Transcription of Solstice N40 (R-448A) Refrigerant
1 Solstice N40 (R-448A) Refrigerant LOWEST GWP, NON FLAMMABLE (A1) REPLACEMENT FOR R-404A FOR. LOW AND MEDIUM TEMPERATURE REFRIGERATION EQUIPMENT. Properties, Guidelines and Retrofits 1. Honeywell Solstice N40. Table of Contents Introduction 3. Applications 3. Physical Properties 3. Specifications 4. Servicing Considerations 4. Materials Compatibility 4. Safety & Toxicity 4. Packaging 4. Pressure vs. Temperature 5. Storage and Handling 6. Bulk and Cylinder 6. Maintenance 6. Leak Detection 6. Retrofitting Existing R-22 Systems 7. Retrofit Procedures 7. Retrofit Checklist 9. Retrofitting Existing R-404A Systems 10.
2 Retrofit Procedures 10. Retrofit Checklist 13. Recycling and Reclamation 14. Environmental Considerations 14. Available Literature/Technical Assistance 14. 2. Introduction Physical properties Honeywell Solstice N40 (a blend of HFC- 32/HFC-125/HFC-134a/. Solstice N40 (R-448A). HFO-1234yf and HFO-1234ze assigned R-448A by ASHRAE). serves as a Low GWP alternative to HFC-404A and also as a non- Class/Type Zeotropic blend ozone depleting replacement for HCFC-22 in various commercial 26%/26%/21%/7%/20%. refrigeration applications, particularly in medium and low Formula R-32/R-125/R-134a/R- temperature applications.
3 1234ze/R-1234yf Since Solstice N40 is a close match to HFC-404A and HCFC-22, Kind HFC / HFO. it also serves as a retrofit fluid in applications where HFC-404A. Appearance Colourless and HCFC-22 are used. Solstice N40 is also the best performing ODP (ODP-R11=1) 0. lower global-warming-potential Refrigerant for new supermarket installations with improved energy efficiency compared to other GWP rev 3rd/4th/5th IPCC 1300 / 1387 / 1273. HFCs. It is a better alternative to R-404A in both low- and medium- Flammability Limits ASTM E681-04. Non Flammable temperature supermarket applications since it has a higher @ 21 C.
4 Capacity and efficiency than R-404A. ASHRAE Std. 34 Safety Class A1. ATEL/ODL (kg/m3) Applications Practical limit kg/m3 Solstice N40 is well-suited as a replacement for HFC-404A. and HCFC-22 in low- and medium-temperature commercial LFL (% vol) Non flammable refrigeration applications such as supermarket freezer cases, REACH Registered display cases, reach-in coolers, transport refrigeration, and ice Units SI. machines. Solstice N40 is a direct replacement to R-404A. In Molecular weight g/mol the case of R-22 replacement, lubricants such as mineral oil and alkylbenzene that have traditionally been used with R-22 are Boiling temperature C.
5 Immiscible with Solstice N40. Miscible synthetic lubricants such as Critical temperature C. polyol esters should be used to ensure adequate oil return. Critical pressure bar Also, Solstice N40 is well suited for new installations as a Critical volume m3/kg replacement for R-404A in supermarket applications. Conversion Critical density kg/m3. existing R-404A supermarket systems to Solstice N40 will result Vapour density at boiling point kg/m3. in significant reduction in their carbon footprint, with reduction in Liquid density at 0 C kg/m3. power consumption. Liquid density at 25 C kg/m3. Solstice N40 is a blend Refrigerant .
6 It is essential that systems be Vapour density at 25 C kJ/kg K. charged with liquid from the cylinder. Vapour charging Solstice N40 may result in the wrong Refrigerant composition and could Liquid heat capacity at 25 C kJ/kg K. damage the system. A throttling valve should be used to control Vapour heat capacity at 25 C kJ/kg K. the flow of Refrigerant to the suction side to ensure that a liquid Heat of vaporisation at boiling point kJ/kg slug does not enter the compressor. For more details about Vapour pressure at 25 C kPa proper retrofitting procedures, see Servicing Considerations and Liquid thermal conductivity at 25 C W/m K.
7 Retrofitting Existing Systems in this brochure. Vapour thermal conductivity at 25 C W/m K. Liquid viscosity at 25 C Pa sec Vapour viscosity at 25 C Pa sec 3. Servicing Considerations Materials Compatibility Solstice N40 is a blend of HFC-32/HFC-125/HFC-134a/ Honeywell does not recommend the use of chlorinated solvents to HFO-1234yf/HFO-1234ze. This product was developed to be clean refrigeration systems or components. used in low and medium-temperature commercial refrigeration Desiccants applications,especially for retrofitting existing HFC-404A and HCFC-22. Desiccant driers compatible with Solstice N40 are commercially available.
8 Individual drier manufacturers should be contacted for Unlike pure fluids and azeotropes, blends boil and condense specific recommendations. at varying temperatures for a given pressure. The range over which the temperature varies is referred to as temperature glide. Compatibility of Plastics and Elastomers Solstice N40 has a moderate temperature glide between about The following table summarizes expected materials compatibility 3 K and 6 K, depending upon pressure. When dealing with data for Solstice N40. It is based on test results for the individual blends, pressure-temperature tables are presented with two Refrigerant components and R-32/R-125/ R-134a/HFO-1234yf/.
9 Pressures listed for each temperature: the dew pressure and the HFO-1234ze blends performed by Honeywell and other worldwide bubble pressure. The dew pressure is used for determining the industry organizations. system pressure when the Refrigerant is in a saturated vapour or superheated condition ( , on the suction and discharge sides This data should be used only as a guide to the compatibility of of the compressor). The bubble pressure is used for determining materials with Solstice N40. When retrofitting existing systems to the system pressure when the Refrigerant is in a saturated liquid Solstice N40, Honeywell recommends that service technicians or subcooled condition ( , at the inlet to the expansion valve or consult with original equipment manufacturers for their approved capillary tube).
10 Replacement parts. Since there are many different grades and formulations of these materials, we recommend that compatibility Solstice N40 must be only liquid charged into a system to ensure testing be performed on the specific grade of materials under proper Refrigerant composition and system performance. (See consideration when designing new systems. The rankings in Retrofit Procedures for more information.). the table should be used with caution since they are judgments based on limited samplings. Customers should consult with the manufacturer or conduct further independent testing. Safety & Toxicity Honeywell recommends reading the MSDS before using Solstice N40.