A YASKAWA AC Drive - V1000 PRELIM.